DSD-080 User Manual                                                                                    V-1.0

 

 

14

 

 

 

SCREEN 

DESCRIPTION 

MIN 

MAX 

WEAK MOT. 

LEVEL

 

WEAK MOTION LEVEL 

This parameter defines the “weak motion” 
alarm threshold. When the unit detects an 
acceleration above this level, it will give a 
weak motion alarm. 

25mg 

75mg 

DUSUK AK

Ü 

SEV.

 

LOW BATTERY VOLTAGE 

If the measured internal battery voltage is 
below this parameter, then a “low battery” 
alarm will occur. 

18V 

26V 

R1, R2, R3, R4

 

RELAY DEFINITIONS 

User defined function settings of relays  

 

 

SLD 

SOLENOID OUTPUT 

This parameter defines the characteristics of 
the solenoid output.  

 

 

 

 

 

Relay and solenoid outputs of the unit may be adjusted to various functions. 
  

Fonksiyon 

Açıklama 

RELAY OPEN 

Output is always passive. 

LOW BATTERY  

Output closed when battery is low. 

WEAK MOTION 

Output closed during a weak motion.  

WEAK MOTION 
LATCHED 

Output  closed  during  a  weak  motion.  Remains  closed 
until manually reset. 

WEAK MOTION 
SOLENOID 

Output closed every 10 seconds when a weak motion is 
detected. Continues operation until a manual reset. 

WEAK MOTION 
SIGNAL 

Output  closed  every  second  when  a  weak  motion  is 
detected. Continues operation until a manual reset. 

STRONG MOTION 

Output closed during a strong motion. 

STRONG MOTION 
LATCHED 

Output  closed  during  a  strong  motion.  Remains  closed 
until manually reset. 

STRONG MOTION 
SOLENOID 

Output  closed  every  10  seconds  when  a  strong  motion 
is detected. Continues operation until a manual reset. 

STRONG MOTION 
SIGNAL 

Output  closed  every  second  when  a  strong  motion  is 
detected. Continues operation until a manual reset. 

6.3 LIST OF PARAMETERS 

 

6.4 LIST OF FUNCTIONS 

 

Содержание DSD-080

Страница 1: ...with a battery backup 24V 1 2A h batteries are incorporated to the unit The unit provides automatic battery charging feature During long mains failures if batteries get low the unit gives audible and...

Страница 2: ...ument These are often good practices for the installation which reduce future issues For all technical queries please contact Datakom at below e mail address technical support datakom com tr REVISION...

Страница 3: ...ust be connected to phase voltage inputs in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Disconnect all power before working on equipment When the unit is conn...

Страница 4: ...N 2 3 ELECTRICAL INSTALLATION 2 4 INSTALLATION DIAGRAM 3 PUSHBUTTON FUNCTIONS 4 DISPLAYS 5 ALARMS 6 DEVICE CONFIGURATION 6 1 ENTERING THE PROGRAM MODE 6 2 CHANGING PARAMETER VALUE 6 3 LIST OF PARAMETE...

Страница 5: ...lugs to their sockets Otherwise you may destroy the socket and connector Be sure that the ambient temperature will not exceed the maximum operating temperature limit Below conditions may damage the de...

Страница 6: ...DSD 080 User Manual V 1 0 6 Dimensions 192x120x65mm WxHYxD Weight 1900g 2 INSTALLATION 2 1 DIMENSIONS 192mm...

Страница 7: ...DSD 080 User Manual V 1 0 7 The unit is designed for wall mounting Please mount on a flat surface through screw openings 2 2 MECHANICAL INSTALLATION WALL...

Страница 8: ...nected to phase voltage input in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0...

Страница 9: ...DSD 080 User Manual V 1 0 9 2 4 CONNECTION DIAGRAM...

Страница 10: ...arm relay are reset Used to navigate between menus Programming mode Increase related value Used to navigate between menus Programming mode Decrease related value HELD PRESSED TOGETHER FOR 3 SECONDS En...

Страница 11: ...it is operating normally BATTERY NORMAL LED Indicates that the battery voltage is above the Low Battery Voltage parameter LOW BATTERY LED Indicates that the battery voltage is below the Low Battery Vo...

Страница 12: ...ay outputs become active and the unit gives an audible alarm By depresing the RESET pushbutton alarms are reset and relays return to their initial position ALARM MESSAGE DESCRIPTION LOW BATTERY Occurs...

Страница 13: ...e memory and are not affected by energy failures In program mode the required parameter is selected using or pushbuttons By depressing the pushbutton the parameter modification is enabled Using and pu...

Страница 14: ...e LOW BATTERY Output closed when battery is low WEAK MOTION Output closed during a weak motion WEAK MOTION LATCHED Output closed during a weak motion Remains closed until manually reset WEAK MOTION SO...

Страница 15: ...r 4W maximum Battery charge voltage 27 5V 0 2V Battery charge current 100mA maximum Low battery voltage limit 22V 0 3V Current drain from battery 15mA max from 24VDC All relays passive Additional 6mA...

Отзывы: