Although the unit is protected against electromagnetic disturbance, excessive disturbance can affect the
operation, measurement precision and data communication quality.
Use cables of appropriate temperature range.
Use adequate cable section, at least 0.75mm
2
(AWG18).
For current transformer inputs, use at least 1.5mm
2
section (AWG15) cable.
The current transformer cable length should not exceed 1.5 meters. If longer cable is used,
increase the cable section proportionally.
Follow national rules for electrical installation.
Current transformers must have 5A output.
Supply voltage:
85-305 V AC (L1-NEUTRAL)
Supply frequency:
45-65Hz
Measurement inputs:
Voltage:
10 - 305 V AC (P-N)
20 - 530 V AC (P-P)
Current:
0.2 - 6.00 A AC
Frequency:
30 - 100 Hz
Accuracy:
Voltage:
% 0.5 + 1 digit
Current:
% 0.5 + 1 digit
Frequency:
% 0.5 + 1 digit
Power
(kW,kVAr)
:
%1.0 + 2 digit
Cos:
%2.0 + 2 digit
Measurement range:
CT range:
5
/
5A to 5000
/
5A
VT range:
0.1
/
1 to 200.0
/
1
kW range:
0.1 kW to 6.5 MW
Power consumption:
< 4 VA
Loading:
Voltage inputs:
< 0.1VA per phase
Current inputs:
< 1VA per phase
Relay output:
5A @ 250V AC
Digital input:
Active level:
5 - 30V DC or AC
Min pulse:
250ms.
Isolation:
1000V AC, 1 minute
Operating temp. range:
-
20°C to +70 °C
-
4 °F to 158°F
Max. Relative humidity:
95% non condensing
Enclosure:
Flame retardent, ROHS
compliant, high temperature ABS/PC
(UL94-V0)
Installation:
DIN rail mounted
Dimensions:
70x115x66mm (WxHxD)
Weight:
200 g (approximative)
EU Directives:
2006/95/EC (LVD)
2004/108/EC (EMC)
Reference
standards:
EN 61010 (safety)
EN 61326 (EMC)
Current Transformers must be used for current measurement.
No direct connection allowed.
Do not install the unit close to high electromagnetic noise
emitting devices like contactors, high current busbars,
switchmode power supplies and the like.
ELECTRICAL CONNECTIONS
TECHNICAL SPECIFICATIONS
Содержание DKM-407
Страница 4: ...INSTALLATION DIAGRAM...