background image

 

 

Three buttons on the front panel provide 
access to configuration and measurement 
screens.  
 

BUTTON 

FUNCTION 

 

Selects display context 

 

THD display 

 

Minimum values display 

 

Maximum values display 

 

Demand display 

 

HELD PRESSED FOR 5SEC:  

resets min-max values and 
displays minimum phase-to-
neutral voltages. 

 

 

Upper screen 

 

Increase (config.) 

 

 

Lower screen 

 

Decrease (config.) 

   

IF NO BUTTON PRESSED 
FOR 5 MINUTES:  

returns to the main display 
screen 

 

 

 

BUTTON 

FUNCTION 

 

   

In order to enter the 
configuration menu, 
hold both arrow buttons 
pressed for 2 seconds. 

 

Pressing the SET button will 
save the current parameter 
and display the next 
parameter. 

 

Holding the SET button 
pressed for 2 seconds will 
display the previous 
parameter. 

 

 

 
 

SCREEN  FUNCTION 




0:

 No action 

1:

 Reset Demand values 




0:

 No action 

1:

 Reset kWh and kVArh 

counters 




0:

 No action 

1:

 Reset hour counter 




0:

 No action 

1:

 Reset alarms

 




Default screen selection (refer user 
manual) 



Current transformer primary (xxx/5A 
format) 




Voltage transformer ratio 
(xxx.x/1 format) 



High voltage alarm limit. If set to 0 
then does not check high voltage. 



Low voltage alarm limit. If set to 0 
then does not check low voltage. 




High frequency alarm limit. If set to 0 
then does not check high frequency. 




Low frequency alarm limit. If set to 0 
then does not check low frequency. 



Overcurrent alarm limit. If set to 0 
then does not check the limit. 



High active power alarm limit. If set 
to 0 then does not check the limit. 



Low active power alarm limit. If set 
to 0 then does not check the limit. 



High reactive power alarm limit. If 
set to 0 then does not check the 
limit. 



Low reactive power alarm limit. If set 
to 0 then does not check the limit. 



High power factor alarm limit. If set 
to 0 then does not check the limit. 



Low power factor alarm limit. If set 
to 0 then does not check the limit. 




Device Modbus address (0-255) 




RS-485 baud rate 
(0=2400 / 1=4800 / 2=9600 / 
3=19200 / 4=38400 / 5=57600 / 
6=115200) 

 

 

 

PROGRAMMING 

 

PROGRAM PARAMETERS 

 

PUSHBUTTON FUNCTIONS 

 