DKM-0208 User Manual                                                                            V-1.0 

(26.10.2015) 

 

-8- 

 

 

 

 

 
 
 
 
 

SIGNAL LEDs:

 There are 8 red/green 

adjustable signal leds on the panel. 
According to the input signal and pressed 
pushbutton,leds can be on Fast Flash, 
Slow Flash, Steady On and Off states. 

FAST FLASH: At the first detection of the 
fault.

 

SLOW FLASH: Activated when the 
ACK(alarm acknowledge) pushbutton is 
pressed and if the fault is still active.  
 
STEADY ON: Activated if the fault signal 
disappears at SLOW FLASH condition. 
 
LED OFF: The alarm led turns off when 
RESET pushbutton is pressed and fault 
signal is not present. 

HORN/BELL LED:

 If the HORN relay 

turns on, the “red” led turns on. If the 
HORN relay is not on and if the BELL 

relay is on, then the “green” led turns on. 
If both relays are off then the led is off. 
  

FAIL/SAFE LED:

 If an internal fault 

condition is detected at self-test, then this 
led will turn on “red”, else it turns on 
“green”. 

HORN RELAY:

 

If any “red” alarm led 

turns on, then the horn relay will also turn 
on. The relay turns off when ACK 
pushbutton is pressed.

 

BELL RELAY:

 If any 

“green” alarm led 

turns on, then the bell relay will turn on. 
The relay turns off when ACK pushbutton 
is pressed. 

WATCHDOG RELAY:

 At startup the 

relay turns on. If the board fails, then the 
wathcdog relay turns off. 

 

 
 

3. DISPLAY AND RELAYS

 

Horn Button 

Reset Button 

Signal Leds 
      (1-8) 

Test Button 

Ack Button 

Horn/Bell Led 

Fail/Safe Led 

Alarm Labels 
        (1-8) 

Содержание DKM-0208

Страница 1: ...input is isolated from other terminals The module has two supply versions being 19 150V DC or 85 305V AC 88 400V DC When the unit detects a fault signal from an input the related alarm led becomes ac...

Страница 2: ...of fast type FF with a maximum rating of 6A Disconnect all power before working on equipment When the unit is connected to the network do not touch terminals Short circuit terminals of unused current...

Страница 3: ...INSTALATION 1 3 ELECTRICAL INSTALLATION 2 PUSHBUTTON FUNCTIONS 3 LED FUNCTIONS 4 SETTINGS 4 1 JUMPER SETTINGS 4 2 SIGNAL LED RED GREEN SETTINGS 4 3 BUZZER SETTINGS 5 MODBUS COMMUNICATION 5 1 INTRODUC...

Страница 4: ...cal connections with plugs removed from sockets then place plugs to their sockets Otherwise the sockets may get damaged Be sure that the relay outputs are not over loaded Use auxiliary contactors if n...

Страница 5: ...DKM 0208 User Manual V 1 0 26 10 2015 5 Panel Cutout Required Panel Depth 1 1 FRONT and BACK PANELS 1 2 MECHANICAL INSTALLATION...

Страница 6: ...ries with the power supply in close proximity of the unit Fuses must be of fast type FF with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0 75...

Страница 7: ...s the buzzer function can be disabled enabled By pressing the pushbutton again the module exits from the test This button is also used in settings menu If the pushbutton is pressed all leds turn on wi...

Страница 8: ...RN relay turns on the red led turns on If the HORN relay is not on and if the BELL relay is on then the green led turns on If both relays are off then the led is off FAIL SAFE LED If an internal fault...

Страница 9: ...long for 3 seconds first led flashes with the adjusted color By pressing RESET pushbutton signal leds can be selected from up to down by pressing HORN pushbutton signal leds can be selected from left...

Страница 10: ...her details of Modbus Protocol Modicon Modbus Protocol Reference Guide can be rewieved The guide can be downloaded from www modbus org docs PI_MBUS_300 pdf Supported Function Function 3 Read multiple...

Страница 11: ...signed word 1 20481 Baudrate Modbus Baudrate Value 16 BIT R O unsigned word 1 20482 Node Adress Modbus Node Adress Value 16 BIT R O unsigned word 1 20483 Jumper Value Jumper Value 16 BIT R O unsigned...

Страница 12: ...er 80dB Relay outputs 3 x 5A 250V AC Serial Port Signal Type RS 485 Protocol Modbus RTU Data Rate 9600 19200baud Isolation 1000V AC 1 minute Operating Temperature Range 20 C 70 C Storage Temperature R...