DKG-509 User Manual V-29
(23.08.2013)
- 49 -
Program Group: Sender Characteristics (password level-2)
Parameter Definition
Unit Factory
Set
Description
Fuel Level Sender Ohms -1
ohm
4
Fuel Level Sender point 1, ohm value
Fuel Level Value -1
%
0
Fuel Level Sender point 1, % value
Fuel Level Sender Ohms -2
ohm
31
Fuel Level Sender point 2, ohm value
Fuel Level Value -2
%
25
Fuel Level Sender point 2, %value
Fuel Level Sender Ohms -3
ohm
67
Fuel Level Sender point 3, ohm value
Fuel Level Value -3
%
50
Fuel Level Sender point 3, %value
Fuel Level Sender Ohms -4
ohm
110
Fuel Level Sender point 4, ohm value
Fuel Level Value -4
%
75
Fuel Level Sender point 4 %value
Fuel Level Sender Ohms -5
ohm
180
Fuel Level Sender point 5, ohm value
Fuel Level Value -5
%
100
Fuel Level Sender point 5, %value
Fuel Level Sender Ohms -6
ohm
1000
Fuel Level Sender point 6, ohm value
Fuel Level Value -6
%
100
Fuel Level Sender point 6, %value