DKG-509 User Manual V-29
(23.08.2013)
- 44 -
Program Group: Engine Parameters (continued)
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(3)
Crank Cut Frequency
Hz
10.0
When the genset frequency reaches this limit, the
engine is supposed running and the crank output will
release.
(2)
Crank Stop with Oil
Pressure
-
0
0:
no crank stop with oil pressure
1:
cranking is stopped when oil presure switch is open
or the oil pressure measured is above shutdown limit.
(2)
Crank Stop with Charge
-
0
0:
no crank stop with charge input
1:
cranking is stopped when the charge alternator
voltage is established.
(2)
Low rpm Shutdown
rpm
0
If the engine speed goes under this limit, a
GENSET
LOW SPEED
alarm is generated and the engine stops.
(2)
Low rpm Warning
rpm
0
If the engine speed goes under this limit, a
GENSET
LOW SPEED
warning is generated.
(2)
High rpm Warning
rpm
0
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
warning is generated.
(2)
High rpm Shutdown
rpm
0
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
alarm is generated and the engine
stops.
(2)
Fan turn-on temp
°C
90
If the coolant temp is above this limit then the fan relay
function will become active.
(2)
Fan turn-off temp
°C
80
If the coolant temp is below this limit then the fan relay
function will become inactive.
(2)
High Oil Temperature
Warning
°C
100
If the oil temperature measured from the analog input
goes over this limit, this will generate a HIGH
OILTEMPERATURE SENDER warning.
(2)
High Oil Temperature
Shutdown
°C
120
f the oil temperature measured from the analog input
goes over this limit, this will generate a HIGH OIL
TEMPERATURE SENDER alarm and the engine will
stop.
(2)
Oil Temp. Sender Type
-
1
This parameter selects the oil temperature sender type:
0: The sender characteristics are defined in Sender
Characteristics table.
1: VDO
2: DATCON DAH type
3: DATCON DAL type