MA1044 MAQ20-RTD31/-RTD41 Hardware User Manual
Page 17 of 38
Table 6: MAQ20-RTD31 Input Sensor Types and Ranges
Range
Standard Input
Temperature
Equivalent Counts Over/Under Range
Equivalent
Counts
Input Units
per Count
P
T
10
0
0
-200°C to +850°C
(Default)
-945 to 4016
-200°C to +850°C
-945 to 4016
0.2117°C
P
T
10
0
1
-200°C to +200°C
-4016 to 4016
-204°C to +204°C
-4095 to 4095
0.0498°C
P
T
10
0
2
-100°C to +100°C
-4016 to 4016
-102°C to +102°C
-4095 to 4095
0.0249°C
P
o
tent
iom
eter
3
0
Ω
to 5000Ω
0 to 4016
0
Ω
to 5098Ω
0 to 4095
1.245
Ω
Ni12
0
4
-80°C to +300°C
-1071 to 4016
-80°C to +300°C
-1071 to 4016
0.0747°C
and
manual. An excerpt from the MAQ20-RTD31 Address Map is shown below. Input Range is stored
starting at Address 100, Channel Enable is stored starting at Address 140, and Channel Data is
stored starting at Address 1000.
NOTE: When a module is registered in a system, addresses are offset by 2000 * R, where R is the
Registration Number. Refer to the
MAQ20 I/O Module Registration
section for further details.
Table 7: MAQ20-RTD31 Address Map Excerpt
– Module Configuration
Address Range 100 - 699 : Module Configuration
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
100
R/W
6
Input Sensor & Range
Platinum, Nickel,
Potentiometer.
Default = 0
0 to 4
INT16
119
W
1
Save to EEPROM
0 = Input Sensor, Range
0
INT16
140
R/W
8
Channel Enable
0 = Disable 1 = Enable
(default)
0 or 1
INT16
Table 8: MAQ20-RTD31 Address Map Excerpt
– Module Data
Address Range 1000 - 1699 : Module Data
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
1000
R/W
6
Channel Data
Data for each of 6
Channels
Table 14
INT16
To change the input range, write the appropriate range code to Address 100 + 2000 * R.
Channels in a module can be selectively enabled for scanning. By default, all channels are enabled.
Non-used channels may be disabled to increase sampling rate of enabled channels. To disable a
channel, write a 0 to the appropriate register starting at Address 140 + 2000 * R. To enable a channel,
write a 1 to this register.