MA1044  MAQ20-RTD31/-RTD41 Hardware User Manual

 

 

Page 9 of 38 

ALM 

Normal operation: Off 
 
Alarm Condition Detected: RED, solid lit.    

 

One or more alarms have been tripped. 

 

Read module Alarm Registers based on Alarm Configuration to determine system status 
 

 
The following troubleshooting tips can be used to further diagnose and fix system problems: 
 

 

Remove  and  reinstall  MAQ20  I/O  module  and/or  MAQ20-COMx  module  to  verify  proper 
insertion into Backbone 

 

Remove and reinstall MAQ20 I/O module into another backbone position 

 

If a Backbone extension cable is used, ensure that the connections are made correctly 

 
 

8.0    Module Identification and Status Registers 

Module identification  including  model number, serial number, date code and  firmware revision  are 
stored in module registers starting at address 0. 
 

I/O modules in a system are identified in general by their model number (MAQ20-RTD31, MAQ20-
VDN, etc.)  and uniquely by their  Serial Number printed on the side label (1234567-89). When I/O 
modules  are  installed  in  the  system,  only  a  general  identifier  is  visible  on  the  front  of  the  module 
(RTD, V, etc.). Wire tags or additional labeling applied to the module terminal block may be used for 
visible unique identification in an installed system. Additionally, the system has a utility to provide a 
visual indication of module response for identification. Any write to address 98 plus the offset based 
on the Registration Number will blink the STATUS LED on the top angled surface of the module at a 
5Hz rate for 5 seconds. 
 

The 

MAQ20-RTD31  Address  Map

  and 

MAQ20-RTD41  Address  Map

  are  found  at  the  end  of  this 

manual. An excerpt from the MAQ20-RTD41 Address Map is shown below. Module identification is 
stored starting at module register address 0, which is system register address 2000*R+100, where R 
is the module Registration Number. Refer to the 

MAQ20 I/O Module Registration

 section for further 

details. 

 

Table 2:  MAQ20-RTD41 Address Map Excerpt 

– Module Information

 

Address Range 0 - 99 : Module Information 

Start 

Address 

Read/

Write 

Number of 

Registers 

Contents 

Description 

Data Range 

Data 

type 

15 

Device Description 

MAQ20-RTD41 

Characters, 

Numbers, "-" 

and Space 

ASCII 

19 

11 

Serial Number 

S1234567-89 

Characters, 

Numbers, "-" 

and Space 

ASCII 

30 

Date Code 

D0622 (D<month><year>) 

Characters, 

Numbers 

ASCII 

35 

Firmware Rev 

Fx.xx 

Characters, 

Numbers 

and "." 

ASCII 

40 

Input Channels 

5 Input Channels 

ASCII 

41 

Output Channels 

0 Output Channels 

ASCII 

98 

Module Detect 

Any write will blink Status LED 
at 5Hz for 5 seconds 

0 to 65,535 

INT16 

Содержание MAQ20-RTD31

Страница 1: ...MAQ 20 Industrial Data Acquisition and Control System MA1044 MAQ20 RTD31 MAQ20 RTD41 Hardware User Manual ...

Страница 2: ...ce The information tables diagrams and photographs contained herein are the property of Dataforth Corporation No part of this manual may be reproduced or distributed by any means electronic mechanical or otherwise for any purpose other than the purchaser s personal use without the express written consent of Dataforth Corporation MAQ 20 is a registered trademark of Dataforth Corporation ReDAQ is a ...

Страница 3: ...ification and Status Registers 9 9 0 Building a System 11 10 0 Maintaining a System 12 11 0 Expanding a System 13 12 0 MAQ20 I O Module Registration and Reading Input Signals 14 13 0 Range Selection Channel Enable Reading Signals 16 14 0 Channel Scan Rate System Throughput Module Internal Multiplexer 19 15 0 Alarm Functions 21 16 0 Setting and Monitoring Alarms 23 17 0 Signal Average Minimum Maxim...

Страница 4: ...ing effects of noise transient power surges internal ground loops and other hazards present in industrial environments Dataforth spans the globe with more than 50 International Distributors and US Representative Companies Our customers benefit from a team of over 130 salespeople highly trained in the application of precision products for industrial markets In addition we have a team of application...

Страница 5: ...cquisition Up to 24 I O modules or 384 analog or 480 digital channels per system 19 rack width Per channel configurable for range alarms and other functions Backbone mounts within DIN rail and distributes power and communications System firmware automatically registers the installation and removal of I O modules I O modules can be mounted remotely from the Communications Module Equal load sharing ...

Страница 6: ...MAQ20 RTD and potentiometer input modules MAQ20 RTD31 and MAQ20 RTD41 interface to 3 wire sensor and 4 wire sensors MAQ20 RTD31 has 6 input channels and MAQ20 RTD41 has 5 input channels MAQ20 RTD31 interfaces to 100Ω Platinum RTDs 120Ω Nickel RTDs and Potentiometers and MAQ RTD41 interfaces to 100Ω Platinum RTDs and 120Ω Nickel RTDs Precision matched low magnitude current sources for sensor excita...

Страница 7: ...n Channel to Channel 3V Transient ANSI IEEE C37 90 1 CMR 100dB 50 60 Hz NMR 20dB 50 60 Hz Accuracy 1 0 06 span Conformity 0 035 span Resolution 0 012 span Stability Zero 50ppm C Span 35ppm C Bandwidth 3Hz Scan Rate 2 Internal Scan to Module Memory 5ms Ch 200 Ch s Module Poll Rate Channel Data from Module Memory 6ms Poll and 6 ch Poll 167 S s per channel 1000 S s total Alarms High High High Low Low...

Страница 8: ...ule Dimensions Table 1 RTD and Potentiometer Input Module Input Terminal Block Connections TERMINAL BLOCK POSITION TOP TO BOTTOM MAQ20 RTD31 INPUT CONNECTIONS MAQ20 RTD41 INPUT CONNECTIONS 1 CH0 EXC SHIELD CH0 EXC SHIELD 2 CH0 IN CH0 IN 3 CH0 IN CH0 IN 4 CH1 EXC SHIELD CH0 EXC 5 CH1 IN CH1 EXC SHIELD 6 CH1 IN CH1 IN 7 CH2 EXC SHIELD CH1 IN 8 CH2 IN CH1 EXC 9 CH2 IN CH2 EXC SHIELD 10 NC CH2 IN 11 N...

Страница 9: ...block to the sensor and wires must be the same length and gage For 2 Wire sensor connections jumper the EXC and IN terminals at the module input terminal block Shield terminals are connected to the Field Side low impedance potential and are isolated from the Bus If shield drain to system ground is required this connection must be made external to the module and must not compromise the Field Side t...

Страница 10: ...res must run the entire distance from the module input terminal block to the sensor Shield terminals are connected to the Field Side low impedance potential and are isolated from the Bus If shield drain to system ground is required this connection must be made external to the module and must not compromise the Field Side to Bus isolation barrier A capacitor with working voltage rating of 2000V or ...

Страница 11: ... Rotate the module and snap in place To remove a module reverse the steps in the installation process If space is available the clip at the bottom of the module can be squeezed by hand to release For tight installations insert a flat blade screwdriver into the recess in the clip 5 place the shaft of the screwdriver against the curved part of the clip and gently pry the clip to release 6 as shown b...

Страница 12: ... so the module location in a system can be visually identified Referring to the Address Map this module register is at address 98 offset from the module base address LED Constant On or Constant Off Abnormal operation Remove and reinstall module to force a reset Remove and reinstall module into another backbone position Determine if the module is communicating by observing the TX and RX LEDs RX TX ...

Страница 13: ...y be used for visible unique identification in an installed system Additionally the system has a utility to provide a visual indication of module response for identification Any write to address 98 plus the offset based on the Registration Number will blink the STATUS LED on the top angled surface of the module at a 5Hz rate for 5 seconds The MAQ20 RTD31 Address Map and MAQ20 RTD41 Address Map are...

Страница 14: ...e Number of Registers Contents Description Data Range Data type 1900 R W 1 Watchdog Flag 1 Watchdog Reset 0 Normal 0 or 1 INT16 1902 R W 1 I2C Error I2C TX Error Counter 0 to 65 535 INT16 1903 R W 1 I2C Error I2C RX Error Counter 0 to 65 535 INT16 1906 R W 1 Numeric Error Increments when a value received is outside of the allowed range 0 to 65 535 INT16 1908 R W 1 UART RX Error UART RX Error Count...

Страница 15: ...d to a system When system power is cycled or the system is reset I O module Registration Numbers will always remain the same If I O modules are removed while the system is powered they will be unregistered and the slots or registration numbers become available to register new modules once inserted If I O modules are removed while the system is powered and then the power is cycled the remaining mod...

Страница 16: ...onnect input output wiring to the I O module and if desired record physical position in the system 3 Repeat Step 2 for any remaining MAQ20 I O modules in the system requiring maintenance ALTERNATE MAINTENANCE PROCESS 1 With system power off remove any I O modules which are to be replaced Replace the modules with others of the same or different model numbers Modules can be installed in any vacant l...

Страница 17: ...ach module has the green Power LED on and communications activity is seen on the TX and RX LEDs Registration is complete when module TX and RX LEDs all have a repeating blink pattern Added modules have now been assigned the next available sequential Registration Numbers but in a random sequence not associated with the physical position on the backbone Modules previously installed and registered in...

Страница 18: ...ion Number 2 is assigned address space 4000 5999 and so on The starting address for the module is very important because this is the offset address that must be added to the addresses listed in the I O module register address map to know where data for that module is located within the system level address map The MAQ20 COMx Communication Module is always assigned a Registration Number of 0 and ca...

Страница 19: ... modules are displayed in the software if the Alternate Registration Processes have been used instead of the Standard Registration Processes Refer to the Building a System Maintaining a System and Expanding a System sections for further details ReDAQ Shape Software for MAQ20 presents a graphical representation of the system on the Acquire panel as shown in Figure 9 I O modules are displayed sequen...

Страница 20: ... to save the new configuration The new registration sequence is permanent across power cycles and any other system configuration as long as I O modules are not removed from or added to a system 13 0 Range Selection Channel Enable Reading Signals The MAQ20 RTD31 module has three user selectable sensor types and five user selectable input ranges The MAQ20 RTD41 module has two user selectable sensor ...

Страница 21: ...t by 2000 R where R is the Registration Number Refer to the MAQ20 I O Module Registration section for further details Table 7 MAQ20 RTD31 Address Map Excerpt Module Configuration Address Range 100 699 Module Configuration Start Address Read Write Number of Registers Contents Description Data Range Data type 100 R W 6 Input Sensor Range Platinum Nickel Potentiometer Default 0 0 to 4 INT16 119 W 1 S...

Страница 22: ...Range Table shows that Range 1 is PT100 200 C to 200 C in and Range 3 is potentiometer 0Ω to 5000Ω in Range information is also stored in registers at Addresses 1700 1800 for user read back if desired Write to register address 4000 100 4100 a data value of 1 to set Ch 0 to PT100 200 C 200 C Write to register address 4000 101 4101 a data value of 1 to set Ch 1 to PT100 200 C 200 C Write to register...

Страница 23: ...efore the scan rate for an individual module and for the channels within that module decreases The following calculation is used to determine channel scan rate for each of the 6 input channels in a MAQ20 RTD31 input module operating in a system of modules The same method applies to determine the channel scan rate of the 5 input channels in a MAQ20 RTD41 module Command response cycle 6ms Module Sca...

Страница 24: ...ses the factory default configuration of all 6 channels enabled new data is posted to the Channel Data register at a rate of 5ms Ch 6Ch 30ms System command response cycle 6ms In this system MAQ20 COM4 MAQ20 RTD31 The MAQ20 RTD31 input channel scan rate is 6ms so it is possible to read the module faster than the internal multiplexer rate In this case the same data will be reported as on the prior s...

Страница 25: ...he register the Alarm Enable register for the channel will be set to 0 and alarms that the channel has tripped will be cleared Tracking alarms follow the value of the input signal and reset automatically when the signal comes back into the valid range specified by the limit and deadband Latching alarms trip when the signal exceeds the alarm condition and remain set until reset by the user High Lim...

Страница 26: ...MA1044 MAQ20 RTD31 RTD41 Hardware User Manual Page 22 of 38 Figure 11 Alarm Parameters and Functionality ...

Страница 27: ...r a Latched alarm write a 0 to the corresponding channel bit 0 to 65 535 INT16 703 R W 1 Alarm Status High High To clear a Latched alarm write a 0 to the corresponding channel bit 0 to 65 535 INT16 704 R W 1 Alarm Enable 1 Enabled 0 Disabled See Setting Monitoring Alarms INT16 710 R W 6 Alarm Configuration Alarm Configuration See Setting Monitoring Alarms INT16 730 R W 6 High Limit High Alarm Limi...

Страница 28: ...nts a Low limit of 500 counts and a Deadband of 100 counts The MAQ20 RTD31 module with s n 1234567 89 has an address offset of 2000 3 6000 Write to register address 6000 711 6711 a value of 1000 300 1300 to set a Tracking Alarm with High Low limits Write to register address 6000 731 6731 a data value of 3000 to set the High limit Write to register address 6000 751 6751 a data value of 500 to set t...

Страница 29: ...umber of Registers Contents Description Data Range Data type 1000 R W 6 Channel Data Data for all 6 Channels Table 14 INT16 1016 R W 1 Alarm Status Status of Low Low Alarm 0 to 65 535 INT16 1017 R W 1 Alarm Status Status of Low Alarm 0 to 65 535 INT16 1018 R W 1 Alarm Status Status of High Alarm 0 to 65 535 INT16 1019 R W 1 Alarm Status Status of High High Alarm 0 to 65 535 INT16 1030 R W 6 Data M...

Страница 30: ...he settings used at the factory during manufacture It performs the standard reset actions plus resets most non volatile parameters to default settings Parameters stored in EEPROM are not affected Table 2 shows what parameters are affected for each reset Table 12 Standard Reset Reset to Default RESET TYPE PARAMETERS Standard Reset Disables all Alarms Clears Alarm Status Resets Alarm Configuration L...

Страница 31: ... register write before carrying out the reset This means the module will be unresponsive to commands for approximately 3 seconds Power On Reset POR and Brownout MAQ20 I O modules utilize a brown out detect circuit and watchdog timer to ensure reliable and predictable operation under all conditions Upon power cycle brown out detect or any extreme circumstance under which the watchdog timer expires ...

Страница 32: ...tored at the specified address ASCII 0123456789ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz INT16 16 bit integer value 0 to 65535 unless otherwise indicated Stored at a single address INT32 32 bit integer value 0 to 4294967295 unless otherwise indicated Stored at two 16 bit addresses MSB is stored at address N LSB is stored at address N 1 Module register addresses 0 to 1999 in the table be...

Страница 33: ...channel bit 0 to 65 535 INT16 702 R W 1 Alarm Status High To clear a Latched alarm write a 0 to the corresponding channel bit 0 to 65 535 INT16 703 R W 1 Alarm Status High High To clear a Latched alarm write a 0 to the corresponding channel bit 0 to 65 535 INT16 704 R W 1 Alarm Enable 1 Enabled 0 Disabled See Setting Monitoring Alarms INT16 709 W 1 Save Alarm Parmeters to EEPROM Writing 1 saves th...

Страница 34: ... W 8 Channel 1 Data Last 8 readings for Ch 1 Tables 14 15 INT16 1110 R W 8 Channel 2 Data Last 8 readings for Ch 2 Tables 14 15 INT16 1120 R W 8 Channel 3 Data Last 8 readings for Ch 3 Tables 14 15 INT16 1130 R W 8 Channel 4 Data Last 8 readings for Ch 4 Tables 14 15 INT16 1140 R W 8 Channel 5 Data Last 8 readings for Ch 5 Tables 14 15 INT16 Address Range 1700 1899 Input Ranges Start Address Read ...

Страница 35: ...se 32 767 to 32 768 INT16 1758 R 1 Range 2 Count Value of fs 32 767 to 32 768 INT16 1759 R 1 Range 2 Future Use 32 767 to 32 768 INT16 1760 R 1 Range 2 Count Value of fs 32 767 to 32 768 INT16 1770 R 1 Range 3 Engineering fs 32 767 to 32 768 INT16 1771 R 1 Range 3 Future Use 32 767 to 32 768 INT16 1772 R 1 Range 3 Engineering fs 32 767 to 32 768 INT16 1773 R 1 Range 3 Future Use 32 767 to 32 768 I...

Страница 36: ...0 R W 1 UART RX Error UART RX Error Counter Command received in invalid state 0 to 65 535 INT16 Table 14 MAQ20 RTD31 Range Table Range Standard Input Temperature Equivalent Counts Over Under Range Equivalent Counts Input Units per Count PT100 0 Default 200 C to 850 C 945 to 4016 200 C to 850 C 945 to 4016 0 2117 C PT100 1 200 C to 200 C 4016 to 4016 204 C to 204 C 4095 to 4095 0 0498 C PT100 2 100...

Страница 37: ...tored at the specified address ASCII 0123456789ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz INT16 16 bit integer value 0 to 65535 unless otherwise indicated Stored at a single address INT32 32 bit integer value 0 to 4294967295 unless otherwise indicated Stored at two 16 bit addresses MSB is stored at address N LSB is stored at address N 1 Module register addresses 0 to 1999 in the table be...

Страница 38: ...channel bit 0 to 65 535 INT16 702 R W 1 Alarm Status High To clear a Latched alarm write a 0 to the corresponding channel bit 0 to 65 535 INT16 703 R W 1 Alarm Status High High To clear a Latched alarm write a 0 to the corresponding channel bit 0 to 65 535 INT16 704 R W 1 Alarm Enable 1 Enabled 0 Disabled See Setting Monitoring Alarms INT16 709 W 1 Save Alarm Parmeters to EEPROM Writing 1 saves th...

Страница 39: ...for Ch 0 Tables 17 18 INT16 1100 R W 8 Channel 1 Data Last 8 readings for Ch 1 Tables 17 18 INT16 1110 R W 8 Channel 2 Data Last 8 readings for Ch 2 Tables 17 18 INT16 1120 R W 8 Channel 3 Data Last 8 readings for Ch 3 Tables 17 18 INT16 1130 R W 8 Channel 4 Data Last 8 readings for Ch 4 Tables 17 18 INT16 Address Range 1700 1899 Input Ranges Start Address Read Write Number of Registers Contents D...

Страница 40: ... 1 Range 2 Engineering fs 32 767 to 32 768 INT16 1753 R 1 Range 2 Future Use 32 767 to 32 768 INT16 1754 R 1 Range 2 fs fs multiplier Factor 10 X 32 767 to 32 768 INT16 1755 R 1 Range 2 Engineering Units C V etc A to Z ASCII 1756 R 1 Range 2 Engineering Units C V etc A to Z ASCII 1757 R 1 Range 2 Future Use 32 767 to 32 768 INT16 1758 R 1 Range 2 Count Value of fs 32 767 to 32 768 INT16 1759 R 1 R...

Страница 41: ...nd Too Long 0 to 65 535 INT16 1910 R W 1 UART RX Error UART RX Error Counter Command received in invalid state 0 to 65 535 INT16 Table 17 MAQ20 RTD41 Range Table Range Standard Input Temperature Equivalent Counts Over Under Range Equivalent Counts Input Units per Count PT100 0 Default 200 C to 850 C 945 to 4016 200 C to 850 C 945 to 4016 0 2117 C PT100 1 200 C to 200 C 4016 to 4016 204 C to 204 C ...

Страница 42: ...aterial Authorization instructions and form are found on the Dataforth website at RMA Instructions and Form The information provided herein is believed to be reliable however DATAFORTH assumes no responsibility for inaccuracies or omissions DATAFORTH assumes no responsibility for the use of this information and all use of such information shall be entirely at the user s own risk Application inform...

Отзывы: