DEFINITION
MIN STD MAX
“
User
”
Enter Password
The user password
should be entered.
User password is
set through
“
PASS
” parameter.
0
0
9999
“
Lern
”
Auto Setup
1
Auto setup
(3+2)
2
Step values
learning
3
CT connection
correction
0
0
3
“rCAP”
Reset error
counters and
dynamic step
values
When this
parameter is set to
1, error counters
and dynamic
values of each
step will be reset.
0
0
1
“rCnt”
Reset step
counters
When this
parameter is set to
1, switching
counters and
hours-run counters
of all steps will be
reset.
0
0
1
“FCty”
Return to factory
settings
When this
parameter is set to
1, all parameters
will return to their
factory set values.
0
0
1
DEFINITION
MIN STD MAX
“CtrF”
Current
Transformer
Primary value of
current
transformers.
Can
be
set
between 5/5A and
5000/5A.
5A
500A
5000A
“CoS”
Target Cos
ø
Target
Cosø can
be set between
capacitive 0.800
and inductive
0.800. Capacitive
power factor is
displayed as
c.800, while
inductive
Cosø is
shown as 0.800
0.800
cap.
0.999
ind.
0.800
ind.
“StEP”
Number of steps
Number of steps
can be adjusted
from 1 to 15.
1
15
15
“ProG”
Compensation
algorithm
Different
compansation
algorithms can be
chosen.
This parameter is
advised to be set
to 10 for
“smart
compe
nsation”
1
10
10
PARAMETER LIST