Chapter 6
102
Figure 38: Connecting Rate Generation SIgnals
(Shown for Counter 0; a Software Gate Is Used)
shows an example of performing an enabled rate generation operation using an
external C/T clock source with an input frequency of 4 kHz, a clock divider of 4, a low-to-high
pulse type, and a duty cycle of 75%. (The gate type does not matter for this example.) A 1 kHz
square wave is the generated output.
shows the same example using a duty cycle of
25%.
Figure 39: Example of Rate Generation Mode with a 75% Duty Cycle
STP300 Panel
TB27
Heater
Controller
Digital Ground
TB29
TB26
Digital Ground
TB25
User Counter Output 0
Signal Source
User Counter Input 0
Pulse
Output
Signal
75% duty cycle
Rate Generation
Operation Starts
External C/T
Clock
Input Signal
(4 kHz)