background image

21

To turn the system back ON , simply click the “Change” button again then select ON on the “Turn 

System ON/OFF” window then click “Submit.”

Содержание idap

Страница 1: ......

Страница 2: ...Data Aire Inc reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice...

Страница 3: ...ation Unit name Model and Cooling Type 8 B Configure a New IP address If necessary 9 C Configure Email on Alarm Notification 10 D Set Date and Time 11 E Changing User Name and Password 11 IV System Mo...

Страница 4: ...ail alarm notifications to allow immediate action as a result of a malfunction Also email logger and graphs Support SNMPv1 v2 BACnet IP and Modbus TCP IP protocols for BMS Building Monitoring System o...

Страница 5: ...boot If dap4 is reset the card will go back to the IP address that is programmed on the card 5 The factory default IP address for the idap card is as follows IP address 172 16 0 1 Net Mask 255 255 0 0...

Страница 6: ...g the IP under Eth0 IP address Main box and NetMask main box The default setting is DHCP 11 Click Submit after entering the IP address 12 It will take approximately 5 minutes for the IP address change...

Страница 7: ...NFIG MEMORIES STATUS 3 Use Select down key i then Enter key to select PCOWEB NET CONFIG the following screen will appear PCOWEB settings PCONET settings 4 Press Enter key to select PCOWEB settings opt...

Страница 8: ...nection to the card open a web browser such as Internet Ex plorer Version 10 or newer Mozilla Firefox or Google Chrome to browse the card Click on Go to Administration Area The following screen will a...

Страница 9: ...play After entering this information Press F5 on your computer to save and refresh this page your loca tion and unit name will start to appear on your System status page B Configure a New IP address I...

Страница 10: ...for sending out emails on alarm are shown above If you do not want a email sent out on a particular alarm merely uncheck clicking on the check mark box the event and send email boxes in the same row...

Страница 11: ...r there are fields for user name and pass word Finally enter the recipient s email address and SMTP server address then click on the Store the E mail configuration box Test email notifications Availab...

Страница 12: ...n messages whether the corresponding events occur or not 3 Check the email logs Example 1 with no errors Example 2 with error no emails will be sent 4 Restart idap must be reboot when finished monitor...

Страница 13: ...time clock synchronization settings will cause time clock and event logging errors To change the date and time go to dap4 menu C Clock and Scheduler To view the clock synchronizer setting click on Dat...

Страница 14: ...n 10 or newer Mozilla Firefox or Google Chrome then enter the IP address of the idap card you want to monitor into the web page address box and press Enter If the address is correct the following page...

Страница 15: ...Force unit only Equipment runtimes Optional discharge temperature and optional chilled water temperature Discharge temperature and chilled water temperature will not show if an optional discharge tem...

Страница 16: ...Log Files To view the return air temperature and humidity graphs for the past 24 hrs click on Data and Graphs menu tab on the left hand of the main system status The following screen will appear Clic...

Страница 17: ...o download a log file click on Download all the csv files and graphs or Download the latest csv file in the Data and Graphs section If you select Download the latest csv file only the latest 24 hours...

Страница 18: ...in system status page click the Configura tion tab on the left hand side then click General tab and select the View Used Free disk space this message will appear to show the used and free disk space E...

Страница 19: ...across the top of the page Consult with factory if software or firmware upgrade are needed G Change Setpoints and Deadbands To modify the system temperature humidity setpoint and deadband simply click...

Страница 20: ...be always active during the OFF mode control period and communicate with the idap card In other words idap web page must be active otherwise the system will revert to ON mode if the web page interface...

Страница 21: ...21 To turn the system back ON simply click the Change button again then select ON on the Turn System ON OFF window then click Submit...

Страница 22: ...IP BMS port 2 N A Check to make sure dap4 is online Reboot the card Missing data or data does not display properly Check the Model and Cooling type setting on Configuration General page Incorrect Loca...

Страница 23: ......

Страница 24: ......

Отзывы: