Q.  Can I use the Dart PU-E pick-up located more than 6 feet from the display?

A. The PU-E pick-up operates at a 5 Volt level, producing a 5 volt Square Wave. If noise is present on the line to or from the

pick-up, some information may be lost and the DM4000 Series may not be able to distinguish between the noise and the
relatively small 5 Volt square wave.  For this reason, we would recommend that in a “normal” environment the PU-E pick-
up not be located more than six (6) feet from the display. In a particularly noisy environment, six feet may exceed the cord
length necessary for an error free signal from the PU-E pick-up. If it is absolutely necessary to exceed six feet, or in a par-
ticularly noisy application, shielded cable should be used, connecting the shield to the COMMON terminal on the wire end
of the PU-E housing.  In such cases, the PU-E pick-up cord should not be grouped with any other wires or cords in the
shielded cable.

Q.

Can the decimal point be easily changed?

A. Yes, all decimal points are illuminated and have been masked with a black sticker to make them invisible. Remove the front

lens and remove the appropriate sticker.

Q.

How many displays can one PU-E pick-up operate at once?

A. We recommend no more than nine.

Q.

Can the DM4000 Series be switched between inputs?

A. Yes. On the PU-E pick-up, switch the “SIG” wire and leave the “COM” and “+V” connected to each pick-up (do not exceed

nine PU-E pick-ups per DM unit).

Q.

Can I tie the DM4000 Series to a computer?

A. No, there are no computer outputs available from the DM4000 Series.

Q.

What is the update time?

A. This varies with the programming of the “S” value setting, which ranges from .0167 through 4.25 seconds. The DM4004

update time = .0167  x “S” (in seconds). See SPECIFICATIONS section shown below.

Q.

How can I program “MS” in order to display RPM using a DM4004 and a PU-2E?

A. Activate switches 3 and 6 in the DM4004 [M(100) x S(36) = 3600].

SPECIFICATIONS

INPUT VOLTAGE ..............................................................  120VAC ±10% (optional 240VAC input); 50/60 Hertz

AC CURRENT - MAXIMUM ........................................................................................................................  225 mA

DECIMAL POINT ....................................................  Illuminated, covered with adhesive dots (field removable)

DISPLAY ..............................................................................................................................  1/2" red L.E.D. 4 digit

DISPLAY ACCURACY .............................................................................................................................  ± 1 count

DISPLAY RANGE .................................................................................................................................  125 to 9999

INPUT PULSE RATE .........................................................................  Minimum required: 125 pulses per minute

.....................................................................................................

Maximum allowed: 600,000 pulses per minute

MINIMUM SINE WAVE .......................................................................................................................  175 mV RMS
(that can be recognized as a signal when used with Proximity Pick-ups)

MOUNTING ..............................................................................................  Panel mounted (screws not provided)

TEMPERATURE ......................................................................................................  -10

o

 to +45

o

 C. (15

o

 to 115

o

F.)

TIME BASE ..............................................................................................................................  A.C. line frequency

TRANSDUCER POWER SUPPLY VOLTAGE ..........................................................  +5 VDC,  75 mA.  maximum

TRANSDUCER TYPES (capable of sinking 3mA) ..............  Hall-Effect, Photo-Electric, Magnetic (Proximity),

.........................................................................................

TTL, or any +5 to +24VDC NPN open collector device

UPDATE TIME .....................................................................................................  Range .0167 thru 4.25 seconds
Varies with programming of “S” value setting (DM update time = .0167 x S (in seconds))

Содержание DM4000 Series

Страница 1: ... CONTROL SERIES LTDM4 IM DM4 0501 P O Box 10 5000 W 106th Street Zionsville Indiana 46077 Phone 317 873 5211 Fax 317 873 1105 www dartcontrols com Instruction Manual Low Voltage DC Brushless Control CONTROLS ...

Страница 2: ...wer disconnect point is out of sight lock it in disconnected position and tag to prevent unexpected application of power Only a qualified electrician or service personnel should perform any electrical troubleshooting or maintenance At no time should circuit continuity be checked by shorting terminals with a screwdriver or other metal device INTRODUCTION The Dart DM4000 Series is available in two b...

Страница 3: ... SIDE OF GASKET FACING THE CUSTOMER MOUNTING PANEL CUSTOMER MOUNTING PANEL HOLE CUT OUT FOR CONTROL HOUSING APPROXIMATELY 3 675 WIDE BY 1 770 HIGH DM4000 SERIES CONTROL DM4000 SERIES FACEPLATE ASSEMBLY 2 CUT OUT MOUNTING DIMENSIONS STEP 1 Remove two screws securing red lens STEP 2 Mount the DM4000 series meter into the panel cut out Note diagram for cut out dimensions shown below Allowance for eas...

Страница 4: ...g or noisy environments a shielded cable is recommended Connect the shield to the common terminal on the ASP10 leaving the shield on the PU E end floating No other mounting screws are necessary as the cord will keep the unit from rotating The PU E gives a high signal when the north pole of the magnetic disk crosses the hall effect The signal is switched low when the south pole crosses the same res...

Страница 5: ...LD PROGRAMMING FORMULA MULTIPLIER TRIMPOT DISPLAY PANEL TIMER SWITCHES DM4000 FRONT VIEW WITHOUT LENS Example Find R We want the meter to display 15 feet per minute at a shaft speed of 1000 RPM Therefore R 15 1000 0 015 Example Use Programming Formula for the DM4004 A motor drives an auger which moves material and we want displayed lbs hr of material moved We know that at 990 RPM we move 435 lbs o...

Страница 6: ... 226 then S8 128 S7 64 S6 32 S2 2 226 STEP 6 Set the Multiplier trimpot using the M value determined in STEPS 3 4 and 5 DECIMAL POINT SELECTION All decimal points are illuminated and are covered with black adhesive backed dots If a decimal point is needed remove dot to illuminate the desired decimal point COMMONLY ASKED QUESTIONS Q Can the DM4000 Series be used above 9 999 RPM A Yes there will be ...

Страница 7: ...etween inputs A Yes On the PU E pick up switch the SIG wire and leave the COM and V connected to each pick up do not exceed nine PU E pick ups per DM unit Q Can I tie the DM4000 Series to a computer A No there are no computer outputs available from the DM4000 Series Q What is the update time A This varies with the programming of the S value setting which ranges from 0167 through 4 25 seconds The D...

Отзывы: