background image

I N S T A L L A T I O N   M A N U A L  

H 5 0 0 0   H Y B R I D   I N V E R T E R

 

R e v .   2  

© 2 0 1 7   D a r f o n   E l e c t r o n i c s   C o r p .  

1 2

  |   P a g e  

OPERATION AND DISPLAY PANEL 

 

 

 

 

 

 

 

 

LCD Display Icons and Pages Introduction 

The display panel includes two part, four function keys and a LCD display. The LCD display will show three different 
pages which include “Power flows”, “Power information” and “System setting”. 

POWER FLOWS

 

PAGE

 

 

POWER INFORMATION

 

PAGE

 

 

SYSTEM SETTING PAGE

 

 

 

ICON

 

FUNCTION 

DESCRIPTION 

 

Enter 

Confirm the selection in setting mode or 
enter setting mode.

 

ESC 

Exit   

Exits setting mode. 

 

Left 

Go to previous page, move or decreasing all 
Number. 

 

Right 

Go to next page; move; to increase all 
Number. 

ICON

 

DESCRIPTION

 

 

Represents the PV Array 

 

Represents the Battery Pack 

 

Represents the Utility 

 

Represents the Load 

 

Represents the Hybrid Inverter 

 

Indicates the Connection to a PC 

 

Indicates the Error and error codes 

 

Indicates an overload has occurred 

 

Represents the System Mode Setting 

 

Represents the System Time Setting 

Represents the System Information 

Today’s Time 

Содержание H5000

Страница 1: ...I N S T A L L A T I O N M A N U A L H 5 0 0 0 H Y B R I D I N V E R T E R R e v 2 2 0 1 7 D a r f o n E l e c t r o n i c s C o r p 1 P a g e INSTALLATION MANUAL H5000 HYBRID INVERTER ...

Страница 2: ...AC OUTPUT CONNECTION 10 Preparation 10 Connecting to the Load 10 FINAL INSTALLATION STEPS 11 TURNING THE SYSTEM ON 11 OPERATION AND DISPLAY PANEL 12 LCD Display Icons and Pages Introduction 12 System Settings 13 Warning and Fault Definition 15 MODE RULE DEFINITION 17 AUX CONTROL PORT 18 Electric parameter 18 Function Description 18 Generator Application Schematic 19 BATTERY CHARGING REQUIREMENTS 2...

Страница 3: ...electrical shock by disconnecting AC DC and battery power from the inverter before attempting any maintenance or cleaning or working on any circuits connected to the inverter Turning off controls will not reduce this risk Internal capacitors can remain charged for 5 minutes after disconnecting all sources of power WARNING Do not disassemble this inverter yourself It contains no user serviceable pa...

Страница 4: ...ed to handle continuous power from PV panels batteries and the utility When the MPP input voltage from the PV panels is within the acceptable range between 250 and 430VDC the inverter is able to feed the grid and charge the batteries This inverter is only compatible with single crystalline and polycrystalline PV panels and any other type of PV panels cannot be used Note When PV input voltage is lo...

Страница 5: ...learance to the sides and 50cm 20in to the top and bottom of the unit for proper air circulation to dissipate heat The ambient temperature must be between 0 and 50 C and relative humidity must be between 5 and 85 to ensure optimal operation Do not operate where the temperature and humidity are beyond the specified limits The unit has a Pollution Degree rating of PD2 The unit must be mounted in a p...

Страница 6: ... 2 2 0 1 7 D a r f o n E l e c t r o n i c s C o r p 6 P a g e Step 3 Using the mounting bracket as a template and install anchors as needed Step 4 Install the mounting bracket onto the wall Step 5 Hang the unit onto the mounting bracket and secure it with two screws on each side ...

Страница 7: ...40 VAC 8 AWG 0 82 Nm WARNING To reduce the risk of injury use the recommended wire size above It is very important for system safety and efficient operation to use the appropriate wire for grid utility connection WARNING To prevent the risk of electric shock make sure the ground wire is properly earthed before operating this unit whether the grid is connected or not Connecting to the Grid Utility ...

Страница 8: ...on to use the appropriate cable for battery connection Connecting the Batteries Please follow below steps to implement battery connection Step 1 Make sure the nominal voltage for the batteries is 48VDC Step 2 Strip 15mm of insulation from the battery cables and then insert the conductors into cable ring terminals Step 3 Connect the external battery cable ring terminal to the battery terminal Follo...

Страница 9: ...n do not connect any PV modules with possibility of leakage current to the inverter For example non grounded PV modules will cause leakage current to the inverter CAUTION To reduce the risk of damage due to surge Darfon recommends surge protection between the modules and the inverter CAUTION To reduce the risk of injury use the proper cable size for PV module connection CAUTION Exceeding the maxim...

Страница 10: ...use the recommended cable size above It is very important for system safety and efficient operation to use the appropriate cable for AC connection CAUTION Make sure the AC Load and AC Grid are properly connected Misconnecting them will damage to this product Connecting to the Load Step 1 Use four wires AC Cables Remove each isolation sleeve 8 mm and insert conductor into cable ring terminal Step 2...

Страница 11: ...with the eleven screws TURNING THE SYSTEM ON Step 1 Turn the on off switch located on the bottom of the case to the on position This will put the inverter into standby power If the inverter only has battery input no PV and Grid then continue to Step 2 If the inverter has PV Grid or multi input then the system will automatically start Step 2 To start the inverter hold down the Enter key located on ...

Страница 12: ...FORMATION PAGE SYSTEM SETTING PAGE ICON FUNCTION DESCRIPTION Enter Confirm the selection in setting mode or enter setting mode ESC Exit Exits setting mode Left Go to previous page move or decreasing all Number Right Go to next page move to increase all Number ICON DESCRIPTION Represents the PV Array Represents the Battery Pack Represents the Utility Represents the Load Represents the Hybrid Invert...

Страница 13: ... of Use with Battery Feed in modes are selected you will be prompted to enter the start and end times for High Price Duration in 24 hour notation Use the key to toggle between the time fields and the or keys to select the values Once the value for the last time field is set press the key You will then be prompted to enter the password Go see password section on page 14 for details B System Time Se...

Страница 14: ...ill need the factory password Please contact your Darfon representative If the password was entered correctly the display will show a Setting OK message The system will now need to be manaully restarted with the on off switch on the bottom of the inverter If the password was not correct the display will show a Setting Fail Password Incorrect message Please confirm you have the correct password and...

Страница 15: ...ction 16 Over temperature fault ON 1sec OFF 1sec 1 The internal temperature is higher than specified temperature 2 Leave system to be cooled to room temperature 3 If the error message still remains please contact your installer 17 PV input voltage exceeds the upper threshold No action 1 Check if the open circuit voltage of PV modules is higher than 500VDC 2 If PV open circuit voltage is less than ...

Страница 16: ... is less than 500VDC and the error message remains pelase contact your installer 54 Power island 1 Shut down the system completely 2 Restart the system to see if it s ok If error message still remains please contact your installer 55 Grid is disconnected 56 Power grid voltage exceeds the upper threshold 57 Power grid frequency falls below the lower threshold 58 Power grid frequency exceeds the upp...

Страница 17: ...RY Load Batt Grid PV Grid Batt PV Grid PV Batt No PV On Grid Off Grid 1 Back up default 2 1 3 1 2 3 Yes Yes Yes No 40 0 2 Residential 1 2 3 1 3 2 Yes No Yes No 40 0 3 Back up w o Feed in 2 1 X 1 2 3 Yes Yes No No 40 0 4 Residential w o Feed in 1 2 X 1 3 2 Yes No No No 40 0 5 TOU Low electricity cost 2 1 3 1 2 3 Yes Yes Yes No 40 0 High electricity cost 1 2 3 1 3 2 Yes No Yes No 40 0 6 TOU w Batt F...

Страница 18: ...esistor for generator voltage sensor Recommend series resistance is 5MΩ 240Vac 2 V sensor 3 12V 12 VDC source Max rating current 250mA 4 Ground 5 N A N A N A 6 Normal Open Dry contact Normal Open Action Close 7 Common Function Description UNIT CONDITION GEN SENSOR LEVEL 12VDC SOURCE DRY CONTACT Power Off Unit is off and no output is powered Low 0 Vdc Open Power On Grid Available Battery voltage Ba...

Страница 19: ... T A L L A T I O N M A N U A L H 5 0 0 0 H Y B R I D I N V E R T E R R e v 2 2 0 1 7 D a r f o n E l e c t r o n i c s C o r p 1 9 P a g e Generator Application Schematic Generator recommended circuit wiring ...

Страница 20: ...on is not set as one of the two back up modes If you want to change battery charging parameters please contact your Darfon representative Charging Voltage Default Value Max Charging Current 60A Floating Charging Voltage 54 0 Vdc Max Absorption Charging Voltage 56 0 Vdc Battery Overcharge Protection 58 0 Vdc Charging process based on default setting 3 stages First max charging voltage increases to ...

Страница 21: ... are two PCB boards 1 Left side Can bus board is used for parallel and display communication 2 Right side External RS485 board is used for master RS485 communicated with battery and slave RS485 communicated with application software data logger FUNCTION DESCRIPTION 1 AUX PORT FOR GENERATION FUNCTION 2 EXTERNAL DISPLAY PORT 3 PARALLELED CAN BUS PORT 4 BOOT LOAD AND COMMUNICATION JUMPER 5 USB PORT 6...

Страница 22: ...es Type A Type B and plug in the USB Type B connector to the USB port another side Type A connecting to the computer Step 3 Please make sure the jumper pins on Tx 2 and Rx 2 Step 4 The H5000 hybrid inverter need to connect the power either choices PV Battery or Grid Then use the application software setting your parameters Tx 1 Rx 1 Tx 2 Rx 2 USB TYPE B USB TYPE A USB port ...

Страница 23: ...c t r o n i c s C o r p 2 3 P a g e USE APPLICATION SOFTWARE MODIFIES PARAMETERS Preparation Download the H5000 application software from Darfonsolar website http www darfonsolar com downloads Connecting to the application software and modifies parameters Step1 Click HyBridTool folder Step2 Click HyBridRDTool ...

Страница 24: ...S T A L L A T I O N M A N U A L H 5 0 0 0 H Y B R I D I N V E R T E R R e v 2 2 0 1 7 D a r f o n E l e c t r o n i c s C o r p 2 4 P a g e Step3 Click Option and select port Step4 Click Read All Parameter ...

Страница 25: ...E l e c t r o n i c s C o r p 2 5 P a g e Step5 Modifies parameters Step6 Click one Inverter every group has its write one inverter button Step7 Click 確定 it means ok if Write successfully Step8 Click Read All Parameter and please make sure the parameters are modified correctly Device Remote Setting RTC ...

Страница 26: ...GE 0 240V 1 230V 2 220V 3 208V 4 FULL RANGE AC L1 TO L2 VOLTAGE MODEL SYSTEM ERS PV INVERTER S N 1 SYSTEM S N CODE HIGH SIDE S N 0 SYSTEM S N CODE LOW SIDE YEARS SYSTEM PRODUCT MONTH SYSTEM PRODUCT DATE SYSTEM PRODUCT INVERTER VERSION SYSTEM INVERTER VERSION DD VERSION SYSTEM DD VERSION EEPROM VERSION SYSTEM EERPOM VERSION RULE 21 ENABLE 0 DISABLE 1 ENABLE PV PARALLEL 0 DISABLE 1 ENABLE ...

Страница 27: ...NUTE ENDHOUR 0 23 HIGH PRICE PERIOD END HOUR ENDMIN 0 59 HIGH PRICE PERIOD END MINUTE MULTI MODULE SETTING 0 SINGLE 1 PARALLEL 2 THREE PHASE MALFUNCTION BATTERY TYPE 0 NO SETTING 1 LEAD ACID 2 GLODEN CROWN 3 DARFON GROWATT BATTERY CURRENT 10A 60A MAX BATTERY CHARGING CURRENT BATTERY SHUTDOWN VOLTAGE 44 0V 48 0V BATTERY CUT OFF VOLTAGE BATTERY FLOATING VOLTAGE 54 0V 58 0V BATTERY FLOATING CHARGING ...

Страница 28: ...en replacing batteries replace with the same type and number of batteries or battery packs The following precautions should be observed when working on batteries a Remove watches rings or other metal objects b Use tools with insulated handles c Wear rubber gloves and boots d Do not lay tools or metal parts on top of batteries e Disconnect charging source prior to connecting or disconnecting batter...

Страница 29: ...65 Hz AC OUTPUT TO GRID Grid Sell Current Range Depending On Operation Mode 0 to 24A 240V Grid Sell Voltage Range L L 211 to 264V 3 0V Grid Sell Frequency Range 59 4 to 60 4Hz 0 05Hz EFFICIENCY Peak PV to Grid 96 CEC weighted PV to Grid 95 5 DC BATTERY CHARGER Maximum Charge Current 60A Output Voltage Range 42 60V 48V Nominal Power Factor Corrected Charging 98 Compatible Battery Types AGM default ...

Страница 30: ...olts Nominal Voltage Phase neutral if neutral available VAC NOMINAL Phase phase 240 Volts Nominal Voltage Phase phase POUT 5 KW Active Power Output INOMINAL OUTPUT 21 Amps Nominal current per phase IMAXIMUM OUTPUT at Vlow 24 Amps Maximum output current at lowest operating voltage VOLTAGE RIDE THROUGH Trip time DESCRIPTION OV tTRIP V 120 0 166 sec Trip time when the voltage is above 288Vac IRMS max...

Страница 31: ...3 sec Capacitive Var injection power factor to Reactive Var absorption power factor range CA Rule 21 Default PF 1 0 and off Volt VAr Q V VALUE RATING UNITS DESCRIPTION Srated 5K VA Apparent Power Rating VA Prated 3 5K W Output Power Rating W Vnom 240 V Nominal AC EPS voltage V Vmin Vmax 211 264 V AC EPS voltage range with function enabled V VAr 5 Reactive Power Accuracy VAr s 500 VAr sec Maximum R...

Страница 32: ...s installation manual or applicable laws regulations 2 installations reinstallations repairs and or alterations performed by persons not authorized by Darfon 3 power surges connection to incorrect voltage or combination with incompatible components or accessories 4 misuse abuse negligence fire natural disasters force majeure or other unforeseeable circumstances outside the range of influence of Darf...

Страница 33: ...aoyuan 333 Taiwan R O C Tel 886 3 2508800 USA Office Darfon America Corp 103A Pioneer Way Mountain View CA 94041 Tel 1 650 316 6300 For more information www darfonsolar com 2017 Darfon Electronics Corp All rights reserved All specifications are subject to change without prior notice Darfon and the Darfon logo are trademarks of Darfon Electronics Corp All other trademarks are the property of the re...

Отзывы: