Torque wrench & sockets for mounting hardware 

 

Adjustable/open-ended wrench (for end caps) 

Compatibility and Capacity 

G320  micro  inverters  are  electrically  compatible  with  PV  modules  that  have  a 
voltage  range  of  24V  to  60V  and  a  maximum  wattage  of  350W  although  320 
watts  is  considered  optimal.  Please  refer  to  the  ‘Compatible  PV  Module 
Calculator’  on  the  website  at  www.darfonsolar.com  to  verify  the  PV  module  is 
electrically compatible. 
 
Before ordering the PV module, make sure the connector type is compatible with 
the micro inverter. 
 

Electrical Compatibility 

Model 

PV MPPT Voltage Range 

PV Module Connector Type 

G320 

24V to 45V 

MC4 Locking 
[Male-Anode (+), Female-Cathode (-)] 

 

Voltage and Capacity 

AC Trunk Cable 

Overcurrent Protection 

240V (Single Phase) 

10AWG 

30Amp Breaker 

19 MI 

12AWG 

20Amp Breaker 

12 MI 

 

WARNING 

DO  NOT  exceed  the  maximum 
number  of  micro  inverters  in 

an AC branch circuit as listed above. 

CAUTION 

Each  AC  branch  circuit  must  be 
protected  by  a  dedicated  circuit 

breaker  of  30A  or  less  if  using  10  AWG  trunk 
cable, or 20A or less if using 12 AWG trunk cable.

 

AC Trunk Cable 

There  are  different  types  and  options  for  AC  trunk  cables.  Depending  on  the 
orientation of the installation, the AC trunk cable can be in portrait or landscape 
format. Trunk cables can also consist of three pins (three wires) or four pins (four 
wires). Currently the four-pin AC trunk cable is used. 

 

Pin 

Wire Color 

Wire Usage 

Black 

L1 

Red 

L2 

Green 

Ground 

White 

Neutral 

Grounding Options 

Option 1: Integrated Grounding 

Integrated  grounding  eliminates  the  need  to  install  Grounding  Electrode 
Conductor  (GEC)  to  each  G320  by  completely  isolating  the  internal  DC  circuit 
from  the  AC  circuit  and  ground.  DC  ground  faults  are  detected  on  either  the 
positive and/or negative conductors of the DC circuit by a Ground Fault Detection 
Interrupter Insulation Monitor (GFDI IM).    If the GFDI IM detects a ground fault 
has occurred to the PV input, the micro inverter will automatically disconnect all 
conductors  and  cease  supplying  output  power.  In  accordance  with  NEC  690.35, 
installers  can  build  ungrounded  arrays  where  only  an  Equipment  Grounding 
Conductor  (EGC)  is  required  to  connect  or  bond  non-current  carrying  metal 
equipment together. The EGC grounding process is completed via the grounding 
connection  of  G320  4-wire  AC  cable  to  the  AC  trunk  cable.  The  PV  module  will 
still need to be grounded according to the module manufacturer’s instructions. 
 

 

 

Option 2: GEC Grounding 

Although the G320 offers integrated grounding (UL 1741 certified), it also comes 
with  a  grounding  terminal  clip  for  any  localities  that  do  not  accept  integrated 
grounding.  The  micro  inverter  manufacturer  will  not  be  held  responsible  for 
improper  installations  that  do  not  have  local  AHJ  and/or  Utility  operational 
approval.   

UP TO 19 MICROINVERTERS IN A CIRCUIT

INTEGRATED GROUNDING

(GEC NOT REQUIRED)

NEUTRAL

GROUND

JUNCTION 

BOX

METER

AC DISTRIBUTION PANEL

2-POLE 30A

CIRCUIT 

BREAKER

Black=L1

Red=L2

White=Neutral
Green=Ground

L1

L2

INTEGRATED GROUNDING

Содержание G320

Страница 1: ...G320 MI CRO I NVERTER U S E R M A N U A L...

Страница 2: ...4 PRE INSTALLATION 5 THE MICRO INVERTER 5 PV SYSTEM LAYOUT 5 PARTS AND TOOLS 5 COMPATIBILITY AND CAPACITY 6 AC TRUNK CABLE 6 GROUNDING OPTIONS 6 MICRO INVERTER LAYOUT 7 SURGE PROTECTION 7 INSTALLING T...

Страница 3: ...urns use caution when working with micro inverters Do not disconnect the DC power source from the micro inverter without first disconnecting the AC power source Both AC and DC power sources must be di...

Страница 4: ...G are bound together or DS73RS 120 where N and G are not bound together JDA D1 80 xxx VG R series http www jdauspice com uploads 2011 01 10 SPD_catalogue pdf FCC Compliance This equipment has been tes...

Страница 5: ...to tap power from the center of the circuit so 2 segments of 9 and 10 modules total 19 for each circuit This maximizes the communication signal strength to the PLC box The use of a RS485 specific cabl...

Страница 6: ...or four pins four wires Currently the four pin AC trunk cable is used Pin Wire Color Wire Usage 1 Black L1 2 Red L2 3 Green Ground 4 White Neutral Grounding Options Option 1 Integrated Grounding Inte...

Страница 7: ...eeled off the micro inverter and adhered to the installation map template where the actual position on the roof would correspond to the same panel on the layout drawing Note Tracking micro inverter lo...

Страница 8: ...icro inverter will be installed Then secure the cable on either side of the rack using cable clips or tie wraps Note the maximum pitch distance is 1050mm when modules are in portrait mode and 1700mm w...

Страница 9: ...fully inserted WARNING Correct AC grounding and short circuit protection must be provided to ensure operational safety 6 2 Repeat for all 1T AC trunk cable in the AC branch circuit 6 3 After connect...

Страница 10: ...ION WARNING Service changes to your electrical system should be carried out only by qualified electricians Do not attempt to repair this product it does not contain user serviceable parts Repairs and...

Страница 11: ...od of time If the removed micro inverter will not be replaced with another micro inverter immediately connect a sealing cap to the T branch connector TROUBLESHOOTING Troubleshooting the Micro Inverter...

Страница 12: ...contact the Technical Support at support darfon com TECHNICAL SPECIFICATIONS Micro Inverter G320 INPUT FROM PV DC Number of Panels per Inverter One Nominal Power STC of Each Panel 320 W Recommended ST...

Страница 13: ...and keep track of the micro inverters placement by serial number Peel off and use secondary serial number label on the micro inverter Installer Array Name Site Address Azimuth Date ______________ She...

Страница 14: ...1 4 NOTES Manufactured by Darfon Electronics Corp 167 Shan ying Road Gueishan Taoyuan 333 Taiwan R O C Tel 886 3 2508800 USA Office Darfon America Corp 103A Pioneer Way Mountain View CA 94041 Tel 1 65...

Отзывы: