Step2.
Verify that the AC voltages at the electrical utility connection and at the
junction box for each circuit are within the appropriate range.
Wire Connection
240V (Single Phase)
L1 to L2
211 to 264VAC
L1 to neutral
106 to 132VAC
L2 to neutral
106 to 132VAC
Step3.
Verify the PV module DC voltage is within the allowable voltage and
wattage range shown in the Technical Specifications section.
Verify the DC leads are connected correctly between the micro inverter and the
PV module.
If the micro inverter’s COMM Status LED is off, then follow these steps:
Step1.
Verify that the Power Status of the micro inverter is functioning properly.
Step2.
Verify that the data logger is uploading data to the monitoring software.
If the problem persists, contact the Technical Support at
.
TECHNICAL SPECIFICATIONS
Micro Inverter
G320
INPUT FROM PV (DC)
Number of Panels per Inverter
One
Nominal Power (STC) of Each Panel
320 W
Recommended STC Panel Power
200~350 W
Maximum Panel Voltage
60 V
Operating Voltage Range
22~60 V
MPPT Voltage Range
24~45 V
Minimum Start Voltage
24 V
Maximum Current per Panel
12 A
OUTPUT DATA (AC)
Nominal Continuous Power Rating
300 W
Nominal Frequency (Range)*
60 (57~63) Hz
Power factor
> 0.99
Total Harmonic Distortion
< 2%
Nominal Voltage / Range
240 /
211~264V
Nominal Output Current
1.25 A
Max. Units per 20A Circuit
12
EFFICIENCY
Peak Efficiency
96.5%
CEC Weighted Efficiency
96.0%
Nominal Static MPPT Efficiency
>99.5%
MECHANICAL & ELECTRICAL
3-Phase Configuration
WYE link
Night time power consumption
< 20 mW
Ambient Operating Temp. Range
-40 to 65 °C
Internal Operating Temp. Range
-40 to 85 °C
Weather-Proof Rating
NEMA 6 or IP67
Dimensions LxWxH
268 x 195 x 34 mm
Weight
1.3 kg
COMPLIANCE & COMMUNICATION
UL, FCC, IEEE Compliance
UL 1741, FCC Part 15, Class B, IEEE 1547
Communication
PLC
* Range programmable at the factory per customer request or local regulation