Danyon DA-HP-16-230 Скачать руководство пользователя страница 46

44

a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:

•  

Mechanical handling equipment is available, if required, for handling refrigerant cylinders;

•  

All personal protective equipment is available and being used correctly;

•  

The recovery process is supervised at all times by a competent person;

•  

Recovery equipment and cylinders conform to the appropriate standards.

d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer s instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from 

site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

18) Labeling
Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that 

there are labels on the equipment stating the equipment contains flammable refrigerant.

19) Recovery
When removing refrigerant from a system, either for service or decommissioning, it is recommended good practice that all refrigerants are 

removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct 

numbers of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and 

labeled for that refrigerant(i.e special cylinders for the recovery of refrigerant). Cylinders shall be completed with pressure relief valve and 

associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order 

with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a 

set of calibrated weighing scales shall be available and in good working order.
Hoses shall be completed with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in 

satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the 

event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste
Transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that 

flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the 

suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall 

be carried out safely.

20) Transportation, marking and storage for units.
Transport of equipment containing flammable refrigerants Compliance with the transport regulations.
Marking of equipment using signs Compliance with local regulations.
Disposal of equipment using flammable refrigerants Compliance with national regulations.
Storage of equipment/appliances.
The storage of equipment should be in accordance with the manufacturer’s instructions.
Storage of packed (unsold) equipment.
Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the 

refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

Содержание DA-HP-16-230

Страница 1: ...OWNER S MANUAL Air to Water Heat Pump System Tri Thermal Monobloc IMPORTANT NOTE Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it for...

Страница 2: ...REFRIGERANT 05 4 INSTALLATION SITE 05 5 INSTALLATION PRECAUTIONS 08 6 OVERVIEW OF THE UNIT 11 7 TEST RUN AND FINAL CHECKS 26 8 MAINTENANCE AND SERVICE 26 9 TURN OVER TO CUSTOMER 27 10 OPERATION AND PE...

Страница 3: ...te personal protection equipment such as gloves and safety glasses while installing the unit or carrying out maintenance activities Contact your dealer for any further assistance Improper installation...

Страница 4: ...odour The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources example open flames an operating gas appliance and...

Страница 5: ...falling from its mount Install the unit on a foundation that can withstand its weight Insufficient physical strength may cause the equipment to fall and possible cause injury Perform specified instal...

Страница 6: ...the air or where volatile flammables such as paint thinner or gasoline are handled These types of gases might cause a fire Where the air contains high levels of salt such as near the ocean Where volt...

Страница 7: ...s than 6 kg of fluorinated greenhouse gases shall not be subject to leak checks For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more but of less than...

Страница 8: ...lling the unit in a place exposed to strong wind pay special attention to the following Strong winds of 5 m sec or more blowing against the unit s air outlet causes a short circuit suction of discharg...

Страница 9: ...be sure to follow the instructions described below 4 1 2 Prevent sunshine As the outdoor temperature is measured via the monobloc air thermistor make sure to install the monobloc in the shade or a ca...

Страница 10: ...ain off too much water through the pressure relief valve Water quality should be complied with EN 98 83 EC Directives NOTE Connect the water supply to the filling valve and open the valve Make sure al...

Страница 11: ...the air inlet or aluminum fins of the unit Do not use the grips in the fan grills to avoid damage The unit is top heavy Prevent the unit from falling due to improper inclination during handling CAUTI...

Страница 12: ...in front of the outlet side 300mm A 2 In case obstacles exist in front of the air inlet In case of installing multiple units in lateral connection per row 5 2 2 In case of multiple row installation fo...

Страница 13: ...install a ground fault circuit interrupter 30 mA Failure to do it may cause electrical shock Be sure to install the required fuses or circuit breakers 6 1 1 Precautions on electrical wiring work The g...

Страница 14: ...27 28 Code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Monobloc Wire controller Stop valve Check valve Three way valve 1 SV1 Buffer tank Buffer tank electric heater IBH1 Zone 1 pump P_O Three way valve 2 S...

Страница 15: ...diagram for electrical wiring works the electric wiring diagrams are located on the service panel Install the wires and fix the cover firmly so that the cover may be fit in properly Field wiring guid...

Страница 16: ...DHW mode the slave unit only can run in heating mode DHW mode and cool mode can t run at the same time All slave units can run in cooling or heating mode and the runing mode and temperature setting ch...

Страница 17: ...after the balance tank Please ensure that the maximum interval between power on times of all units does not exceed 2 minutes If it exceeds the maximum communication detection time of the master and sl...

Страница 18: ...087 0 66 0 66 8kW 3kW heater 220 240 50 50 198 198 264 264 29 30 32 32 40 40 14 5 0 17 0 17 1 4 1 4 0 087 0 087 0 66 0 66 220 240 15 5 12kW 14kW 50 50 198 198 264 264 26 28 32 32 24 0 17 0 17 1 4 1 4...

Страница 19: ...E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 N L LPS Fuse CN32 CN33 CN31 TBH 1 SL1 2 SL2 3 1ON 4 1OFF 5 2ON 6 2OFF 7 3ON 8 IBH1 9 N 10 N 11 N 12 N 13 4ON 14 4OFF 15 3OFF 16 MV1 1 MV2 2 P_O 3 P_M 4...

Страница 20: ...N 9 N 10 N 11 N 12 N 13 N 14 N 15 AHS2 16 E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 The ground fault circuit interrupter must be a high speed type breaker of 30 mA 0 1 s Flexible cord must meet...

Страница 21: ...10 N 11 N 12 N 13 4ON 14 4OFF 15 3OFF 16 MV1 1 MV2 2 P_O 3 P_M 4 P_T 5 P_S 6 P_R 7 AHS1 8 N 9 N 10 N 11 N 12 N 13 N 14 N 15 AHS2 16 E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 0 2A load can conne...

Страница 22: ...nect the cable to the appropriate terminals as shown in the picture Fix the cable reliably a Procedure Connect the cable to the appropriate terminals as shown in the picture Fix the cable reliably SV4...

Страница 23: ...AHS1 8 N 9 N 10 N 11 N 12 N 13 N 14 N 15 AHS2 16 E 1 12V 2 B1 3 A1 4 E1 5 A 6 B 7 E 8 H1 9 H2 10 CN32 CN33 CN31 L1 L2 L3 N L1 L2 L3 N TBH 1 SL1 2 SL2 3 1ON 4 1OFF 5 2ON 6 2OFF 7 3ON 8 IBH1 9 N 10 N 1...

Страница 24: ...6 8 L N Auxiliary heat source KM5 Power supply 7 5 3 1 A1 A2 2 4 6 8 ATCO TCO 10 For backup electric heating L N CN32 CN33 CN31 TBH 1 SL1 2 SL2 3 1ON 4 1OFF 5 2ON 6 2OFF 7 3ON 8 IBH1 9 N 10 N 11 N 12...

Страница 25: ...iggnal are off the unit operates as below The unit will not operate DHW mode and the TBH is invalid disinfect function is invalid The max running time for cooling heat ing is SG RUNNING TIME then unit...

Страница 26: ...m 1N ON OFF SW3 Slave unit Master unit E4 12V B1 A1 E1 CN37 E 12V B1 A1 E1 A B E H1 H2 CN33 Power supply Please use the shielded wire and the shield layer must be grounded On Off switch Fuse Distribut...

Страница 27: ...the cord from being pulled out by external force make sure it is fixed securely Power cord Insulation tube Circular wiring terminal Power Supply Circuit Breaker Manual switch Wire Distribution Box 25...

Страница 28: ...to be carried out at regular intervals This maintenance has to be carried out by your local technician ELECTRIC SHOCK Before carrying out any maintenance or repairing activity must switch off the powe...

Страница 29: ...he refrigerant leaks in the room contact with a fire of a burner a heater or a cooker may result in a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer whe...

Страница 30: ...l not become hot immediately at the beginning of the heating operation 3 5 minutes ago depends on the indoor and outdoor temperature until the indoor heat exchanger become hot then becomes hot During...

Страница 31: ...new sensor Plate heat exchanger refrigerant liquid pipe is abnormal d5 1 Check the resistance of the sensor 2 The sensor connector is loosen Reconnect it 3 The sensor connector is wet or there is wate...

Страница 32: ...ter circuit are completely open 5 Check if the water filter needs cleaning 6 Insufficient water flow 7 Detect the amount of refrigerant Plate heat exchanger inlet water temperature is too low L5 1 Che...

Страница 33: ...the temperature Controller is reset it can be reset manually Multiple master control failure C1 1 When an internal machine is connected with two line controllers if both line controllers are set as ma...

Страница 34: ...hether the power supply voltage of the monobloc is too low resulting in abnormal reversing of the 4 way valve 3 If the fault still cannot be solved consult the manufacturer Outdoor exhaust temperature...

Страница 35: ...n plug off the connector for several times to make sure the valve is working correctly Low pressor switch protection H2 High pressure sensor failure H3 1 Check whether the sensor is connected properly...

Страница 36: ...95 996 535 DC motor Horizontal DC inverter dual rotary Fin coil R32 1400g Unit model 220 240V 1N 50Hz 8kW 17A 30A 3300W 3000W 15 5A 3600W 3000W Electric heater Rated water pressure Filter mesh Min wat...

Страница 37: ...0 1 0 3MPa Heating mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature range Operating temper...

Страница 38: ...al rotary Fin coil R32 1740g Unit model 220 240V 1N 50Hz 12kW 27 5A 29 5A 25 5A 5400W Electric heater Rated water pressure Filter mesh Min water flow flow switch Pump Type Max head Power input Expanss...

Страница 39: ...ng mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature range Operating temperature Storage te...

Страница 40: ...ual rotary Fin coil R32 1740g Unit model 380 415V 3N 50Hz 12kW 9 5A 10 0A 9 0A 5400W Electric heater Rated water pressure Filter mesh Min water flow flow switch Pump Type Max head Power input Expanssi...

Страница 41: ...ng mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature range Operating temperature Storage te...

Страница 42: ...otor Horizontal DC inverter dual rotary Fin coil R32 1740g Unit model 318 415V 3N 50Hz 5800W 9000W 22 5A 23 0A 5400W 9000W 22 0A 6200W 9000W Electric heater Rated water pressure Filter mesh Min water...

Страница 43: ...essure R5 4 20 60 C 0 1 0 3MPa Heating mode Cooling mode Domestic hot water mode 25 35 C 5 43 C 25 43 C Outlet water heating model Outlet water cooling model 25 65 C 5 20 C Water outlet temperature ra...

Страница 44: ...all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to in...

Страница 45: ...the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is...

Страница 46: ...inders shall be completed with pressure relief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recov...

Страница 47: ......

Отзывы: