11 ERROR CODES
29
When a safety device is activated, an error code will be displayed on the user interface. A list of all errors and corrective actions can be
found In the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
Abnormal outlet water temperature after
auxiliary heating
d1
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor connector is wet or there is water in. remove the water, make
the connector dry. Add waterproof adhesive
4. The sensor failure, change a new sensor.
Abnormal temperature of plate heat exchange
inlet water
d2
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor connector is wet or there is water in. Remove the water,
make the connector dry. Add waterproof adhesive.
4. The sensor failure, change a new sensor.
Abnormal temperature of plate heat exchange
outlet water
d3
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor connector is wet or there is water in. Remove the water,
make the connector dry. Add waterproof adhesive
4. The sensor failure, change a new sensor.
Plate heat exchanger refrigerant gas pipe is
abnormal
d4
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor connector is wet or there is water in. remove the water, make
the connector dry. Add waterproof adhesive
4. The sensor failure, change a new sensor.
Plate heat exchanger refrigerant liquid pipe is
abnormal
d5
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor connector is wet or there is water in. Remove the water,
make the connector dry. Add waterproof adhesive.
4. The sensor failure, change a new sensor.
Abnormal final outlet water temperature of
the system
d6
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
.3. The sensor failure
,
change a new sensor or change a new interface.
Zone 1 inlet water temperature abnormal
d7
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor failure, change a new sensor or change a new interface.
Zone 2 inlet water temperature abnormal
d8
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor failure, change a new sensor or change a new interface.
Zone 3 inlet water temperature abnormal
d9
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor failure, change a new sensor or change a new interface.
Zone 2 room temperature abnormal
dB
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor failure
,
change a new sensor or change a new interface.
Zone 1 room temperature abnormal
dA
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor failure, change a new sensor or change a new interface.
Zone 3 room temperature abnormal
dC
Err code
Malfunction or protection
The exclusion method
1. Check the resistance of the sensor.
2. The sensor connector is loosen. Reconnect it.
3. The sensor failure
,
change a new sensor or change a new interface.