4.1.10 RS485-2 MODBUS communication protocol
Function code description:
function 03 – read; function 06 – write single; function 16 – write multiple
Address Function
Code
Object
Byte
Read Only or
Read/Write
Data
0x1001 03/16/16
ON/OFF
2 bytes
Read/Write
0
- OFF
1
- ON
0x1002 03/16/16
Fan speed
2 bytes
Read/Write
1
- 1st fan speed
2
- 2nd fan speed
3
- 3rd fan speed
4
- 4th fan speed
5
- 5th fan speed
0x1003 03/16/16
Air damper close/open
2 bytes
Read/Write
0
- close
1
- open
0x1004 03/16/16
Humidity set
2 bytes
Read/Write
1~99%
0x1006 03/16/16
Air damper automatic
humidity set
2 bytes
Read/Write
1~99%
0x1008 03/16/16
Air damper automatic
close/open
2 bytes
Read/Write
0
– not in use
1
- in use
0x101B 03/16/16
Temperature set
2 bytes
Read/Write
5~35°C
0x101C 03/16/16
Working modes
2 bytes
Read/Write
0 - dehumidification
1 – dehumidification
2 – dehumidification
3 – humidification
4 – humidification
5 - humidification
0x101D 03/16/16
Humidification set
2 bytes
Read/Write
1~99
0x2001
03
Indoor temperature sensor 2 bytes
Read Only
0x2002
03
Indoor humdity sensor
2 bytes
Read Only
0x2003
03
External temperature sensor 2 bytes
Read Only
0x2004
03
External humidity sensor
2 bytes
Read Only
0x2005
03
Fan running time
2 bytes
Read Only
1=10 hours
0x2006
03
Failure
2 bytes
Read Only
Bit 0: built sensor failure
bit 1: external sensor failure
bit 2: filter alarm
bit 3: minimum absolute
humidity protection
bit 4: in defrost
0x2007
03
Dew point
2 bytes
Read Only
0x2008
03
Absolute humidity
2 bytes
Read Only