14

www.danvex.fi

• MAN

 - 

manual control mode. The dehumidifier operates 

continuously without the humidity controller being activated 
and until it is turned off by the operator

• AUTO

 - 

automatic control mode. In this mode, the dehumidifier 

is automatically controlled by the humidity controller 
depending on the set humidity value and the current values 
from the remote sensor, which is installed in the room being 
dried. The dehumidifier starts when the current humidity 
is higher than the one set in the controller and stops when 
the set humidity is reached

 

The main control element of the dehumidifier in automatic mode 

is 

humidity controller

 (Humidistat). When the dehumidifier 

is operating in automatic mode, the upper panel displays 
the current humidity in the zone of installation of the remote 
sensor, the lower panel displays the humidity set by the operator

.

Hour meter 

displays the total running time (for AD-200 and AD-550 models)

.

Ammeter

 displays the current in the recovery air heater circuit (for AD-200)

.

Thermal controller

 (Temp. Controller) regulates the temperature on the regeneration air 

PTC heater (for model AD-550). The upper digital display shows the current temperature 
of the heater, the lower display shows the set temperature

.

It is forbidden to change the preset settings of the temperature controller during

to avoid incorrect operation of the dehumidifier or its failure!

4.2 

   Humidity controller interface and settings

The humidity controller used in the dehumidifier is a versatile device and can be configured 
for use in a dehumidifier or humidifier. During the dehumidifier factory testing, the controller was 
configured to work correctly.
However, it is recommended to check the parameters at the first start and change them if necessary.

Содержание AD-200

Страница 1: ...Manual Desiccant dehumidifiers AD 200 AD 400 AD 550 rev 2 01...

Страница 2: ...1 Enclosure 7 2 3 2 Conveying air circuit 7 2 3 3 Regeneration air circuit 7 2 3 4 Rotor 7 2 3 5 Rotor drive 7 2 3 6 Safety devices 7 3 INSTALLATION 8 3 1 Introduction 8 3 2 Transport and storage 8 3...

Страница 3: ...thm of operation of the dryer components 16 5 MAINTENANCE 17 5 1 Introduction 17 5 2 Filters 17 5 3 Rotor 17 5 4 Gear motor 17 5 5 Heating device 17 5 6 Drive belt 17 6 TROUBLESHOOTING 18 6 1 Inspecti...

Страница 4: ...ion and operation instructions Content General information about the management of the dehumidification process the principle of operation and maintenance standards system errors diagnostics and troub...

Страница 5: ...he operator s responsibility for compliance with personal safety requirements at work and local safety standards During the installation and operation of equipment each employee must follow the instru...

Страница 6: ...ith relative humidity below 35 and low dew point process air preparation systems single pass airflow systems manufacturing packaging storage testing and research of pharmaceutical products production...

Страница 7: ...air passes through the filter into the rotor the moisture from the air is absorbed by the dehumidifying working sector of the rotor and the dehumidified air is expelled from the other side of the roto...

Страница 8: ...at resistant composite material The composite material is a corrugated structure filled with a highly effective desiccant forming many small air flow channels contacting the air with a large area and...

Страница 9: ...tdoor use To ensure proper maintenance for opening the service panels it is recommended that when installing the dryer leave a free space on all sides of about 800 mm The minimum width of the service...

Страница 10: ...e ground or equipped with an additional inlet filter to prevent dust and debris from being sucked in The inlet must be away from possible sources of pollution such as exhaust gases steam and harmful g...

Страница 11: ...t is particularly long or must be installed vertically it must be thermally insulated and a drain point provided at its lowest position The air duct outlet must be equipped with a metal grill or mesh...

Страница 12: ...st be located outside the circuit to be dried Dry air must be evenly distributed in the room to be dried no duct connection to the process air inlet is required Installation diagram inside the dehumid...

Страница 13: ...cal equipment must be carried out in accordance with the standards of the country in which the equipment is used and only by qualified experts It is forbidden to connect the dehumidifier to the mains...

Страница 14: ...as temperature changes may affect the measurement process The scheme for connecting an external temperature and humidity sensor to the controller is shown in the general wiring diagram of the install...

Страница 15: ...on of the remote sensor the lower panel displays the humidity set by the operator Hour meter displays the total running time for AD 200 and AD 550 models Ammeter displays the current in the recovery a...

Страница 16: ...ork until the humidity is reaches 45 then turns off When the relative humidity level in the drying zone reaches 50 the dehumidifier will restart 3rd press buttons Setting Set 20 20 Humidity Sensor Cal...

Страница 17: ...f the components is repeated manual shutdown of the dehumidifier by selecting the OFF mode middle position on the 3 position switch switching off the regeneration air heater and the working air fan th...

Страница 18: ...with two independent filter elements for filtering the working and regeneration air Filters are installed at the inlet of the air duct and provide cleaning of the air entering the dehumidifier Cleani...

Страница 19: ...iring is not loose Check for signs of damage and overheating Heater Remove debris and dust from the surface of the heater Rotor Check for signs of overheating and blockage Clean the dust from the surf...

Страница 20: ...fuse the fan is damaged rotor damaged the electric heater is damaged check the fan and its motor check the rotor drive motor and belt check the electric heater The device does not starts no power sup...

Страница 21: ...nt A 6 10 22 Power consumption kW 1 3 2 4 5 Voltage frequency 230V 50Hz 230V 50Hz 230V 50Hz Noise level dB 45 60 65 Duct size working air mm D100 D125 D125 Duct size dry air mm D100 D125 D125 Supply d...

Страница 22: ...EN IN REGEN IN AIR IN AIR IN REGEN OUT REGEN OUT 8 OVERALL AND MOUNTING DIMENSIONS DanVex AD 200 678 395 80 210 80 300 155 125 8 0 125 235 210 110 310 604 424 652 140 175 140 480 1 0 0 1 0 0 157 140 2...

Страница 23: ...22 www danvex fi 870 571 245 240 205 650 100 100 1 2 5 1 2 5 145 650 190 200 420 505 DanVex AD 550 AIR OUT AIR IN REGEN IN REGEN OUT...

Страница 24: ...ECTION DIAGRAM DanVex AD 200 Process motor Gear motor Humidistat Plug Humidity sensor Rocker Switch Heater Regen motor 230V 16A RVV3 x 1 5 mm 2 x 3m AC230V 50Hz Control Panel FY 2010 JS M3 M1 M2 MAN A...

Страница 25: ...minals for Humidity limit signal Humidistat Plug Humidity sensor Rocker Switch Communication terminals Heater Regen motor DanVex AD 400 230V 16A RVV3 x 1 5 mm 2 x 3m AC230V 50Hz Control Panel RVV2 x 0...

Страница 26: ...er Reserved terminals for Humidity limit signal Humidistat Plug Heater Rocker Switch Communication terminals Humidity sensor DanVex AD 550 AC230V 50Hz 3 x 4 mm 2 x 3m Control Panel RVV2 x 0 5 mm 2 x 1...

Отзывы: