40
1007332 ISSUE 5
OWNER/INSTALLATION MANUAL
10�1 START UP PROCEDURE AFTER WINTERISATION
1. Replace covers (if not fitted).
2. Remove front grille – using soft brush clean finned
surfaces of heat pump. Replace panel.
3. Remove plastic covers on water connections and
reconnect water piping or close drain valve.
4. Start up water circulating pump and leave running
for at least ¼ hour to establish flow and enable any
air in system to escape.
5. Replace fuses to heat pump circuit.
6. Switch on heat pump.
7. Check control thermostat is set to required pool
temperature.
8. Check daily to ensure pool water is at correct pH
and has correct chemical balance.
See section 11.0 Warranty Conditions.
10�0 WINTERISATION PROCEDURE
WARNING. Isolate machine before opening! As heat pump embodies electrical and rotational
equipment, it is recommended for your own safety that a competent person carries out the
following procedure.
(Drain Down Procedure)
ALL MODELS
Objective
To provide frost protection
To eliminate corrosion problems
To inhibit electrical components
1. Switch off electrical supply to heat pump.
2. Remove external fuses and keep in safe place away
from heat pump to prevent accidental operation of
heat pump.
3. Ensure water circulation pump is switched off.
4. Drain water from heat pump by:
a) Drain valve if fitted.
b) Disconnecting pipework to and from heat pump.
c) Remove condenser drain down cover.
d) Flush through water circuit in heat pump by using
CLEAN TAP WATER (NOT POOL WATER) via hose into
outlet connection – run for 10 minutes minimum, use
spray nozzle if available.
e) Allow to drain – fit plastic bags secured by elastic
bands over water connections.
5. Uncover electrical enclosure (page 18) and
liberally spray interior of unit, with moisture
repellent aerosol WD-40 or similar, reseal enclosure.
6. If heat pump located outside, protect from weather
by covering with VENTILATED cover. A bespoke
cover is available. Do not use plastic sheet as
condensation can occur within unit.
If this procedure is not adopted and frost or corrosion damage results
then the warranty will become invalid.
Содержание HPP-iw Series
Страница 27: ...27 1007332 ISSUE 5 Done...
Страница 42: ...42 1007332 ISSUE 5 OWNER INSTALLATION MANUAL 12 0 DECLARATION OF CONFORMITY...
Страница 43: ...43 1007332 ISSUE 5...
Страница 71: ...27 1007332 DITION 5 Done...
Страница 86: ...42 1007332 DITION 5 GUIDE D INSTALLATION ET D UTILISATION 12 0 D CLARATION DE CONFORMIT...
Страница 87: ...43 1007332 DITION 5...
Страница 115: ...27 1007332 AUSGABE 5 Done...
Страница 130: ...42 1007332 AUSGABE 5 BENUTZER INSTALLATIONSHANDBUCH 12 0 KONFORMIT TSERKL RUNG...
Страница 131: ...43 1007332 AUSGABE 5...
Страница 159: ...27 1007332 EDICI N 5 Done...
Страница 174: ...42 1007332 EDICI N 5 MANUAL DE USUARIO INSTALACI N 12 0 DECLARACI N DE CONFORMIDAD...
Страница 175: ...43 1007332 EDICI N 5...
Страница 177: ...Pompe di calore inverter HPP i HPP iw HPP i 8 12 16 HPP iw 12 16 22 28 Manuale d uso e installazione 1007332 Edizione 5...
Страница 204: ...28 1007332 EDIZIONE 5 MANUALE D USO INSTALLAZIONE Done...
Страница 219: ...43 1007332 EDIZIONE 5 12 0 DICHIARAZIONE DI CONFORMIT...
Страница 247: ...27 1007332 WYDANIE 5 Done...
Страница 262: ...42 1007332 WYDANIE 5 INSTRUKCJA OBS UGI INSTALACJI 12 0 DEKLARACJA ZGODNO CI...
Страница 263: ...43 1007332 WYDANIE 5...
Страница 264: ...Dantherm A S Marienlystvej 65 DK 7800 Skive Tel 45 96 14 37 00 info dantherm com Dantherm jest mark danthermgroup com...
Страница 291: ...27 1007332 EDI O 5 Done...
Страница 306: ...42 1007332 EDI O 5 MANUAL DE INSTALA O PROPRIET RIO 12 0 DECLARA O DE CONFORMIDADE...
Страница 307: ...43 1007332 EDI O 5...