OWNER/INSTALLATION MANUAL

> 50 cm

Plant room

Heat Pump*

Wall

Heat Pump

Possible positions of HPP-i Heat Pump

Wall

Suitable opening

Heat Pump*

>70 cm

Heat Pump

>70 cm

>250 cm

Heat Pump

The red lines represent the air inlet area

* Controls are obscured by the wall� Connect to 
optional remote control panel or Wi-Fi before 
installing the heat pump in position�

Required free areas to provide air flow to and from heat 
pumps when installed in an enclosed area or where 
required to pass air through a wall etc. Ensure the heat 
pump is sealed against the wall so the outlet air cannot 
recirculate. Ensure the hole through the wall is sealed 
to avoid the outlet air entering cavities and is smooth 
so the outlet air is not restricted.

Free area is the available area through which air can 
pass through a grille or louvres.

Minimum free areas m

2

Model

Discharge area

HPP-i 8

0.169

HPP-i 12

0.169

HPP-i 16

0.169

HPP-i 18

0.229

HPP-i 24

0.301

HPP-i 30

0.301

Содержание HPP-i 12

Страница 1: ...HPP i inverter heat pumps HPP i 8 12 16 18 24 30 Owner Installation Manual 1007332 Issue 1...

Страница 2: ...s This appliance can be used by children from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision...

Страница 3: ...PPLY 17 3 8 CONNECTING THE HEAT PUMP TO THE POWER SUPPLY 18 3 9 POOL PUMP SYNCHRONISATION TERMINALS P1 AND P2 19 3 10 INSTALLING THE OPTIONAL REMOTE CONTROLLER 20 4 0 USING YOUR HEAT PUMP 22 4 1 THE K...

Страница 4: ...ked on the heat pump Please read and follow all safety advice The refrigerant used in this heat pump is R32 This refrigerant is environmentally friendly but safety instructions must be strictly adhere...

Страница 5: ...e following location requirements must be fulfilled The heat pump must be kept away from sources of fire or naked flames The heat pump must be installed operated and stored where the floor area is lar...

Страница 6: ...warning Electric storms can damage electronic equipment Ideally the heat pump should be switched off at the mains HEAT PUMP MALFUNCTION WARNING Isolate heat pump electrically and wait 3 minutes befor...

Страница 7: ...nts may not contain an odour Appliance shall be installed operated and stored in a room with a floor area larger than Xm2 where X is the minimum area shown in section 3 2 and section 8 0 The heat pump...

Страница 8: ...t Do not lift the heat pump by the water inlet or outlet connections If this is done the titanium heat exchanger inside the heat pump could be damaged 2 2 ACCESSORIES These accessories are provided wi...

Страница 9: ...E 1 2 3 OPTIONAL ACCESSORIES The following items are additional accessories available for purchase Rubber mounting kit Pack of 4 mounts Remote controller kit for indoor installation 10m extension cabl...

Страница 10: ...application Stable inverter control system 2 5 OPERATING CONDITIONS AND RANGE Air temperature operating range HPP i 8 12 16 5 43 C HPP i 18 24 30 10 43 C Water temperature setting range Heating 18 C 4...

Страница 11: ...not block inlet or outlet grilles The heat pump absorbs energy from the air drawn through it To function effectively the heat pump must have access to the fresh air it needs Air must not recirculate...

Страница 12: ...free areas to provide air flow to and from heat pumps when installed in an enclosed area or where required to pass air through a wall etc Ensure the heat pump is sealed against the wall so the outlet...

Страница 13: ...332 ISSUE 1 350 cm Swimming pool or spa To comply with safety regulations regarding electrical installations in wet areas the heat pump must be installed at least 350cm away from the edge of the pool...

Страница 14: ...the concentration level in a room stays below their lower flammability limit LFL European standard EN378 defines requirements to remain far below the lower flammable limit in case of accidental leaka...

Страница 15: ...ted Non return valve Sanitiser or chemical dosing device If fitted Aux heater If fitted Filter Pump To waste for winterising drain down 100mm Condensate water to waste Spare port for winterising flush...

Страница 16: ...onditions Note Fittings shown at larger scale for clarity Hose Condensate adaptor Fit in hole in base of unit Approximate position shown Water out Water in 3 5 INITIAL CHECKS Start the filtration pump...

Страница 17: ...filters pump strainer boxes heat exchangers steps and handrails It is highly recommended that bonding be retrofitted to existing pools which may not be protected by this system All electrical work to...

Страница 18: ...ugh cable entry points in machine Isolator which disconnects all poles fitted within 2m and in line of sight of the heat pump L3 N Fuses MCB Earthed Power Supply 400V 50Hz L3 N P1 P2 Power terminals P...

Страница 19: ...erature the point heat pump will continue to run the filter pump and heat cool the pool If the measured temperature is within 1 C of the set temperature the filter pump will turned off until the next...

Страница 20: ...10m away Take the lid off the HPP i to gain access to the existing controller Remove the front cover Disconnect the plug from the socket on the back of the controller as shown Remove the bulkhead conn...

Страница 21: ...mperature on the remote controller to slightly higher than the pool water The HPP i should run to heat the pool immediately if the pump synchronisation is not in use or at the next sampling period if...

Страница 22: ...er is locked Symbol Designation Function On Off 1 Power On Off 2 Wi Fi Setting Lock Unlock and Heat Mode 1 Lock Unlock Screen 2 Heating mode 18 40 C 3 Cooling mode 12 30 C 4 Auto mode 12 40 C Speed Mo...

Страница 23: ...se Boost mode for initial heating f Wi Fi When the screen is on press for 3 seconds after flashes enter Wi Fi connection Connect Wi Fi on mobile phone and input password then control equipment by Wi F...

Страница 24: ...in with Existing Acount 1 Register by mobile or E mail 2 Account Registra on 1 APP Download Android please download from iOS please download from 2 Mobile or E mail registra on Obtain verification cod...

Страница 25: ...nected to the Wi Fi 1 Press for three seconds to unlock the screen 2 Press for three seconds then release after hearing the beep enter the Wi Fi code During connection the flashes When the APP connect...

Страница 26: ...26 1007332 ISSUE 1 OWNER INSTALLATION MANUAL Confirm Indicator Rapidly Blink Xiaomi_abc Confirm Add Device Pool Heat Pump 2 Click Add Device and then follow instruc ons to pair device...

Страница 27: ...27 1007332 ISSUE 1 Done...

Страница 28: ...re 1 For heat pump with Hea ng func on only Select Boost Whisper Mode The se ng temperature On O The current swimming pool water temperature Indicates the mode Boost or Whisper mode Timer Select Hea n...

Страница 29: ...rator can operate as below Inverter Check Now No ce The weather forecast is just for reference App is subject to upda ng without no ce 6 Share Devices to Your Family Members After pairing if your fami...

Страница 30: ...NER INSTALLATION MANUAL 4 4 USING THE OPTIONAL REMOTE CONTROLLER 4 5 THE KEY PAD Symbol Function Power On Off Heating Cooling Auto mode Press to start Boost mode Press to start Whisper mode Temperatur...

Страница 31: ...and light will turn on Press to start Whisper mode and light will turn on Default mode is Boost Please choose Boost mode for initial heating c Defrosting 1 Automatic defrosting When machine is defros...

Страница 32: ...p doesn t run No power Wait until the power is restored Power is switched off Switch on the power Fuse has blown Check and change the fuse The breaker is off Check and turn on the breaker Fan running...

Страница 33: ...6 Low water flow indicated by more than 10 C difference in inlet and outlet temperature Check water flow and pool pump 5 Eb Ambient temperature is out of range either lower than 5 C 10 C HPP 18 24 30...

Страница 34: ...as return temp sensor failure 13 P6 Cooling coil pipe temp sensor failure 14 P7 Ambient temp sensor failure 15 P8 Cooling plate sensor failure 16 P9 Current sensor failure 17 PA Restart memory failure...

Страница 35: ...bles and connections regularly Repair service and disposal of redundant heat pumps must be completed by authorised technicians It is illegal to allow refrigerant gases to escape to air Do not attempt...

Страница 36: ...wer kW 0 3 1 79 0 40 2 38 0 57 3 21 Rated input current A 1 38 7 58 1 82 10 8 2 60 14 61 Maximum input current A 9 5 12 5 19 5 Rated RCD type F mA 30 30 30 Rated Fuse aM MCB type C A 16 16 25 Sound pr...

Страница 37: ...0 41 3 15 0 48 3 91 0 64 5 20 Rated input current A 0 59 4 56 0 69 5 66 0 92 7 53 Maximum input current A 5 8 7 9 5 Rated RCD type B mA 30 30 30 Rated Fuse aM MCB type C A 10 10 16 Sound pressure leve...

Страница 38: ...Water in A B C D E F G H J HPP i 8 334 560 318 359 864 250 74 648 116 HPP i 12 334 560 318 359 864 290 74 648 116 HPP i 16 334 590 318 359 954 390 74 748 116 HPP i 18 3 Ph 404 590 388 429 954 460 74...

Страница 39: ...R HPP i 8 478 465 285 288 533 565 50 HPP i 12 478 465 285 288 630 565 50 HPP i 16 478 465 349 315 675 666 50 HPP i 18 3 Ph 587 540 370 349 731 667 50 HPP i 24 3 Ph 645 640 462 405 799 861 50 HPP i 30...

Страница 40: ...Objective To provide frost protection To eliminate corrosion problems To inhibit electrical components 1 Switch off electrical supply to heat pump 2 Remove external fuses and keep in safe place away f...

Страница 41: ...chemical balance is outside the following limits 6 The heat pump has suffered frost damage 7 The electrical supply is insufficient or in any way incorrect 8 The fan amps and duct pressure are outside...

Страница 42: ...42 1007332 ISSUE 1 OWNER INSTALLATION MANUAL 12 0 DECLARATION OF CONFORMITY...

Страница 43: ...43 1007332 ISSUE 1...

Страница 44: ...Dantherm A S Marienlystvej 65 DK 7800 Skive Tel 45 96 14 37 00 info dantherm com Dantherm is a brand of dantherm com...

Отзывы: