19
Installation
: Electrical connection
It is the responsibility of the installer to ensure the conformity towards national regulations of
all, not supplied cables.
The interfaces and terminals on the control panel make it possible to communicate with the
dehumidifier and connect accessory such as a RH/T sensor, an alarm and a heating coil. The
figure and table below describe the different functions of the interface.
+v
TH
TH
GND
GND
+
GND
+
RH
ON
ON
USB
RS485
EXT RH/T
ALARM
12V DC
RUN
FAIL
HEAT1 HEAT2
GND
+
GND
+
RH
ON
ON
OK
1
2
3
4
5
Fig. 6
Pos . Interface
Description
1
USB
USB is used for datalogging/ software update. See more information
in section “Software update and log files” on page 25.
2
Modbus RTU
(RS-485)
Connection via modbus. A list of data for the Modbus interface can be
downloaded on support.dantherm.com
3
External
RH/T sensor
Terminals for connecting an external humidity/ temperature sensor.
See wiring example in Fig. 7
4
Alarm
An external alarm can reveal, if the dehumidifier is operating normally
or has an error. See wiring example in Fig. 8
5
12 VDC
Heat control
Connection of LPHW (water) or electric heating helps controlling the
indoor temperature. Contact your Dantherm dealer for more informa-
tion.
There is an option for connecting an external RH/T sensor, which makes it possible to overrule
the internal sensors. In Fig. 7 there is an example on how it could be connected.
Fig. 7
*Switch in position: 0 = Internal sensors in use, 1 = External sensors in use
**Note, operational range is within 40-99% RH, if out of range the dehumidifier will be in
stand by mode
!
NOTICE
Control panel
interfaces
External RH/T
sensor connection
(Optional)
External temperature sensor
(or resistor)
ON/OFF switch for
external sensors*
(Optional)
EXT RH/T
External humidity sensor
(or control unit)
EXT RH/T
V+
TH
TH
RH
GND
10kΩ NTC
0V = 0% RH
5V = 50% RH
10V = 100% RH**
0
1
GND
0-10V
en
Содержание CDP 40
Страница 1: ...CDP 40 50 70 CDP T 40 50 70 SERVICE MANUAL EN Rev 1 5 2022 W38 3...
Страница 2: ......
Страница 10: ...10 Product description Enclosure dimensions Enclosure dimensions Fig 4 Fig 5 CDP 40 50 70 CDP 40T 50T 70T...
Страница 17: ...17 Installation Wall mounting 6 Hang the dehu midifier on the wall suspension bar Warning Caution en...
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......