18
Mounting and installation guide
Suspension
The wall suspension bar supplied with the unit is
fixed to the wall and the dehumidifier is hung up
on it. It is important to mount the unit in a hori-
zontal position to secure correct outflow of the
condensate water.
To make sure that the room air passes unimped-
edly through the dehumidifier, air inlet and air
outlet openings must be free.
It is important that the dehumidifier is not in-
stalled near a source of heat as for example a ra-
diator, and doors and windows must be kept
closed when the dehumidifier is in function
NOTE
Dantherm Air Handling recommends a minimum distance between dehumidifier and
ceiling and dehumidifier and floor of 225 mm.
*)
The dimensions indicate the placing of the wall suspension bar.
Condensate outlet
The condensate outlet is located at the bottom of the dehumidifier. The unit has a drain
spigot intended for connection of a ½’’ flexible or fixed water connection. If water drain
through the wall is chosen, a suitable hole is made in the wall and the condensate hose
is led out through this hole, before suspending the dehumidifier on the wall suspension
bar.
It is important that the hose from the dehumidifier to the drainage has a fall of at least
2 % to make sure that the water runs away from the condensate tray.
As an alternative a condensate pump can be fitted at the water outlet to pump the water
to a drain.
Placing of the con-
densate outlet
The placing of the con-
densate outlet is shown
on the drawing – the
unit is seen from
above.
Connection of power
supply
Power is connected to the unit in accordance with the nameplate. Please refer to the
wiring diagrams from page 54.
Note! All electrical connections must be made in accordance with local power supply
company regulations.
*