Part/function
This table gives an overview of each part of the control panel in fig. 6:
No
Part
Function
Electric
connection
Mains cable with a 16 A CEE connector at the end
Function
switch
The function switch selects the operating mode and has three
positions:
VENT, OFF and AUTO
Indicator
lamps
On the operator panel there are three control lamps, indicating the
following:
Color
Unit
Description
Green Power
Shows that power has been connected to
the unit
Red
Thermo
relay fail
Illuminates if the compressor, evaporator fan
or condenser fan thermo relay has cut off
because of a too high running current.
Please also refer to the “Fault finding guide”
Yellow HP/LP
Illuminates when the built-in HP/LP pressure
switch cuts out and stops the com-pressor
because of too high pressure (HP) or low
pressure (LP) in the cooling circuit. The HP/LP
pressure switch automatically resets after a
few minutes. Do not let the product operate
with HP/LP switching ON and OFF.
If the lamp continues to illuminate, please
refer to the “Fault finding guide”
Reset
button
•Compressor
•Evaporator fan
•Condenser fan
If the failure indicator (Thermo relay
) illuminates, the thermo relay
will have to be reset on one of the reset buttons.
If it is not clear which one of the thermo relays has disconnected,
push the reset buttons one by one.
See also “Fault finding guide”
Thermostat
connection
Cable for the remote thermostat
Description of the control board,
continued
17
en
Содержание AC-24
Страница 1: ...AC 24 SERVICE MANUAL en Rev 1 2 1 2020 W48 3...
Страница 2: ......
Страница 34: ...Spare parts for cabinet Illustration Available spare parts 1 3 1 4 1 5 1 1 1 6 1 7 1 8 1 3 1 9 1 2 34...
Страница 40: ...40...
Страница 47: ...Dimensions Dimensions 47 en...
Страница 48: ...Wiring diagram Wiring diagram 48...
Страница 49: ...Wiring diagram Continued Wiring diagram continued 49 en...
Страница 51: ......