The Rs485Bus standards require a daisy- chain
connection between the equipment. There must be
termination resistors with 120
(as the picture8-
4.1). Please refer to picture 8-4 .2 for simple
connection. D should not exceed 7m.
Ø
Connection and termination resistor
Ω
8.4 Rs485Bus basic knowledge
1 20
Ω
1#
2#
3#
4#
32#
Picture8-4.1
12 0
Ω
120
Ω
1#
2#
3#
4 #
32#
D
A+
B-
A+
B-
Pict ure8-4.2
120
Ω
2400BPS
4800BPS
9600BPS
1800m
1200m
800m
Baud rate
Max d istance
19200BPS
600m
Ø
The termination resistor is ready on the protocol
PCB.The are two kinds of connection(as show 8-4.3
form). It is the factory default connection. The jumper
cap of switchboard is seated on pin 2&Pin 3 and the
termination resistor120
is no t connected.
When connecting the 120
termination resistor,
usershould pull out the protocol PCB and plug the
jumper on Pin1&pin2. Install the PCB back and the
termination resistor is connected.
(as show the picture8-4.3)
The connection of 120
temination resistor:
Ω
Ω
Ω
24
Factory default setting
Connection of120 setting
Ω
1
2
3
On
On
Off
On means insert the jumper cap
Off
On
On
Picture8-4.3
Appendix
As specified by Rs485 standard, Rs485 Bus is
of half-duplexed data transmission cables with
characteristicimpedance as 120
. The maximum
load capacity is 32unit loads(including main
controller and controller equipment)
Ω
Ø
Characteristics of Rs485 Bus
Ø
Transmission distances of Rs485 Bus
When user selects the 0.56mm(24AWG) twisted
pair wires as data transmission cable, the maximum
theoreticcal transmitting distance are as follow:
If user selects thinner cables, or installs the
dome in an environment with strong electromagnetic
interference, or connects lots of equipment to the
Rs485Bus, the maximumtransmitting distance will
be decreased. To increase the maximum transmitting
distance, do the contrary.