background image

Instructions

AN233086441027en-000201 | 5

© Danfoss | DCS (CC) | 2019.03

11 – Check with running compressor

 Check current draw and voltage. Measurement 

of amps and volts during running conditions must 

be taken at other points in the power supply, not 

in the compressor electrical box.

 •  Check suction superheat to reduce risk of 

slugging.

 •  

Observe the oil level at start and during 

operation to confirm that the oil level remains 

visible. Excess foaming in oil sight glass 

indicates refrigerant on the sump.

 •  Monitor the oil sight glass for 1 hour after 

system equilibrium to ensure proper oil return 

to the compressor. This oil check has to be 

done over the speed range to guarantee:

  -   a good oil return at low speed with minimum 

gas velocity.

  -   a good oil management at high speed with 

maximum oil carry over.

  •   Respect the operating limits.

 •  

Check all tubes for abnormal vibration. 

Movements in excess of 1.5 mm / 0.06 inch 

require corrective measures such as tube 

brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side 

as far as possible from the compressor. The 

compressor must be operating during this 

process.

  •   Do not overcharge the system.

  •   Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

  •   Compressor failure to build up pressure: Check 

all bypass valves in the system to ensure that 

none of these has been opened. Also check 

that all solenoid valves are in their proper 

position.

 •  Abnormal running noise: Ensure the absence 

of any liquid flood-back to the compressor by 

means of measuring the return gas superheat 

and compressor sump temperature. The sump 

should be at least 6K above the saturated 

suction temperature under steady-state 

operating conditions.

 •  

The high-pressure switch trips out: Check 

condenser operations (condenser cleanliness, 

fan operation, water flow and water 

pressure valve, water filter, etc.). If all these 

are OK, the problem may be due to either 

refrigerant overcharging or the presence of 

a noncondensable (e.g. air, moisture) in the 

circuit.

 •  

The low-pressure switch trips out: Check 

evaporator operations (coil cleanliness, fan 

operations, water flow, water filter, etc.), liquid 

refrigerant flow and pressure drops (solenoid 

valve, filter dryer, expansion valve, etc.), 

refrigerant charge.

 •   Low refrigerant charge: The correct refrigerant 

charge is given by the liquid sight glass 

indication, the condenser delta T in relation 

to the refrigerant pressure tables (pressure-

temperature), the superheat and the sub-

cooling, etc. (if additional charge is deemed 

necessary, refer to section 8).

 •  

Compressor short cycling: The number of 

cycles shall never exceed 12 starts per hour.

12 – Maintenance

  Internal pressure and surface temperature 

are dangerous and may cause permanent injury. 

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature may 

exceed 100°C / 212°F and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor problems, 

following periodic maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

  •   Ensure that the system is leak tight.

  •   Check the compressor current draw by reading 

one of the parameters via Modbus.

 •   Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 

•  

Keep the compressor clean and verify 

the absence of rust and oxidation on the 

compressor shell, tubes and electrical 

connections.

 •  Acid / moisture content in system and oil 

should be checked regularly.

13 - Warranty

Always transmit the model number and serial 

number with any claim filed regarding this 

product.

Use the fault memory of the frequency converter 

to recover the fault descriptions before initializing 

the system and even before shutting off the 

power. 

Variable speed drive model and serial number 

must also be transmitted with the claim.

The product warranty may be void in following 

cases:

  •   Absence of nameplate.

 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

  •   Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

 •   Use of a refrigerant or lubricant not approved 

by Danfoss.

  •   Any deviation from recommended instructions 

pertaining to installation, application or 

maintenance.

  •   Use in mobile applications.

  •   Use in explosive atmospheric environment.

  •   No model number or serial number transmitted 

with the warranty claim.

14 – Disposal

   Danfoss recommends that compressors and 

compressor oil should be recycled by a 

suitable company at its site.

Содержание VZH028

Страница 1: ...ressure has been relieved from the compressor A B C D E F G Operating limits Quick connect spade terminals VZH028 044 push push push Electrical connections All the above limits temperatures and speeds are secured by parameters in the drive and application controller softwares VZH028 VZH065 compressors can be powered by the dedicated variable speed drive or third party drive When Danfoss drive is s...

Страница 2: ...n COM N RS485 69 P RS485 68 COM RS485 61 RELAY 2 CDS803 Legends Ana Analogue Dig Digital in Input out Output COM Common NC Normally closed NO Normally open Open loop Process loop 91 92 93 3 phases mains input x x 95 Earth x x 42 45 0 4 20 mA Analague Output or Digital Output 50 10V DC Output 53 0 10V or 4 20mA Analague Input x 54 0 10V or 4 20mA Analague Input x 55 Com Analague In Out x 12 Externa...

Страница 3: ...ly open Open loop Process loop 91 92 93 3 Phase mains input X X 95 Earth X X 39 42 Analogue output 50 Analogue output 53 PLC 0 to 10 V X 54 Sensor X 55 PLC X 12 HP LP switch X X 12 External On Off NO X X 13 Factory bridged to 37 X X 13 Sensor X 18 External On Off NO X X 19 Digital input 27 HP LP switch NC safety devices X X 29 Digital input output 32 33 Digital input 20 Digital input Common 37 Fac...

Страница 4: ...al panels and electrical boxes of the system Wiring All control wires have to be of a screeened design The cable for electrical motor supply has to be of a shielded design as well Correct earthing of the shield cover has to be done using the method shown on drawings every time this one has to be earthed on each end of the cables Distinct cable trays must be used for control and motor supply The fr...

Страница 5: ... filter etc liquid refrigerant flow and pressure drops solenoid valve filter dryer expansion valve etc refrigerant charge Low refrigerant charge The correct refrigerant charge is given by the liquid sight glass indication the condenser delta T in relation to the refrigerant pressure tables pressure temperature the superheat and the sub cooling etc if additional charge is deemed necessary refer to ...

Страница 6: ...ter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S 6430 Nordborg Denmark ...

Отзывы: