Instructions

2 | AN233086441027en-000201

© Danfoss | DCS (CC) | 2019.03

Oil level switch assembly

Electrical connections / Wiring

Install the screw-in optical part on oil level 

switch port. (Factory preset for manifold version 

VZH compressor.)

3

1

4

2

1: Power supply wire
2: Power supply wire

3: Output wire

4: Not used

Install the electrical part on optical part. Make 

sure the cable outlet downside vertically

See at the correct diagram corresponding 

to different power supply models for proper 

wiring

1

OVDC

24VDC

2

3

Sensor

External

Load / Relay

24VDC MODEL

1

OVAC

24VAC

2

3

Sensor

External

Load / Relay

24VAC MODEL

1

N

L

2

3

Sensor

External

Load / Relay

230VAC MODEL

R

E

LA

Y

 1

L1

91

L1

U

96

T1/U

L2

92

L2

V

97

T2/V

L3

93

L3

W

98

T3/W

95

PE

PE

99

45

Ana out or Dig out

42

Ana out or Dig out

50

out +10 V

NC

53

Ana in 

NO

02

54

Ana in 

COM

01

55

Ana in/out COM

NC

06

NO

05

12

+24V

COM

04

18

Dig in

19

Dig in

27

Dig in/out

29

Dig in/out

20

Dig in COM

N- RS485

69

P+ RS485

68

COM RS485

61

R

E

LA

Y

 2

C

D

S8

03

Legends: 

Ana: Analogue

Dig: Digital

in: Input

out: Output

COM: Common

NC: Normally-closed

NO: Normally-open

Open loop

Process loop

91,92,93

3 phases mains input

x

x

95

Earth

x

x

42,45

0/4-20 mA Analague Output or Digital Output

-

-

50

+10V DC Output

-

-

53

0-10V or 4-20mA Analague Input

x

-

54

0-10V or 4-20mA Analague Input

-

x

55

Com Analague In/Out

x

-

12

External On/Off(NO)

x

x

18

External On/Off(NO)

x

x

19

Digital Input

-

-

27

Safety Device

x

x

29

Digital Input

-

-

20

Com Digital Input

-

-

98

To Compressor T3

x

x

97

To Compressor T2

x

x

96

To Compressor T1

x

x

99

Earth

x

x

03,02,01

Relay 1

-

-

06,05,04

Relay 2

-

-

69,68

RS485 Bus

-

-

61

RS485 Bus Com

-

-

-: Optional connection

X: Mandatory connection

The CDS803 frequency converter is factory preset with parameters for the open loop control 

principle. The process loop control principle can be selected by changing parameters in the «Quick 

menu».

Open loop: preset on input 53

0 - 10 V control

Frequency converter in slave mode

Process loop: preset on input 54

 4 - 20 mA control

Frequency converter under own PID controller

Basic connections for VZH028-044 drives

Содержание VZH028

Страница 1: ...ressure has been relieved from the compressor A B C D E F G Operating limits Quick connect spade terminals VZH028 044 push push push Electrical connections All the above limits temperatures and speeds are secured by parameters in the drive and application controller softwares VZH028 VZH065 compressors can be powered by the dedicated variable speed drive or third party drive When Danfoss drive is s...

Страница 2: ...n COM N RS485 69 P RS485 68 COM RS485 61 RELAY 2 CDS803 Legends Ana Analogue Dig Digital in Input out Output COM Common NC Normally closed NO Normally open Open loop Process loop 91 92 93 3 phases mains input x x 95 Earth x x 42 45 0 4 20 mA Analague Output or Digital Output 50 10V DC Output 53 0 10V or 4 20mA Analague Input x 54 0 10V or 4 20mA Analague Input x 55 Com Analague In Out x 12 Externa...

Страница 3: ...ly open Open loop Process loop 91 92 93 3 Phase mains input X X 95 Earth X X 39 42 Analogue output 50 Analogue output 53 PLC 0 to 10 V X 54 Sensor X 55 PLC X 12 HP LP switch X X 12 External On Off NO X X 13 Factory bridged to 37 X X 13 Sensor X 18 External On Off NO X X 19 Digital input 27 HP LP switch NC safety devices X X 29 Digital input output 32 33 Digital input 20 Digital input Common 37 Fac...

Страница 4: ...al panels and electrical boxes of the system Wiring All control wires have to be of a screeened design The cable for electrical motor supply has to be of a shielded design as well Correct earthing of the shield cover has to be done using the method shown on drawings every time this one has to be earthed on each end of the cables Distinct cable trays must be used for control and motor supply The fr...

Страница 5: ... filter etc liquid refrigerant flow and pressure drops solenoid valve filter dryer expansion valve etc refrigerant charge Low refrigerant charge The correct refrigerant charge is given by the liquid sight glass indication the condenser delta T in relation to the refrigerant pressure tables pressure temperature the superheat and the sub cooling etc if additional charge is deemed necessary refer to ...

Страница 6: ...ter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S 6430 Nordborg Denmark ...

Отзывы: