 Single compressors

Technical specifications

Capacity at EN12900 conditions - VZH028CJ-VZH035CJ-VZH044CJ

M

od

els

rpm

rps

Te

-30

-25

-20

-15

-10

-5

0

5

10

15

20

Tc

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

Qo

Pe

VZ

H

02

8C

J

18

00

30

5

-

-

1791

0.54

2252 0.519 2798 0.499 3437 0.479 4177

0.46

5027 0.442

-

-

-

-

-

-

-

-

25

-

-

1460 0.812 1873 0.804 2351

0.79

2905 0.771 3541 0.747 4269 0.717 5096 0.682 6031 0.643 7081 0.599 8257

0.55

45

-

-

-

-

-

-

1805 1.198 2256 1.218 2772 1.227 3359 1.224 4027

1.21

4783 1.185 5636 1.149 6593 1.103

65

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

36

00

60

5

3009

1.04

3787 1.056 4725 1.042 5840 0.984 7151 0.869 8676

0.68 10435 0.403

-

-

-

-

-

-

-

-

25 2371 1.492 3054 1.527 3863 1.572 4817 1.613 5934 1.634 7232 1.622 8730

1.56 10445 1.436 12396 1.234 14602 0.94 17081 0.539

45

-

-

2284 2.296 2937 2.292 3702 2.323 4597 2.375 5638 2.431 6845 2.479 8235 2.502 9825 2.487 11634 2.419 13680 2.283

65

-

-

-

-

-

-

-

-

-

-

3761 3.567 4622 3.615 5626

3.68

6789 3.744 8128 3.795 9660 3.818

6000

10

0

5

5025

1.96

6302 2.006 7834 1.996 9651 1.917 11784 1.756 14263 1.499 17119 1.131

-

-

-

-

-

-

-

-

25 4004

2.64

5147 2.772 6495 2.887 8075 2.972 9920 3.012 12058 2.994 14520 2.905 17336 2.73 20536 2.456 24150 2.068 28209 1.555

45

-

-

3860 3.845 4978 3.968 6278

4.1

7789 4.225 9540 4.331 11560 4.403 13879 4.429 16527 4.393 19532 4.283 22923 4.084

65

-

-

-

-

-

-

-

-

-

-

6426 6.069 7912 6.187 9633 6.296 11616 6.383 13888 6.433 16477 6.434

VZ

H

035

C

J

18

00

30

5

-

-

2268 0.658 2851 0.633 3542 0.608 4350 0.584 5287 0.561 6363 0.539

-

-

-

-

-

-

-

-

25

-

-

1848

0.99

2370

0.98

2977 0.964 3677

0.94

4483

0.91

5403 0.874 6450 0.832 7634 0.784 8964

0.73 10452 0.67

45

-

-

-

-

-

-

2284 1.461 2856 1.485 3508 1.496 4252 1.492 5098 1.475 6055 1.445 7134 1.401 8346 1.345

65

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

36

00

60

5

3808 1.268 4794 1.287 5981

1.27

7392

1.2

9052 1.059 10983 0.829 13209 0.491

-

-

-

-

-

-

-

-

25 3002

1.82

3866 1.862 4890 1.917 6098 1.966 7512 1.992 9155 1.977 11050 1.903 13222 1.751 15692 1.505 18484 1.146 21622 0.657

45

-

-

2891 2.799 3718 2.795 4687 2.833 5819 2.895 7137 2.965 8665 3.022 10424 3.051 12437 3.033 14727 2.95 17316 2.784

65

-

-

-

-

-

-

-

-

-

-

4760 4.349 5851 4.408 7121 4.487 8594 4.566 10289 4.628 12228 4.655

6000

10

0

5

6361 2.344 7977 2.398 9916 2.387 12217 2.293 14917

2.1

18055 1.792 21670 1.353

-

-

-

-

-

-

-

-

25 5069 3.157 6516 3.314 8221 3.452 10222 3.553 12557 3.601 15263 3.58 18379 3.473 21944 3.264 25994 2.936 30570 2.473 35708 1.859

45

-

-

4885 4.597 6301 4.745 7947 4.902 9859 5.052 12076 5.178 14633 5.265 17569 5.295 20920 5.253 24723 5.121 29017 4.883

65

-

-

-

-

-

-

-

-

-

-

8134 7.256 10015 7.397 12193 7.528 14704 7.632 17580 7.692 20857 7.693

VZ

H

044

CJ

18

00

30

5

-

-

2916 0.824 3666 0.792 4554

0.76

5594 0.731 6799 0.702 8183 0.675

-

-

-

-

-

-

-

-

25

-

-

2377 1.239 3048 1.227 3828 1.206 4729 1.176 5765 1.139 6949 1.094 8295 1.041 9817

0.98 11527 0.913 13441 0.839

45

-

-

-

-

-

-

2938 1.828 3673 1.858 4512 1.871 5468 1.867 6556 1.846 7787 1.808 9175 1.753 10733 1.682

65

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

36

00

60

5

4897 1.558 6165 1.581 7691 1.561 9507 1.475 11641 1.301 14124 1.018 16986 0.604

-

-

-

-

-

-

-

-

25 3860 2.235 4972 2.288 6289 2.355 7842 2.416 9660 2.448 11773 2.429 14211 2.337 17003 2.152 20180 1.849 23770 1.408 27806 0.807

45

-

-

3718 3.439 4782 3.433 6027

3.48

7483 3.557 9179 3.642 11143 3.713 13405 3.748 15994 3.726 18939 3.624 22269 3.42

65

-

-

-

-

-

-

-

-

-

-

6122 5.343 7524 5.416 9158 5.512 11052 5.609 13232 5.685 15725 5.718

6000

10

0

5

8180 2.932 10259

3

12752 2.986 15711 2.868 19183 2.627 23219 2.242 27868 1.692

-

-

-

-

-

-

-

-

25 6518 3.949 8379 4.146 10572 4.318 13145 4.445 16148 4.505 19628 4.478 23636 4.345 28220 4.083 33429 3.673 39313 3.094 45920 2.326

45

-

-

6283 5.751 8103 5.936 10220 6.132 12679 6.32 15529 6.478 18818 6.586 22593 6.624 26903 6.571 31794 6.406 37316 6.109

65

-

-

-

-

-

-

-

-

-

-

10460 9.077 12879 9.254 15681 9.418 18909 9.547 22608 9.623 26823 9.624

To: Evaporating temperature in °C 

Superheat = 10 K 

Tc: Condensing temperature in °C 

Subcooling = 0 K

Qo: Cooling capacity in W 

Pe: Power input in kW (with drive loss)

10

FRCC.PC.034.A2.02

Application Guidelines

Содержание VZH Series

Страница 1: ...Inverter scroll compressors VZH028 035 044 single R410A Application guidelines http cc danfoss com ...

Страница 2: ......

Страница 3: ...Content VZH028 035 044 single compressors 4 3 FRCC PC 034 A2 02 Application Guidelines ...

Страница 4: ...qualization connection 15 Suction discharge connections 15 Frequency converter dimensions 15 CDS803 frequency converter 16 Electrical data connections and wiring 17 Supply voltage 17 Compressor electrical specifications 17 Terminal cover mounting 17 Terminal cover removal 17 Fuses 18 Wire sizes 19 Wiring EMC protection 19 EMC correct installation of an IP20 frequency drive CDS803 20 Wiring diagram...

Страница 5: ...rigeration or air conditioning system 35 Compressor sound radiation 35 Mechanical vibrations 35 Speed by pass 35 Gas pulsation 35 Installation 36 Compressor handling 36 Mounting 36 Removing connections shipping plugs 36 System cleanliness 37 Tubing 37 Filter driers 37 Brazing and soldering 37 Compressor connection 37 High voltage test 38 Leak detection 39 Vacuum pump down and moisture removal 39 R...

Страница 6: ...ge valves for better efficiency at low pressure ratio Scrolls with optimized volume ratio lead to better heat pump application New distributed IPM motor lead to higher power factor Linear control oil pump PVE 32 lubricant EMC Electro Magnetic Compatibility bracket provided allows for grounding termination of shielded wire harness which reduces EMC emissions between drive and compressor 6 FRCC PC 0...

Страница 7: ...d in the following pages Detailed performances can be found in datasheets and in selection programs Compressor size Different frequency converter variants are available according to 1 Mains supply voltage 2 IP class CDS803 drives are available in IP20 or IP21 requiring additional kit housings 3 RFI Radio Frequency Interference class H4 4 Printed Circuit Board PCB coated When the compressor size an...

Страница 8: ... drive Equipement version A brazed connections single version B brazed connections manifold version Motor voltage code to CDS803 G 380 480V 3 50 60 Hz J 200 240V 3 50 60 Hz main supply voltage to frequency converter Oil sight glass Oil level switch Single version Threaded None Manifold version None Threaded H4 E20 T4 P7K5 803 CDS Dedicated compressor drive for VZH scroll Serie 803 output power in ...

Страница 9: ...ps for 19 minutes the internal lubrication algorithm in the drive will accelerate the compressor speed to 40 rps or above for 60 seconds to ensure sufficient lubrication of compressor moving parts Warning This function is enabled by parameter 28 10 as default setting Please notice when hands on mode is selected oil return management will not work even if parameter 28 10 oil return management is se...

Страница 10: ...222 1 751 15692 1 505 18484 1 146 21622 0 657 45 2891 2 799 3718 2 795 4687 2 833 5819 2 895 7137 2 965 8665 3 022 10424 3 051 12437 3 033 14727 2 95 17316 2 784 65 4760 4 349 5851 4 408 7121 4 487 8594 4 566 10289 4 628 12228 4 655 6000 100 5 6361 2 344 7977 2 398 9916 2 387 12217 2 293 14917 2 1 18055 1 792 21670 1 353 25 5069 3 157 6516 3 314 8221 3 452 10222 3 553 12557 3 601 15263 3 58 18379 ...

Страница 11: ... 0 657 45 3198 2 799 4106 2 795 5168 2 833 6407 2 895 7849 2 965 9517 3 022 11436 3 051 13630 3 033 16123 2 95 18941 2 784 65 5703 4 349 6988 4 408 8483 4 487 10212 4 566 12199 4 628 14469 4 655 6000 100 5 6730 2 344 8434 2 398 10478 2 387 12900 2 293 15741 2 1 19041 1 792 22841 1 353 25 5449 3 157 6998 3 314 8821 3 452 10958 3 553 13449 3 601 16335 3 58 19655 3 473 23449 3 264 27758 2 936 32621 2...

Страница 12: ... 1 884 13222 1 734 15692 1 49 18484 1 135 21622 0 65 45 2891 2 771 3718 2 767 4687 2 805 5819 2 867 7137 2 935 8665 2 993 10424 3 021 12437 3 003 14727 2 921 17316 2 757 65 4760 4 306 5851 4 365 7121 4 442 8594 4 52 10289 4 582 12228 4 609 6000 100 5 6361 2 321 7977 2 374 9916 2 363 12217 2 27 14917 2 079 18055 1 774 21670 1 339 25 5069 3 126 6516 3 282 8221 3 418 10222 3 518 12557 3 565 15263 3 5...

Страница 13: ...35 23057 0 65 45 3198 2 771 4106 2 767 5168 2 805 6407 2 867 7849 2 935 9517 2 993 11436 3 021 13630 3 003 16123 2 921 18941 2 757 65 5703 4 306 6988 4 365 8483 4 442 10212 4 52 12199 4 582 14469 4 609 6000 100 5 6730 2 321 8434 2 374 10478 2 363 12900 2 27 15741 2 079 19041 1 774 22841 1 339 25 5449 3 126 6998 3 282 8821 3 418 10958 3 518 13449 3 565 16335 3 544 19655 3 438 23449 3 231 27758 2 90...

Страница 14: ... 11 Nm 1 Nm Ø11 Ø164 5 Suction line 3 4 Organ pipe fitting Schrader valve and cover Overall height Top of sensor bracket 404 4 360 4 230 5 55 0 42 5 78 0 11 239 190 5 Ø19 5 4X 95 25 129 5 109 7 Suction line 111 3 discharge line 14 2 45 2 31 17 34 60 Oil level sensor prism Discharge line 1 2 Ø164 5 Top of sensor bracket Suction 3 4 Discharge line 1 2 404 4 360 4 230 5 Oil Sight Glass 1 1 8 Schrader...

Страница 15: ...nd on supply voltage IP rating and power The table below gives an overview of the overall dimensions and different drive enclosures H3 H5 Details for each drive enclosure are on the following pages Sight glass oil level switch Oil equalization VZH028 035 044 Rotolock 1 1 8 Suction Discharge VZH028 035 044 3 4 1 2 Drive supply voltage Drive power kW Compressor voltage code Compressor model IP20 Dri...

Страница 16: ...7 8 4 7 9 H5 IP20 334 402 314 150 120 255 12 6 7 8 5 9 5 A1 Including decoupling plate The dimensions are only for the physical units but when installing in an application it is necessary to add space for free air passage both above and below the units The amount of space for free air passage is listed in frequency converter dimensions Clearance above below mm inch 99 99 Decoupling Plate Illustrat...

Страница 17: ...e is the current value at maximum load in the operating envelope and at maximum speed and maximum drive input voltage RLA Rated Load Amp Max Operating Current A Wiring connections Max operating current is the maximum continuous current which is 115 of RLA This value is printed on compressor nameplate VZH scroll compressors will only compress gas while rotating counter clockwise when viewed from th...

Страница 18: ...0 JJN 60 60 PKZM4 63 3x380 480 V IP20 4 TR VZH028 FRS R 25 KTS R25 JKS 25 JJS 25 25 PKZM4 25 5 TR VZH035 FRS R 25 KTS R25 JKS 25 JJS 25 25 PKZM4 25 6 5 TR VZH044 FRS R 30 KTS R30 JKS 30 JJS 30 30 PKZM4 50 Danfoss recommends using the fuses listed below to protect service personnel and property in case of component break down in the frequency converter For circuit breakers Moeller types have been t...

Страница 19: ...he metal chassis of the converter Use star washers and galvanically conductive installation plates to secure good electrical connections Refer to instructions MG18N102 for tightening torques and screw sizes Note that the CDS803 must be mounted on a plain wall to ensure a good air flow through its heat exchanger From network to frequency converter From frequency converter to compressor Type mm AWG ...

Страница 20: ... 3 A Not present on all power sizes Do not connect shield to 61 01 02 03 relay1 relay2 UDC UDC Motor U V W 06 05 04 240 V AC 3 A EMC correct installation of an IP20 frequency drive CDS803 EMC qualification reports are available upon request to Danfoss technical support B a c k OK Com On Warn Alarm Hand On Reset Auto On Menu Status Quick Menu Main Menu L1 L2 L3 PE Min 16 mm Equalizing cable Control...

Страница 21: ...or 4 20mA Analague Input x 55 Com Analague In Out x 12 24V output 18 External On Off NO x x 19 Digital Input 27 Safety Device e g HP LP switch x x 29 Digital Input 20 Com Digital Input 98 To Compressor T3 x x 97 To Compressor T2 x x 96 To Compressor T1 x x 99 Earth x x 03 02 01 Relay 1 06 05 04 Relay 2 69 68 RS485 Bus 61 RS485 Bus Com Optional connection X Mandatory connection The CDS803 frequency...

Страница 22: ...ains connection to the CDS803 frequency converter order has no influence on the output phase sequence which is managed by the frequency converter The compressor terminal box IP rating according to IEC529 is IP22 VZH scroll compressors are not equipped with an internal motor protector Motor protection is provided by the variable speed drive All parameters are factory preset in order to guaranty loc...

Страница 23: ...e maximum allowable voltage imbalance between each phase is 3 Voltage imbalance causes high amperage over one or several phases which in turn leads to overheating and possible drive damage Mains imbalance function in CDS803 frequency converter can be set to 0 Trip or 1 Warning in 14 12 parameter It is by default factory preset to 1 Warning Then the compressor electrical motor is never affected by ...

Страница 24: ...2 or CE 0038 European Directive All VZH models UL Underwriters Laboratories All VZH models EMC 2004 108 EC All VZH models CCC All VZH models Products Internal free volume at LP side without oil liter VZH028 3 2 VZH035 3 2 VZH044 3 2 Products VZH028 VZH035 VZH044 Fluids Group 2 Category PED I TS service temperature LP 35 C TS 55 C PS service pressure LP 33 3 bar g 24 FRCC PC 034 A2 02 Application G...

Страница 25: ...ly controlled by an external main controller it is recommended to limit the start stop frequency to 12 times per hour The operating envelopes for VZH scroll compressors are given in the figures below where the condensing and evaporating temperatures represent the range for steady state operation Under transient conditions such as start up and defrost the compressor may operate outside this envelop...

Страница 26: ...ge temperature must be monitored during development test by the equipment manufacturer The compressor must not be allowed to cycle on the discharge gas thermostat Continuous operations beyond the compressor s operating range will cause serious damage to the compressor VZH028 044 can install a discharge sensor dome sensor at the top of shell through a bracket and the sensor has to been connected an...

Страница 27: ...rication compressor speed will boost to 40 rps minimum ORM Boost Speed 28 17 at a fixed time intervals as programmed in parameter 28 12 default 24 hrs any way OEM could set 28 17 to a higher speed such as 70 rps to secure oil management According to different application requirements OEM can either add oil separator including to add more oil in the system or adjust oil return parameters or might n...

Страница 28: ...circuit The LP switch tolerance must not allow for vacuum operations of the compressor LP switch settings for pump down cycles with automatic reset are also listed in the table below The lock out circuit or LP switch or series with other safety devices could be connected to CDS803 input 27 The low pressure switch must have the highest priority that shall not be by passed It means when low pressure...

Страница 29: ...ning back to the compressor when stopped For Inverter applications with long lines we recommend the use of an oil separator even if it is only the condenser which is far away from the unit Piping must also be designed with care in order to make sure the remaining oil not trapped by the oil separator is properly carried over the system Basic principal is shown here Note that for the discharge line ...

Страница 30: ... positive effect of sub cooling on system efficiency will be significantly larger than in R22 R407C systems Furthermore for good operation of the expansion device and to maintain good efficiency in the evaporator it is important to have an adequate liquid sub cooling Without adequate sub cooling flash gas will be formed at the expansion device resulting in a high degree of vapor at the evaporator ...

Страница 31: ...than 2 3 bar An external non return valve is recommended to avoid liquid flood back from the high pressure side Liquid receiver Refrigerant charge optimization varies with compressor speed To avoid flash gas at low speed a receiver may be necessary Receiver dimensioning requires special attention The receiver shall be large enough to contain part of the system refrigerant charge but shall not be t...

Страница 32: ...ng pressure must be set at the minimum saturated condensing temperature shown in the application envelopes Under very low ambient conditions in which testing has revealed that the above procedures might not ensure satisfactory condensing and suction pressures the use of a liquid receiver with condenser and receiver pressure regulators would be possible Condensing pressure control is also strongly ...

Страница 33: ... 1 meter of discharge line is necessary to generate this volume To help reduce the gas volume immediately after start up even further the supply of cooling water to the heat exchanger may be opened before the compressor starts up so as to remove superheat and condense the incoming discharge gas more quickly Because of the large compressor capacity variation and VZH capability to run at low condens...

Страница 34: ...me compressor will run at 50 rps for at least 1 minute Thus to avoid excessive liquid refrigerant to come back to the compressor sump The use of a suction line accumulator is strongly recommended in reversible cycle applications This because of the possibility of a substantial quantity of liquid refrigerant remaining in the evaporator which acts as a condenser during the heating cycle This liquid ...

Страница 35: ...must be checked frame piping pipes using cushioned clamps But if some frequencies continue to produce unacceptable vibration levels speed by pass is adjustable in the frequency converter in order to avoid some frequency ranges Four by pass ranges are adjustable and settings can be made in parameter group 4 6 The VZH scroll compressor has been designed and tested to ensure that gas pulsation has be...

Страница 36: ... concerning lifting objects of the type and weight of these compressors Maintain the compressor in an upright position during all handling operations When the compressor is mounted as part of an installation never use the lift rings on the compressor to lift the installation The risk is that the lugs could separate from the compressor or that the compressor could separate from the base frame with ...

Страница 37: ... When brazing the compressor fittings do not overheat the compressor shell which could severely damage certain internal components due to excessive heating Use of a heat shield and or a heat absorbent compound is highly recommended Due to the relatively sizable tubing and fitting diameters a double tipped torch using acetylene is recommended for brazing operation on VZH compressors B C A heat shie...

Страница 38: ...and can cause substantial damage to the internal parts of the system and compressor The polyolester oil used in VZH compressors is highly hygroscopic and will rapidly absorb moisture from the air The compressor must therefore not be left open to the atmosphere for a long period of time The compressor fitting plugs shall be removed just before brazing the compressor The compressor should always be ...

Страница 39: ...s on the liquid line between the condenser outlet and the filter drier Then during commissioning when needed a complement of charge can be done in liquid phase slowly throttling liquid in on the low pressure side as far away as possible from the compressor suction connection The refrigerant charge quantity must be suitable for both summer and winter operations Refer to news bulletin FRCC EN 050 Da...

Страница 40: ...am filling in the sight glass indicates large concentration of refrigerant in the oil and or presence of liquid returning to the compressor The oil level can also be checked a few minutes after the compressor stops the level must be between and of sight glass When the compressor is off the level in the sight glass can be influenced by the presence of refrigerant in the oil Always use original Danf...

Страница 41: ...Single compressors Trouble shooting 06 03 2015 page 1 c a s s w c w m s 06 03 2015 page 2 f S mains O e b s a c l o Check HP LP switch Reset start 41 FRCC PC 034 A2 02 Application Guidelines ...

Страница 42: ...Single compressors Trouble shooting 06 03 2015 page 3 heating t o m overheating r 06 03 2015 page 4 42 FRCC PC 034 A2 02 Application Guidelines ...

Страница 43: ...Single compressors Trouble shooting 06 03 2015 page 5 43 FRCC PC 034 A2 02 Application Guidelines ...

Страница 44: ...MA 120G0067 VZH044CJAMA 120G0068 Manifold VZH044CGBMA VZH044CJBMA The tables on the following pages give code numbers for ordering purposes for the VZH compressor and CDS803 frequency converter kit packed and shipped separately VZH scroll compressors and drive can be ordered in single packs Please use the code numbers from below tables for ordering Kit ordering and shipping Compressor single pack ...

Страница 45: ...NO T2 200 240V 3ph 50 60Hz VZH028 CDS803P6K0T2E20H4 134N4260 VZH035 CDS803P7K5T2E20H4 134N4261 VZH044 CDS803P10KT2E20H4 134L9470 T4 380 480V 3ph 50 60Hz VZH028 CDS803P6K0T4E20H4 134N4262 VZH035 CDS803P7K5T4E20H4 134N4263 VZH044 CDS803P10KT4E20H4 134L9473 LCP user interface 120Z0581 accessory 45 FRCC PC 034 A2 02 Application Guidelines ...

Страница 46: ...6 Solder sleeve adapter set 1 1 4 Rotolock 3 4 ODF 1 Rotolock 1 2 ODF VZH028 044 Multipack 6 Solder sleeve adapter sets Type Code n Description Application Packaging Pack size 120Z5040 Belt type crankcase heater 65W 230V CE mark UL wire length 1270mm VZH028 044 Multipack 4 120Z5041 Belt type crankcase heater 55 70W 400 460V CE mark UL wire length 1270mm Multipack 4 Type Code n Description Applicat...

Страница 47: ...r VZH028 044 Multipack 10 Spare parts frequency converter Type Code n Description Application Packaging Pack size 120Z0581 LCP Frequency converter all models Single pack 1 120Z0617 LCP kit for remote mounting Frequency converter all models Single pack 1 Frame Compressor Decoupling plate Packaging Pack size 200 240V 380 480V H3 VZH028 035 120Z0582 Single pack 1 H4 VZH028 035 VZH044 120Z0583 Single ...

Страница 48: ...and positioned us as distinct variable speed technology specialists Today we operate from engineering and manufacturing facilities spanning across three continents FRCC PC 034 A2 02 Danfoss DCS CC 2015 05 Our products can be found in a variety of applications such as rooftops chillers residential air conditioners heatpumps coldrooms supermarkets milk tank cooling and industrial cooling processes h...

Отзывы: