manualshive.com logo in svg
background image

Instructions

8510286P01AA - AN280556890612en-000201 | 3

© Danfoss | DCS (CC) | 2022.11

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.

  •   Do not use leak detection dye.

 •  Perform a leak detection test on the complete 

system.

 •   The low side test pressure must not exceed 31 bar 

/450 psi.

 •   When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the 

system.

 •  Connect a vacuum pump to both the LP & HP sides.

 •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) / 0.02 inch Hg absolute.

  •   Do not use a mega ohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

  •   Switch off and isolate the main power supply.

  •   Before touching any potentially live part of the 

drive, wait at least 4 minutes.

 •  The compressor is protected against excess 

current by the frequency converter. Follow 

local regulations regarding power line 

protection.The compressor must be connected 

to ground.

 •  Use 6.3 mm tabs for quick connect spade 

terminals.

  •   Use a self-tapping screw to connect the ground 

conductor to the compressor.

 •  

Care must be taken during installation to 

ensure that the compressor operates in the 

correct direction. T1 (U), T2 (V) and T3 (W) 

terminals of compressor and drive U, V, W must 

match. Please refer to drawings for typical 

wiring connections and examine the specific 

wiring diagram located in the frequency 

converter package. For further details, refer to 

the application guidelines.

 •  Mounting: The base frame of the frequency 

converter must be very well fixed to the 

support to ensure a very good continuity 

between the ground potential of all electrical 

panels and electrical boxes of the system.

 •  

Wiring: All control wires have to be of a 

screened design. The cable for electrical motor 

supply has to be of a shielded design as well. 

Correct earthing of the shield cover has to be 

done using the method shown on drawings, 

every time this one has to be earthed on each 

end of the cables. Distinct cable trays must be 

used for control and motor supply.

 •   The frequency converter ensures direct motor 

protection and the factory set parameters 

are such to protect the motor over all current 

malfunctions. An external overload is not 

necessary.

 •  Set the frequency converter parameters in 

accordance with Danfoss recommendations 

for the frequency converter and VLZ variable 

speed compressor.

 •  

Refer to variable speed drive manual for 

electrical connections details and installation.

 •  Compressor motor protection is provided by 

the variable speed drive. 

8 – Filling the system

  •   Keep the compressor switched off.

 •  Fill the refrigerant in liquid phase into the 

outlet of the condenser or the liquid receiver. 

The charge must be as closed as possible 

to the nominal system charge to avoid low 

pressure operation and excessive superheat. 

For VLZ028-044, the refrigerant charge limit is 

3.6 kg, Pump down switch setting should be 

not lower than 1.0 bar(g) for R448A/1.0 bar(g) 

for R449A/1.5 bar(g) for R404A. 

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 

with both generally and locally applicable 

regulations and safety standards. Ensure that 

they are operational and properly set. 

 Check that the settings of high-pressure 

switches do not exceed the maximum service 

pressure of any system component.

 •  A low-pressure switch is mandatory to avoid 

vacuum operation. Minimum setting 0.8 bar(g) 

for R448A/R449A. Minimum pressure 1.3 bar(g) 

for R404A.

 •  

Verify that all electrical connections are 

properly fastened and in compliance with local 

regulations.

 •  

When using discharge temperature sensor, 

ensure that the discharge temperature sensor 

is correctly installed and fitted to the discharge 

piping (6 inches from discharge fitting) and 

well connected, especially after maintenance 

operations.

  •   After comissioning it is strongly recommended to 

keep the frequency converter always energized.

10 – Start-up

  •   Never start the compressor when no refrigerant 

is charged.

 •   Do not provide any power to the drive unless 

suction and discharge service valves on 

compressor are open, if installed.

 •   Energize the drive. The compressor must start, 

according to defined ramp-up settings. If 

the compressor does not start, check wiring 

conformity.

 •  Check the frequency converter control panel: 

If any alarm is displayed check the wiring and 

in particular the polarity of the control cables. 

If an alarm is shown, refer to the frequency 

converter application manual. Verify in 

particular the combination of compressor, 

frequency converter and refrigerant.

 •   Check current draw and voltage levels on the 

mains. The values for the compressor electrical 

motor can be directly displayed on the 

frequency converter control panel.

  •   The optimum compressor suction superheat is 

around 10K.

 •  Eventual reverse rotation can be detected by 

following phenomena; the excessive noise, 

no pressure differential between suction 

and discharge, and line warming rather than 

immediate cooling. A service technician should 

be present at initial start-up to verify that 

wiring from drive to compressor is properly 

phased and that the compressor is rotating in 

the correct direction. 

 •  Note that a 300 seconds period is necessary 

between 2 starts, a shorter period will be not 

allowed by the drive. The minimum running 

time is 12s for each start.

11 – Check with running compressor

 Check current draw and voltage. Measurement 

of amps and volts during running conditions must 

be taken at other points in the power supply, not 

in the compressor electrical box.

 •  Check suction superheat to reduce risk of 

slugging.

 •  

Observe the oil level at start and during 

operation to confirm that the oil level remains 

visible. Excess foaming in oil sight glass 

indicates refrigerant on the sump.

 •  Monitor the oil sight glass for 1 hour after 

system equilibrium to ensure proper oil return 

to the compressor. This oil check has to be 

done over the speed range to guarantee:

  -   a good oil return at low speed with minimum 

gas velocity.

  -   a good oil management at high speed with 

maximum oil carry over.

  •   Respect the operating limits.

 •  

Check all tubes for abnormal vibration. 

Movements in excess of 1.5 mm / 0.06 inch 

require corrective measures such as tube 

brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side 

as far as possible from the compressor. The 

compressor must be operating during this 

process.

  •   Do not overcharge the system.

  •   Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

  •   Compressor failure to build up pressure: Check 

all bypass valves in the system to ensure that 

none of these has been opened. Also check 

that all solenoid valves are in their proper 

position.

 •  Abnormal running noise: Ensure the absence 

of any liquid flood-back to the compressor by 

means of measuring the return gas superheat 

and compressor sump temperature. The sump 

should be at least 10K above the saturated 

suction temperature under steady-state 

operating conditions.

 •  

The high-pressure switch trips out: Check 

condenser operations (condenser cleanliness, 

fan operation, water flow and water 

pressure valve, water filter, etc.). If all these 

are OK, the problem may be due to either 

refrigerant overcharging or the presence of 

a noncondensable (e.g. air, moisture) in the 

circuit.

 •  

The low-pressure switch trips out: Check 

evaporator operations (coil cleanliness, fan 

operations, water flow, water filter, etc.), liquid 

refrigerant flow and pressure drops (solenoid 

valve, filter dryer, expansion valve, etc.), 

refrigerant charge.

 •   Low refrigerant charge: The correct refrigerant 

charge is given by the liquid sight glass 

indication, the condenser delta T in relation 

to the refrigerant pressure tables (pressure-

temperature), the superheat and the sub-

cooling, etc. (if additional charge is deemed 

necessary, refer to section 8).

 •  

Compressor short cycling: The number of 

cycles shall never exceed 12 starts per hour.

Отзывы: