5.10 Emergency Run Operation
In normal operation, the VLT
®
Soft Starter MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
A 2-wire circuit connected to input A (terminals 11, 16) controls emergency run. Closing input A causes the soft starter to
run the motor and ignore all trip conditions.
K1
F
24
VD
22
21
6/T3
2/T1
13
14
4/T2
24
33
34
06
05
08
07
17
18
25
11
16
A6
A5
A4
5/L3
3/L2
15
S3
S1
S2
E
1/L1
+
+
5
6
7
4
2
A
3
1
177HA524
.1
1
Control voltage (model dependent)
S1
Start/stop contact
2
24 V DC output
S2
Reset contact
3
Remote control inputs
S3
Emergency run contact
4
Motor thermistor input (PTC only)
13, 14
Relay output A
5
Relay outputs
21, 22, 24
Relay output B
6
3-phase supply
33, 34
Relay output C
7
Motor terminals
Illustration 5.12 Emergency Run Operation
Parameter settings:
•
Parameter 3-3 Input A Function.
-
Select
Emergency Run
- assigns input A to emergency run function.
•
Parameter 15-3 Emergency Run.
-
Select
Enable
- Enables the emergency run-mode.