Illustration 4.9 In-line Installation, Externally Bypassed,
MCD5-0360C to MCD5-1600C
4.3.3 Inside Delta Installation
NOTICE
When connecting the VLT
®
Soft Starter MCD 500 in
inside delta configuration, always install a main
contactor or shunt trip circuit breaker.
NOTICE
When connecting in inside delta, enter the motor full
load current (FLC) for
parameter 1-1 Motor FLC
. The MCD
500 automatically calculates inside delta currents based
on this data.
Parameter 15-7 Motor Connection
is set to
Auto detect
as default and can be set to force the soft
starter in inside delta or in-line.
4.3.3.1 Internally Bypassed
6/T
2/T
13
14
4/T
K1
U1(1) U2(4)
V1(2)
V2(5)
W1(3)
W2(6)
5/L3
3/L2
1/L1
E
K1
F1
M
3
177HA501.11
K1
Main contactor
F1
Semiconductor fuses (optional)
Illustration 4.10 Inside Delta Installation, Internally Bypassed
4.3.3.2 Non-bypassed
177HA500.12
M
3
6/T
2/T
5/L
3/L
1/L
1
1
4/T
K1
K1
F
U1(1 U2(4
V1(2
V2(5
W1(
W2(
L2
L1
L3
E
K1
Main contactor
F1
Semiconductor fuses (optional)
Illustration 4.11 Inside Delta Installation, Non-bypassed
Electrical Installation
VLT
®
Soft Starter MCD 500
18
Danfoss A/S © 05/2016 All rights reserved.
MG17K602