13-41 Logic Rule Operator 1
Option:
Function:
Select the 1st logical operator to use on the
boolean inputs from
and
.
[0]
*
Disabled
Ignores
parameter 13-42 Logic Rule Boolean 2
,
parameter 13-43 Logic Rule Operator 2
, and
parameter 13-44 Logic Rule Boolean 3
[1]
AND
Evaluates the expression [13-40] AND [13-42].
[2]
OR
Evaluates the expression [13-40] OR [13-42].
[3]
AND NOT
Evaluates the expression [13-40] AND NOT
[13-42].
[4]
OR NOT
Evaluates the expression [13-40] OR NOT
[13-42].
[5]
NOT AND
Evaluates the expression NOT [13-40] AND
[13-42].
[6]
NOT OR
Evaluates the expression NOT [13-40] OR
[13-42].
[7]
NOT AND
NOT
Evaluates the expression NOT [13-40] AND
NOT [13-42].
[8]
NOT OR
NOT
Evaluates the expression NOT [13-40] OR NOT
[13-42].
13-42 Logic Rule Boolean 2
Option:
Function:
Select the 2nd boolean (TRUE or
FALSE) input for the selected logic
rule. See
(
[0]–[61]
), and
(
[70]–[74]
) for further
description.
[0]
*
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
13-42 Logic Rule Boolean 2
Option:
Function:
[28] Logic rule 2
[29] Logic rule 3
[30] SL Time-out 0
[31] SL Time-out 1
[32] SL Time-out 2
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
[39] Start command
[40] Drive stopped
[42] Auto Reset Trip
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[83] Broken Belt
13-43 Logic Rule Operator 2
Option:
Function:
Select the 2nd logical operator to be used
on the boolean input calculated in
parameter 13-40 Logic Rule Boolean 1
parameter 13-41 Logic Rule Operator 1
and
parameter 13-42 Logic Rule Boolean 2
, and
the boolean input coming from
parameter 13-42 Logic Rule Boolean 2
Parameter 13-42 Logic Rule Boolean 2
signifies the boolean input of
parameter 13-44 Logic Rule Boolean 3
Parameter 13-40 Logic Rule Boolean 1
and
parameter 13-42 Logic Rule Boolean 2
signify
the boolean input calculated in
parameter 13-40 Logic Rule Boolean 1
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-42 Logic Rule Boolean 2
[0]
*
Disabled
Ignores
parameter 13-44 Logic Rule Boolean 3
.
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND
NOT
[8]
NOT OR NOT
Parameter Descriptions
Programming Guide
MG07C102
Danfoss A/S © 12/2015 All rights reserved.
87
4
4
Содержание VLT Midi Drive FC 280
Страница 1: ...Programming Guide VLT Midi Drive FC 280 vlt drives danfoss com ...
Страница 2: ......
Страница 143: ...Index Programming Guide MG07C102 Danfoss A S 12 2015 All rights reserved 141 ...