MCD Modbus Module Instructions 

 

AP ASCII Protocol 

 

MG.17.F5.02 - VLT

® is a registered Danfoss trademark 

10.

 

AP ASCII Protocol 

The message fragments used to communicate with the Modbus Module as an AP ASCII slave device 
are shown below. The message fragments may be assembled into complete messages as described 
in the sections that follow. 

 

 

N.B.!:

 

Data must be transmitted in 8-bit ASCII, no parity, one stop bit.  

 

Message Fragment Type  ASCII Character String or  

(Hexadecimal Character String) 

Send address 

EOT 
(04h 

[nn] 
[nn] 

[lrc] 
[lrc] 

ENQ   or 
05h) 

Send command 

STX 

[ccc] 

[lrc] 

ETX   or 

Send request 

(02h 

[ccc] 

[lrc] 

03h) 

Receive data 

STX 
(02h 

[dddd] 
[dddd] 

[lrc] 
[lrc] 

ETX   or 
03h) 

Receive status 

STX 
(02h 

[ssss] 
[ssss] 

[lrc] 
[lrc] 

ETX   or 
03h) 

ACK (acknowledge) 

ACK 
(06h) 

or 

 

 

NAK (negative 
acknowledge) 

NAK 
(15h) 

or 

 

 

ERR (error) 

BEL 
(07h) 

or 

 

 

 

nn = 

two byte ASCII number representing the soft starter address where each decimal digit is 
represented by n. 

lrc = 

two byte longitudinal redundancy check in hexadecimal. 

ccc = 

three byte ASCII command number where each character is represented by c. 

dddd = 

four byte ASCII number representing the current or temperature data where each decimal digit is 
represented by d. 

ssss = 

four byte ASCII number. The first two bytes are ASCII zero. The last two bytes represent the nibbles 
of a single byte of status data in hexadecimal. 

 

10.1.

 

Commands 

Commands can be sent to the soft starter using the following format: 

Send 

address 

 

ACK 

 

Send 

command

 

ACK  

 

 

 

 

 

 

 

 

Possible error responses: 

 

 

NAK (Invalid 

LRC) 

 

 

 

 

 

 

 

 

 

= Master 

 

 

=

Slave 

(soft starter) 

 

Command 

ASCII 

Comment 

Start 

B10 

Initiates a start 

Stop 

B12 

Initiates a stop 

Reset 

B14 

Resets a trip state 

Quick stop 

B16 

Initiates an immediate removal of voltage from the motor. Any soft 
stop settings are ignored. 

Forced communication trip 

B18 

Causes a communications trip 

 

Содержание VLT MCD 200

Страница 1: ...ion with a Remote Operator This document describes Modbus and AP ASCII messaging and Appendix A describes how to connect the Remote Operator and use it as a Modbus RTU or AP ASCII slave device 2 Insta...

Страница 2: ...o accept serial commands a link must be fitted across terminals A1 N2 on MCD 200 Series starters In order for the MCD 500 to accept commands from the serial network the soft starter must be in Auto On...

Страница 3: ...ns link between the module and the network LED operation is as follows LED 177HA263 11 Off On Flashing No connection or soft starter not powered up Communication active Communication inactive N B If c...

Страница 4: ...Jog forward 9 Jog reverse 4 1 Positive phase sequence only valid if bit 6 1 Always 0 5 1 Current exceeds FLC 6 0 Uninitialised 1 Initialised 7 Always 0 40004 Trip Code Multiple Read See Trip Code tab...

Страница 5: ...mplete parameter list The first product parameter is always allocated to register 40009 The last product parameter is allocated to register 40XXX where XXX 008 plus total number of available parameter...

Страница 6: ...tantaneous overcurrent 8 Power loss Power circuit 9 Undercurrent 10 Heatsink overtemperature 11 Motor connection 12 Input A trip Auxiliary input A 13 FLC too high FLC out of range 14 Unsupported optio...

Страница 7: ...Configuration For standard Modbus 11 bit transmission the Master must be configured for 2 stop bits with No Parity and 1 stop bit for odd or even parity For 10 bit transmission the Master must be conf...

Страница 8: ...ister not allowed for data reading 04 Not writable data Register not allowed for data writing 05 Data boundary fault Multiple data transfer across data boundary or data size more than 125 06 Invalid c...

Страница 9: ...r nn two byte ASCII number representing the soft starter address where each decimal digit is represented by n lrc two byte longitudinal redundancy check in hexadecimal ccc three byte ASCII command num...

Страница 10: ...pped 7 Program mode 4 1 Positive phase rotation only valid if bit 6 1 5 1 Current exceeds FLC 6 0 Uninitialised 1 Initialised 7 0 Communications are OK 1 Communications device fault 10 3 Data Retrieva...

Страница 11: ...5Ah 0101 1010 1 s COMPLEMENT 01h 0000 0001 1 5Bh 0101 1011 2 s COMPLEMENT 3 ASCII 5 B ASCII CONVERT 4 or 35h 42h LRC CHECKSUM The complete command string becomes ASCII STX B 1 0 5 B ETX or 02h 42h 31h...

Страница 12: ...le This resistance should match the cable impedance typically 120 Do not use wire wound resistors Network Master RS485 Remote Operator RS485 Soft Starter Module RS485 GND B8 B6 B7 B3 B1 B2 68 B8 69 B6...

Страница 13: ...parity 5 Timeout No timeout 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 16 8 4 2 1 0 0 0 0 0 DIP SWITCH A DIP SWITCH B 177HA543 10 1 2 3 4 5 The Remote Operator internal parameters must be set as follows Parameter...

Страница 14: ...30 VAC VDC 1 2 POWER SUPPLY The Serial Timeout setting on the MCD 3000 Parameter 24 applies to communications between the Remote Operator and the MCD 3000 See the MCD 3000 Operating Instructions for s...

Страница 15: ...op function disable 0 0 Remote Operator and Network start stop quick stop function enabled 1 Remote Operator start stop quick stop function enabled Network start stop quick stop function disabled 2 Re...

Страница 16: ...on is restored To clear nEt from the display press the Data Prog pushbutton momentarily or send a Reset command from the network Master SP flashing on display Soft starter is off and being programmed...