3.7.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital
output Terminal 42. Analog outputs are current outputs: 0/4
- 20mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be setup as digital output.
6-90 Terminal 42 Mode
Option:
Function:
Set Terminal 42 to act as analog output or as
digital output.
[0]
*
0-20 mA
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Option:
Function:
Select the function of Terminal 42 as an
analog current output. See also
.
[0]
*
No operation
[100] Output frequency 0 - 100Hz
[101] Reference
MinRef. - MaxRef.
[102] Feedback
MinFB - MaxFB
[103] Motor current
0 - I
max
[106] Power
0 - P
nom
[139] Bus Control
0 - 100%
6-92 Terminal 42 Digital Output
Option:
Function:
Select the function of
Terminal 42 as an
analog current output.
See also
. See
for
description of the
choices.
[0]
*
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
VLT running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[21]
Thermal warning
6-92 Terminal 42 Digital Output
Option:
Function:
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[35]
External Interlock
[36]
Control word bit 11
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
Function:
0.0 %
*
[0.0 - 200.0
%]
Scale for the minimum output (0 or 4mA) of
the analogue signal at Terminal 42. Set the
value to be the percentage of the full range
of the variable selected in
Parameters
VLT HVAC Basic Drive Programming Guide
44
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3