background image

1.1  Cascade Controller

Constant Speed

Pumps (2)

Variable Speed

Pumps (1)

Motor starter

Frequency Converter

with

Cascade Controller

Pressure Sensor

130BA362.10

Illustration 1.1 Cascade Controller

The Cascade Controller is used for pump applications
where a certain pressure (“head”) or level needs to be
maintained over a wide dynamic range. Running a large
pump at variable speed over a wide for range is not an
ideal solution because of low pump efficiency and because
there is a practical limit of about 25% rated full load speed
for running a pump.

In the Cascade Controller the frequency converter controls
a variable speed motor as the variable speed pump (lead)
and can stage up to two additional constant speed pumps
on and off. By varying the speed of the initial pump,
variable speed control of the entire system is provided.
This maintains constant pressure while eliminating
pressure surges, resulting in reduced system stress and
quieter operation in pumping systems.

Fixed Lead Pump
The motors must be of equal size. The Cascade Controller
allows the frequency converter to control up to 5 equal
size pumps using the drives two built-in relays and
terminal 27, 29 (digital input/digital output). When the
variable pump (lead) is connected directly to the frequency
converter, the other 4 pumps are controlled by the two
built-in relays and terminal 27, 29 (digital input/digital
output). Lead pump alternation can not be chosen when
lead pump is fixed.

Lead Pump Alternation
The motors must be of equal size. This function makes it
possible to cycle the frequency converter between the
pumps in the system (when 

25-57 Relays per Pump

 =1,

maximum pump is 4. When 

25-57 Relays per Pump

 =2,

maximum pump is 3). In this operation the run time
between pumps is equalized reducing the required pump
maintenance and increasing reliability and lifetime of the
system. The alternation of the lead pump can take place at
a command signal or at staging (adding lag pump).

The command can be a manual alternation or an
alternation event signal. If the alternation event is selected,
the lead pump alternation takes place every time the
event occurs. Selections include whenever an alternation
timer expires, when the lead pump goes into sleep mode.
Staging is determined by the actual system load.

25-55 Alternate if Load

50%

=1, if load >50% Alternation

will not happen. If load 

50% Alternation will happen.

When 

25-55 Alternate if Load

50%

 =0, Alternation will

happen no matter with Load. Total pump capacity is
determined as lead pump plus lag speed pumps capacities.

Bandwidth Management
In cascade control systems, to avoid frequent switching of
fixed speed pumps, the desired system pressure is kept
within a bandwidth rather than at a constant level. The
Staging Bandwidth provides the required bandwidth for
operation. When a large and quick change in system
pressure occurs, the Override Bandwidth overrides the
Staging Bandwidth to prevent immediate response to a
short duration pressure change. An Override Bandwidth
Timer can be programmed to prevent staging until the
system pressure has stabilized and normal control
established.

When the Cascade Controller is enabled and running
normally and the frequency converter issues a trip alarm,
the system head is maintained by staging and destaging
fixed speed pumps. To prevent frequent staging and
destaging and minimize pressure fluxuations, a wider Fixed
Speed Bandwidth is used instead of the Staging
bandwidth.

Illustration 1.2 Bandwidth

VLT® HVAC Basic Drive Casca...

VLT

®

 HVAC Basic Drive Cascade Controller

MI18I302 - VLT

®

 is a registered Danfoss trademark

1

1

1

Содержание VLT HVAC

Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction VLT HVAC Basic Drive Cascade Controller...

Страница 2: ......

Страница 3: ...is 3 In this operation the run time between pumps is equalized reducing the required pump maintenance and increasing reliability and lifetime of the system The alternation of the lead pump can take p...

Страница 4: ...P Coast to stop Cut out correspond relays terminal 27 29 and 42 45 External Interlock Coast to stop Cut out built in relays are de energized Table 1 1 Commands Assigned to Digital Inputs LCP keys Vari...

Страница 5: ...he programmed time expires Parameter Range Default Function 25 42 Staging Threshold Expressionlimit 0 100 90 The percentage of maximum pump speed to stage on a fixed speed pump 25 43 Destagi ng Thresh...

Страница 6: ...an be reset by writing 0 25 90 Pump Interlock 0 Off 1 On 0 Off Choose the pump to interlock for e g service The pump will be taken out of any pump cycling etc Table 1 3 1 2 Installation 1 2 1 Control...

Страница 7: ...PNP Bus ter Bus ter RS 485 Interface RS 485 N PS 485 69 P RS 485 68 Com RS 485 61 PNP Source NPN Sink ON Terminated OFF Unterminated ON 1 2 240V AC 3A Not present on all power sizes Do not connect shi...

Страница 8: ...Coated Coated Coated Coated Coated Coated Coated Coated Coated Table 1 4 Frequency Converter P15K P18K P22K P30K P37K P45K P55K P75K P90K Typical shaft output kW 15 18 22 30 37 45 55 75 90 IP20 Frame...

Страница 9: ...Digital Outputs 5 30 Terminal 27 Digital Output 5 31 Terminal 29 Digital Output 5 34 On Delay Digital Output 5 35 Off Delay Digital Output 5 4 Relays 5 40 Function Relay 5 41 On Delay Relay 5 42 Off...

Страница 10: ...25 06 Number of Pumps 25 2 Bandwidth Settings 25 20 Staging Bandwidth 25 21 Override Bandwidth 25 22 Fixed Speed Bandwidth 25 23 SBW Staging Delay 25 24 SBW Destaging Delay 25 25 OBW Time 25 27 Stage...

Страница 11: ...www danfoss com drives MI18I302 130R0267 MI18I302 Rev 2012 08 31...

Отзывы: