1.1.1 System Status and Operation

Only when lead pump is working, the frequency converter
can go into sleep mode. When the Cascade Controller is
enabled, the operation status for each pump and the
Cascade Controller is displayed by 

25-81, Pump Status

 and

25-80, Cascade Status

 on the LCP. Cascade Controller

information displayed includes:

Pumps Status, is a read out of the status for the
relays assigned to each pump. The display shows
pumps that are disabled, off, running on the
frequency converter or running on the mains/
motor starter.

Cascade Status, is a read out of the status for the
Cascade Controller. The display shows the
Cascade Controller is disabled, all pumps are
running off, fixed speed pumps are being
staged/de-staged and lead pump alternation is
occurring.

1.1.2 Start/Stop Conditions

See 

5-1* Digital Inputs

.

Digital input commands

Variable speed pump (lead)

Fixed speed pumps (lag)

Start (SYSTEM START/STOP)

Ramps up (if stopped and there is a
demand)

Staging (if stopped and there is a demand)

Lead Pump Start

Ramps up if SYSTEM START is active

Not affected

Coast (EMERGENCY STOP)

Coast to stop

Cut out (correspond relays, terminal 27/29
and 42/45)

External Interlock

Coast to stop

Cut out (built-in relays are de-energized)

Table 1.1 Commands Assigned to Digital Inputs

LCP keys

Variable speed pump (lead)

Fixed speed pumps (lag)

[Hand On]

Ramps up (if stopped by a normal stop
command) or stays in operation if already
running

Destaging (if running)

[Off]

Ramps down

Destaging

[Auto On]

Starts and stops according to commands via
terminals or serial bus cascade controller
only can work when drive in "Auto ON"
mode

Staging/Destaging

Table 1.2 Function of Keys on LCP

1.1.3 Cascade Controller Parameter Detail

Parameter

Range

Default

Function

25-00 Cascade
Controller

*[0] Disabled
[1] Enabled

*[0] Disabled Enable/disable

the cascade
controller which
is used for
staging multiple
pumps.

25-04 Pump
Cycling

*[0] Disabled
[1] Enabled

*[0] Disabled Select the

method for
determining the
order of cutting
in/out the fixed
speed pumps.

Parameter

Range

Default

Function

25-05 Fixed
Lead Pump

[0] No
*[1] Yes

*[1] Yes

Select if the lead
pump is fixed
(Yes) or can be
cycled (No).

25-06 Number
of Pumps

2 - Expres-
sionlimit (5)

*2

Set the total
number of
pumps including
the variable
speed pump.

VLT® HVAC Basic Drive Casca...

VLT

®

 HVAC Basic Drive Cascade Controller

2

MI18I302 - VLT

®

 is a registered Danfoss trademark

1

1

Содержание VLT HVAC

Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction VLT HVAC Basic Drive Cascade Controller...

Страница 2: ......

Страница 3: ...is 3 In this operation the run time between pumps is equalized reducing the required pump maintenance and increasing reliability and lifetime of the system The alternation of the lead pump can take p...

Страница 4: ...P Coast to stop Cut out correspond relays terminal 27 29 and 42 45 External Interlock Coast to stop Cut out built in relays are de energized Table 1 1 Commands Assigned to Digital Inputs LCP keys Vari...

Страница 5: ...he programmed time expires Parameter Range Default Function 25 42 Staging Threshold Expressionlimit 0 100 90 The percentage of maximum pump speed to stage on a fixed speed pump 25 43 Destagi ng Thresh...

Страница 6: ...an be reset by writing 0 25 90 Pump Interlock 0 Off 1 On 0 Off Choose the pump to interlock for e g service The pump will be taken out of any pump cycling etc Table 1 3 1 2 Installation 1 2 1 Control...

Страница 7: ...PNP Bus ter Bus ter RS 485 Interface RS 485 N PS 485 69 P RS 485 68 Com RS 485 61 PNP Source NPN Sink ON Terminated OFF Unterminated ON 1 2 240V AC 3A Not present on all power sizes Do not connect shi...

Страница 8: ...Coated Coated Coated Coated Coated Coated Coated Coated Coated Table 1 4 Frequency Converter P15K P18K P22K P30K P37K P45K P55K P75K P90K Typical shaft output kW 15 18 22 30 37 45 55 75 90 IP20 Frame...

Страница 9: ...Digital Outputs 5 30 Terminal 27 Digital Output 5 31 Terminal 29 Digital Output 5 34 On Delay Digital Output 5 35 Off Delay Digital Output 5 4 Relays 5 40 Function Relay 5 41 On Delay Relay 5 42 Off...

Страница 10: ...25 06 Number of Pumps 25 2 Bandwidth Settings 25 20 Staging Bandwidth 25 21 Override Bandwidth 25 22 Fixed Speed Bandwidth 25 23 SBW Staging Delay 25 24 SBW Destaging Delay 25 25 OBW Time 25 27 Stage...

Страница 11: ...www danfoss com drives MI18I302 130R0267 MI18I302 Rev 2012 08 31...

Отзывы: