7 Specifications
7.1 Power-dependent Specifications
7.1.1 VLT
®
HVAC Drive FC 102
Power range
N315
N355
N400
N450
N500
Drive modules
2
2
2
2
2
Rectifier configuration
12-pulse
6-pulse/12-pulse
High/normal load
NO
NO
NO
NO
NO
Output current [A]
Continuous (at 380–440 V)
588
658
745
800
880
Intermittent (60 s overload) at 400 V
647
724
820
880
968
Continuous (at 460/500 V)
535
590
678
730
780
Intermittent (60 s overload) at 460/500 V
588
649
746
803
858
Input current [A]
Continuous (at 400 V)
567
647
733
787
875
Continuous (at 460/500 V)
516
580
667
718
759
Power losses [W]
Drive modules at 400 V
5825
6110
7069
7538
8468
Drive modules at 460 V
4998
5964
6175
6609
7140
AC bus bars at 400 V
550
555
561
565
575
AC bus bars at 460 V
548
551
556
560
563
DC bus bars during regeneration
93
95
98
101
105
Maximum cable size [mm
2
(mcm)]
Mains
4x120 (250)
4x150 (300)
Motor
4x120 (250)
4x150 (300)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
1)
4x120 (250)
4x150 (300)
6x120 (250)
Maximum external mains fuses
6-pulse configuration
–
–
–
–
600 V, 1600 A
12-pulse configuration
700 A, 600 V
–
Table 7.1 FC 102, 380–480 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302
Danfoss A/S © 08/2017 All rights reserved.
45