6.5 Testing the Motor Operation
1.
Press [Main Menu] twice on the LCP.
2.
Press the navigation keys and the [OK] key to
navigate to
parameter group 1-** Load and Motor
and press [OK].
3.
Navigate to
parameter 1-23 Motor Frequency
and
enter the frequency from the motor nameplate.
4.
Navigate to
parameter 1-23 Motor Frequency
and
enter the current from the motor nameplate.
5.
Navigate to
parameter 1-25 Motor Nominal Speed
and enter the speed from the motor nameplate.
6.
Press [Status] to return to the operational display.
7.
Press [Hand On].
8.
Press [
▲
] to accelerate the motor.
9.
Press [
▼
] to decelerate the motor.
10.
Press [Off].