Control card performance
Scan interval
5 ms
Control card, USB serial communication
USB standard
1.1 (full speed)
USB plug
USB type B device plug
NOTICE
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB
connector on the drive or an isolated USB cable/converter.
9.7 Fuses
Fuses ensure that possible damage to the drive is limited to damages inside the unit. To ensure compliance with EN 50178,
use identical Bussmann fuses as replacements. Refer to
.
NOTICE
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Input voltage (V)
Bussmann part number
380–500
170M7309
525–690
170M7342
Table 9.5 Fuse Options
The fuses listed in
are suitable for use on a circuit capable of delivering 100000 A
rms
(symmetrical), depending on
the drive voltage rating. With the proper fusing, the drive short-circuit current rating (SCCR) is 100000 A
rms
. E1h and E2h
drives are supplied with internal drive fusing to meet the 100 kA SCCR. E3h and E4h drives must be fitted with Type aR
fuses to meet the 100 kA SCCR.
NOTICE
DISCONNECT SWITCH
All units ordered and supplied with a factory-installed disconnect switch require Class L branch circuit fusing to meet
the 100 kA SCCR for the drive. If a circuit breaker is used, the SCCR rating is 42 kA. The specific Class L fuse is
determined by the input voltage and power rating of the drive. The input voltage and power rating is found on the
product nameplate. See
.
Input voltage (V)
Power rating (kW)
Short circuit rating (A)
Required protection
380–480
355–450
42000
Circuit breaker
100000
Class L fuse, 800 A
380–480
500–560
42000
Circuit breaker
100000
Class L fuse, 1200 A
525–690
450–630
42000
Circuit breaker
10000
Class L fuse, 800 A
525–690
710–800
42000
Circuit breaker
100000
Class L fuse, 1200 A
Specifications
VLT® HVAC Drive FC 102
82
Danfoss A/S © 01/2017 All rights reserved.
MG16O102
9
9
Содержание VLT HVAC Drive FC 102
Страница 2: ......
Страница 113: ...Index Operating Guide MG16O102 Danfoss A S 01 2017 All rights reserved 111 ...