5.
Select
parameter 3-02 Minimum Reference
.
Set the minimum internal drive reference to 0 Hz
and press [OK].
130BF727.10
Q3-21
3-02 Minimum Reference
0.000 Hz
14.7% 0.00A 1(1)
Analog Reference
Illustration 6.6
Parameter 3-02 Minimum Reference
6.
Select
parameter 3-03 Maximum Reference
.
Set the maximum internal drive reference to
60 Hz and press [OK].
130BF728.10
Q3-21
3-03 Maximum Reference
50.000 Hz
14.7% 0.00A 1(1)
Analog Reference
Illustration 6.7
Parameter 3-03 Maximum Reference
7.
Select
parameter 6-10 Terminal 53 Low Voltage
.
Set the minimum external voltage reference on
terminal 53 at 0 V and press [OK].
130BF729.10
Q3-21
6-10 Terminal 53 Low
Voltage
0.00 V
14.7% 0.00A 1(1)
Analog Reference
Illustration 6.8
Parameter 6-10 Terminal 53 Low Voltage
8.
Select
parameter 6-11 Terminal 53 High Voltage
.
Set maximum external voltage reference on
terminal 53 at 10 V and press [OK].
130BF730.10
Q3-21
6-11 Terminal 53 High
Voltage
10.00 V
14.7% 0.00A 1(1)
Analog Reference
Illustration 6.9
Parameter 6-11 Terminal 53 High Voltage
9.
Select
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value
. Set minimum speed reference on terminal
53 at 20 Hz and press [OK].
130BF731.10
Q3-21
14.7 % 0.00 A 1(1)
Analog Reference
6 - 14 Terminal 53 Low
Ref./Feedb. Value
000020.000
Illustration 6.10
Parameter 6-14 Terminal 53 Low Ref./Feedb.
Value
10.
Select
parameter 6-15 Terminal 53 High Ref./Feedb.
Value
. Set maximum speed reference on terminal
53 at 50 Hz and press [OK].
130BF732.10
Q3-21
14.7 % 0.00 A 1(1)
Analog Reference
6 - 15 Terminal 53 High
Ref./Feedb. Value
50.000
Illustration 6.11
Parameter 6-15 Terminal 53 High Ref./Feedb.
Value
Commissioning
VLT® HVAC Drive FC 102
50
Danfoss A/S © 01/2017 All rights reserved.
MG16O102
6
6