Parameter 5-19 Terminal 37 Safe Stop

[6]

PTC 1 &
Relay Alarm

If the motor temperature is too high, or if a
PTC failure occurs, the MCB 112 activates the
STO of the frequency converter. Terminal 37
goes LOW (active), and digital input 33 goes
HIGH (active). This parameter decides the
consequence of the Safe Torque Off (STO).
With this selection, the frequency converter
coasts and the LCP displays 

Alarm 71 PTC 1

Safe Stop

. Reset the frequency converter

manually from LCP, digital input, or fieldbus
when the conditions of the PTC are
acceptable again (the motor temperature has
dropped). An emergency stop can also
activate STO. Terminal 37 goes LOW (active),
but MCB 112 X44/10 does not trigger digital
input 33 as the MCB 112 did not need to
activate the STO. Therefore, digital input 33
remains HIGH (inactive).

5-15 Terminal 33 Digital Input

[80] PTC Card 1 Connects the digital input of terminal 33 to

the MCB 112, which enables the MCB 112 to
indicate when STO has been activated from
here.

Table 5.2 Programming Example 2

Alternatively, 

parameter 5-19 Terminal 37 Safe Stop

 could be

set to 

[7] PTC 1 & Relay Warning

. Selecting this option

causes an automatic restart when the conditions of the
PTC circuit and/or emergency stop circuit have returned to
normal. The selection depends on customer demands. Also,
the setting of 

parameter 5-19 Terminal 37 Safe Stop

 could

be 

[8] PTC 1 & Relay A/W

 or 

[9] PTC 1 & Relay W/A

, which is

a combination of alarms and warnings. The selection
depends on customer demands.

NOTICE

Selections 

[4] PTC 1 Alarm

 to 

[9] PTC 1 & Relay W/A

 in 

parameter 5-19 Terminal 37 Safe Stop

 are only visible if

the MCB 112 is plugged into the B-option slot.

NOTICE

Take care that the digital input set to 

[80] PTC Card 1

 is

not also configured as thermistor resource (motor
overload protection) in 

1-93 Thermistor Resource

.

Application Examples

VLT

®

 PTC Thermistor Card MCB 112

18

Danfoss A/S © 01/2015 All rights reserved.

MG33V302

5

5

Содержание VLT HVAC Drive FC 102

Страница 1: ...At the end of this document you will find links to products related to this catalog You can go directly to our shop by clicking HERE HERE...

Страница 2: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT PTC Thermistor Card MCB 112 VLT HVAC Drive FC 102 VLT AQUA Drive FC 202 VLT AutomationDrive FC 302 vlt drives danfoss com...

Страница 3: ......

Страница 4: ...8 Symbols Abbreviations and Conventions 6 2 Safety 7 2 1 Safety Symbols 7 2 2 Qualified Personnel 7 2 3 Safety Precautions 7 3 Installation 9 3 1 Safety Instructions 9 3 2 Installation of Sensor Circ...

Страница 5: ...Warning Code List 19 6 2 2 Description of Alarm Word Warning Word and Extended Status Word 19 7 Technical Specifications 21 7 1 Mains Supply 21 7 2 Control Inputs and Outputs 21 7 3 Ambient Condition...

Страница 6: ...tions via email to techcom_change_request danfoss com including a reference to the document version Table 1 1 shows the document version and the changes applied Edition Remarks MG33V3xx Replaces MG33V...

Страница 7: ...on device can be used 1 5 4 ATEX ETR Thermal Monitoring NOTICE The ATEX ETR thermal monitoring function only applies to Ex e and Ex n motors and is only available for VLT AutomationDrive FC 302 freque...

Страница 8: ...hazardous zone The Ex n motor must be approved for operation in hazardous zones ATEX Zone 2 22 in combination with frequency conveters The motor must be certified for the particular harzardous zone N...

Страница 9: ...ge probability of failure on demand value used for low demand operation SFF EN IEC 61508 Safe failure fraction percentage of safe failures and dangerous detected failures of a safety function or a sub...

Страница 10: ...tifying safety functions required and allocating SIL to each of the functions Other subsystems and the validity of signals and commands from those subsystems Designing appropriate safety related contr...

Страница 11: ...uipment or property damage The motor can start by means of an external switch a serial bus command an input reference signal from the LCP after a cleared fault condition or after the motor and motor t...

Страница 12: ...m Permissible Length of Sensor Circuit Wires NOTICE Route the sensor circuit wires as separate control wires It is not allowed to use wires from the supply cable or any other mains cables Use screened...

Страница 13: ...erminal on the control card X44 10 Logic output signals the status in case of failure Table 3 2 Terminal Definitions CAUTION RISK OF OVERVOLTAGE Long cables voltage peaks or increased mains voltage ma...

Страница 14: ...e 2 Fit the extended LCP frame and terminal cover 3 Fit the LCP or blind cover in the extended LCP frame 4 To indicate that the ATEX module is integrated apply the delivered sticker to the front of th...

Страница 15: ...Pay attention to the ambient conditions in chapter 7 Technical Specifications 4 1 1 Monitoring Sensor Resistance 1 Short circuit 2 Tripping is not saved and is not protected against 0 voltage Illustra...

Страница 16: ...R PWM CONV 3kHz l 1 5XIM N tOL 10s tCOOL 10min MIN FREQ 5Hz MAX FREQ 85 Hz PWM CONTROL f Hz Ix IM N PTC C DIN 44081 82 Manufacture xx EN 60079 0 EN 60079 7 1180 Ex e ll T3 5 15 25 50 85 0 4 0 8 1 0 1...

Страница 17: ...permitted for a limited period of 60 s The actual thermal overload is calculated based on the ETR function selected in 1 90 Motor Thermal Protection and is displayed in 16 18 Motor Thermal Running abo...

Страница 18: ...he PTC options to get the full benefit from the alarm handling Options 4 PTC 1 Alarm and 5 PTC 1 Warning are relevant when the MCB 112 is the only interrupt device using STO Options 6 PTC 1 Relay A to...

Страница 19: ...utton through a safety relay to terminal 37 Coasts the frequency converter when Safe Torque Off is activated terminal 37 off When Safe Torque Off circuit is re established the frequency converter cont...

Страница 20: ...s when the conditions of the PTC are acceptable again temperature of motor has dropped 5 15 Terminal 33 Digital Input 80 PTC Card 1 Connects the digital input of terminal 33 in the FC 302 to the MCB 1...

Страница 21: ...gital input of terminal 33 to the MCB 112 which enables the MCB 112 to indicate when STO has been activated from here Table 5 2 Programming Example 2 Alternatively parameter 5 19 Terminal 37 Safe Stop...

Страница 22: ...ed To resume normal operation apply 24 V DC to terminal 37 then send a reset signal via bus digital I O or by pressing Reset Warning 68 Safe Stop STO has been activated Normal operation is resumed whe...

Страница 23: ...ies that STO is only triggered from MCB 112 Activated Not activated Function Number X44 10 DI STO terminal 37 PTC 1 Alarm 4 PTC 1 Warning 5 PTC 1 Relay A 6 PTC 1 Relay W 7 PTC 1 Relay A W 8 PTC 1 Rela...

Страница 24: ...tage level 0 24 V DC Voltage Low 0 PNP 4 V DC High 1 PNP 20 V DC Current 60 mA Logic out X44 10 Output PNP transistor Logical voltage level 0 24 V DC Voltage Low 0 PNP 5 V DC High 1 PNP 10 V DC Curren...

Страница 25: ...0 SIL 2 Type A device Table 7 1 Safety Integrity Level SIL EN 61508 MCB 112 MTBF SFF SD SU DD DU Ta 40 C 44 years 96 5 2103 x 10 9 h 41 8 x 10 9 h 1 23 x 10 9 h 81 4 x 10 9 h Table 7 2 Safety related...

Страница 26: ...t atmosphere 3 7 Explosive gas atmosphere 3 7 Extended status word 19 F Frequency converter Requirement 13 I Intended use 3 M Maintenance 19 Manual reset 15 Marking D 3 Marking G 3 Maximum current 5 M...

Страница 27: ...C 60529 7 8 10 ISO 13849 2 7 Sticker 4 Symbols 6 T Terminals Safe stop T37 10 T1 12 T2 12 X44 1 21 X44 10 4 11 15 19 20 21 X44 12 4 10 12 21 X44 2 21 Test 12 Testing conditions 21 Thermal limitation c...

Страница 28: ...Index Operating Instructions MG33V302 Danfoss A S 01 2015 All rights reserved 25...

Страница 29: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Страница 30: ...l products Estimated delivery time enquiry in real time Logistics systems for the shipment of materials almost anywhere in the world Purchasing management order record and tracking of shipments To acc...

Отзывы: