5-19 Terminal 37 Safe Stop
To configure the Safe Torque Off functionality, set this parameter.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a fieldbus, digital I/O, or by pressing [Reset]
on the LCP). When the MCB 112 is mounted, configure the PTC
options to get the full benefit from the alarm handling.
Option:
Function:
[4]
PTC 1 Alarm
Coasts the frequency converter
when Safe Torque Off is activated.
Manual reset from LCP, digital input,
or fieldbus.
[5]
PTC 1 Warning
Coasts the frequency converter
when Safe Torque Off is activated
(terminal 37 off). When Safe Torque
Off circuit is re-established, the
frequency converter continues
without manual reset, unless a
digital input set to
[80] PTC Card 1
is
still enabled.
[6]
PTC 1 & Relay A This option is used when the PTC
option gates with a stop button
through a safety relay to terminal
37. Coasts the frequency converter
when Safe Torque Off is activated.
Manual reset from LCP, digital input,
or fieldbus.
[7]
PTC 1 & Relay W This option is used when the PTC
option gates with a stop button
through a safety relay to terminal
37. Coasts the frequency converter
when Safe Torque Off is activated
(terminal 37 off). When Safe Torque
Off circuit is re-established, the
frequency converter continues
without manual reset, unless a
digital input set to
[80] PTC Card 1
is
still enabled.
[8]
PTC 1 & Relay
A/W
This option makes it possible to use
a combination of alarm and warning.
[9]
PTC 1 & Relay
W/A
This option makes it possible to use
a combination of alarm and warning.
NOTICE
Selecting
Auto Reset/Warning
enables automatic restart
of the frequency converter.
Function
Num-
ber
PTC
Relay
No Function
[0]
–
–
Safe Stop Alarm
[1]*
–
Safe Stop [A68]
Safe Stop
Warning
[3]
–
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop
[A71]
–
PTC 1 Warning
[5]
PTC 1 Safe Stop
[W71]
–
PTC 1 & Relay A
[6]
PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay
A/W
[8]
PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay
W/A
[9]
PTC 1 Safe Stop
[W71]
Safe Stop [A68]
Table 4.5 Overview of Functions, Alarms, and Warnings
W means warning and A means alarm. For further information, see
Alarms and Warnings in the Troubleshooting section in the design
guide or the operating instructions.
A dangerous failure related to Safe Torque Off issues
Alarm
72 Dangerous Failure
.
Refer to
Table 6.1
.
Commissioning
VLT
®
PTC Thermistor Card MCB 112
16
Danfoss A/S © 01/2015 All rights reserved.
MG33V302
4
4
Содержание VLT HVAC Drive FC 102