Surroundings
Enclosure
IP20
Enclosure kit available.
IP21, TYPE 1
Vibration test
1.0 g
Max. relative humidity
5%–95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1-H5
Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame H6-H10
Class 3C2
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6-H10
Class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
See max. output current at 104/122 °F [40/50
°
C] in
chapter 1.7.2 Line Power Supply 3x380–480 V AC
Derating for high ambient temperature, see .
Minimum ambient temperature during full-scale operation
32 °F [0
°
C]
Minimum ambient temperature at reduced performance, enclosure frame H1-H5
-4 °F [-20
°
C]
Minimum ambient temperature at reduced performance, enclosure frame H6-H10
14 °F [-10
°
C]
Temperature during storage/transport
-22 to +149/158 °F [-30 to +65/70
°
C]
Maximum altitude above sea level without derating
3,300 ft [1,000 m]
Maximum altitude above sea level with derating
10,000 ft [3,000 m]
Derating for high altitude, see
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards,
Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
61000-4-5, EN 61000-4-6
1.8 Special Conditions
1.8.1 Derating for Ambient Temperature and Switching Frequency
The ambient temperature measured over 24 hours should be at least 9 °F [5
°
C] lower than the max. ambient temperature.
If the adjustable frequency drive is operated at a high ambient temperature, the continuous output current should be
decreased. For derating curve, see
VLT
®
HVAC Basic Design Guide
.
1.8.2 Derating for Low Air Pressure
The cooling capability of air is decreased at low air pressure. For altitudes above 6,600 feet [2 km], contact Danfoss
regarding PELV. Below 3,300 ft [1,000 m] altitude, no de-rating is necessary, but above 3,281 ft [1,000 m], the ambient
temperature or the maximum output current should be decreased. Decrease the output by 1% per 330 ft [100 m] altitude
above 3,300 ft [1,000 m] or reduce the max. ambient temperature by 1
°
per 660 ft [200 m].
1.9 Options for VLT
®
HVAC Basic Drive FC 101
For options, see the
VLT
®
HVAC Basic Drive FC 101 Design Guide
.
1.10 MCT 10 Support
MCT 10 Set-up Software information is available at:
www.danfoss.com/BusinessAreas/DrivesSolutions/fc101driveupdates
Quick Guide
Quick Guide
46
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
MG18A522
1
1