Power (hp [kW])
Torque (in-lb [Nm])
Frame
IP class
3x380–480 V
Line
Motor
DC
connection
Control
terminals
Ground
Relay
I2
IP54
1– 5 [0.75–4.0]
12.39 [1.4]
7.08 [0.8]
7.08 [0.8]
4.43 [0.5]
7.08 [0.8]
4.43 [0.5]
I3
IP54
7.5–10 [5.5–7.5]
12.39 [1.4]
7.08 [0.8]
7.08 [0.8]
4.43 [0.5]
7.08 [0.8]
4.43 [0.5]
I4
IP54
15–25 [11–18.5]
12.39 [1.4]
7.08 [0.8]
7.08 [0.8]
4.43 [0.5]
7.08 [0.8]
4.43 [0.5]
I6
IP54
30–50 [22–37]
0.18 [4.5]
0.18 [4.5]
-
4.43 [0.5]
26.55 [3]
5.31 [0.6]
I7
IP54
60–75 [45–55]
88.51 [10]
88.51 [10]
-
4.43 [0.5]
26.55 [3]
5.31 [0.6]
I8
IP54
100–125 [75–90] 123.91/212.42
[14/24]
1
123.91/212.42
[14/24]
1
-
4.43 [0.5]
26.55 [3]
5.31 [0.6]
Table 1.8 Enclosure I1-I8
Power (hp [kW])
Torque (in-lb [Nm])
Frame
IP class
3x525–600 V
Line
Motor
DC
connection
Control
terminals
Ground
Relay
H9
IP20
3–10 [2.2–7.5]
15.93 [1.8]
15.93 [1.8]
Not
recommended
4.43 [0.5]
26.55 [3]
5.31 [0.6]
H10
IP20
15–20 [11–15]
15.93 [1.8]
15.93 [1.8]
Not
recommended
4.43 [0.5]
26.55 [3]
5.31 [0.6]
H6
IP20
25–40 [18.5–30]
0.18 [4.5]
0.18 [4.5]
-
4.43 [0.5]
26.55 [3]
4.43 [0.5]
H7
IP20
50–75 [37–55]
88.51 [10]
88.51 [10]
-
4.43 [0.5]
26.55 [3]
4.43 [0.5]
H8
IP20
100–125 [75–90] 123.91/212.42
[14/24]
1
123.91/212.42
[14/24]
1
-
4.43 [0.5]
26.55 [3]
4.43 [0.5]
Table 1.9 Details of Tightening Torques
1
Cable dimensions
≤
0.1472 in
2
[95 mm
2
]
2
Cable dimensions >0.1472 in
2
[95 mm
2
]
1.3.4 Connecting to Line Power and Motor
The adjustable frequency drive is designed to operate all standard three-phased asynchronous motors. For maximum cross-
section on wires, see
chapter 1.7 General Specifications
.
•
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both
the decoupling plate and the motor metal.
•
Keep motor cable as short as possible to reduce the noise level and leakage currents.
•
For further details on mounting of the decoupling plate, see
FC 101 Decoupling Plate Mounting Instruction
.
•
Also see
EMC-Compatible Installation in the VLT
®
HVAC Basic Design Guide
.
1.
Mount the ground wires to the ground terminal.
2.
Connect the motor to terminals U, V and W.
3.
Mount line power supply to terminals L1, L2 and L3 and tighten.
Quick Guide
Quick Guide
8
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
MG18A522
1
1