Parameter
Option
Default
Function
1-20 Motor Power
0.12–110 kW/0.16–150 hp
Size related
Enter motor power from nameplate data
1-22 Motor Voltage
50.0–1000.0 V
Size related
Enter motor voltage from nameplate data
1-23 Motor Frequency
20.0–400.0 Hz
Size related
Enter motor frequency from nameplate data
1-24 Motor Current
0.01–10000.00 A
Size related
Enter motor current from nameplate data
1-25 Motor Nominal Speed
100.0–9,999.0 RPM
Size related
Enter motor nominal speed from nameplate
data
1-26 Motor Cont. Rated Torque
0.1–1000.0
Size related
This parameter is available only when
1-10 Motor Construction Design is set to
[1]
PM, non-salient SPM
.
NOTICE!
Changing this parameter will affect
settings of other parameters
1-29 Automatic Motor Adaption
(AMA)
See
1-29 Automatic Motor
Adaption (AMA)
Off
Performing an AMA optimizes motor
performance.
1-30 Stator Resistance (Rs)
0.000–99.990
Size related
Set the stator resistance value
1-37 d-axis Inductance (Ld)
0–1000
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance
cannot be found by performing an AMA.
1-39 Motor Poles
2–100
4
Enter the number of motor poles
1-40 Back EMF at 1000 RPM
10–9000
Size related
Line-Line RMS back EMF voltage at 1000 RPM
1-73 Flying Start
When PM is selected, Flying Start is enabled
and cannot disable
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select
[1] Enable
to enable the drive to catch
a motor spinning due to line drop-out. Select
[0] Disable
if this function is not required.
When is enabled
1-71 Start Delay
and
1-72 Start Function
have no function. is active
in VVC
plus
mode only
3-02 Minimum Reference
-4999–4999
0
The minimum reference is the lowest value
obtainable by summing all references.
3-03 Maximum Reference
-4999–4999
50
The maximum reference is the lowest
obtainable by summing all references.
3-41 Ramp 1 Ramp Up Time
0.05–3600.0 s
Size related
Ramp-up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected;
ramp-up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected
3-42 Ramp 1 Ramp Down Time
0.05–3600.0 s
Size related
Ramp-down time from rated 1-23 Motor
Frequency to 0 if Asynchron motor is selected;
ramp-down time from 1-25 Motor Nominal
Speed to 0 if PM motor is selected.
4-12 Motor Speed Low Limit [Hz]
0.0–400 Hz
0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0.0–400 Hz
65 Hz
Enter the maximum limit for high speed
4-19 Max Output Frequency
0-400
Size related
Enter the maximum output frequency value
5-40 Function Relay [0] Function
relay
See 5-40 Function Relay
Alarm
Select the function to control output relay 1.
5-40 Function Relay [1] Function
relay
See 5-40 Function Relay
Drive running
Select the function to control output relay 2.
6-10 Terminal 53 Low Voltage
0–10 V
0.07 V
Enter the voltage that corresponds to the low
reference value.
Quick Guide
Quick Guide
MG18A522
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
25