Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature
•
The frequency converter is protected against short-circuits between motor terminals U, V, W.
•
If a motor phase is missing, the frequency converter trips and issues an alarm.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
•
The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains Supply (L1, L2, L3)
Supply voltage
200-240V
±
10%
Supply voltage
380-480V
±
10%
Supply frequency
50/60Hz
Max. imbalance temporary between mains phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
) near unity
(> 0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5
Max. 2 times/min.
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8
Max. 1 time/min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor Output (U, V, W):
Output voltage
0 - 100% of supply voltage
Output frequency
0-200 Hz (VVC+), 0-400 Hz (u/f)
Switching on output
Unlimited
Ramp times
0.05 - 3600 sec.
Cable Lengths and Cross Sections:
Max. motor cable length, screened/armoured (EMC correct installation)
See chapter EMC test results
Max. motor cable length, unscreened/unarmoured
50m
Max. cross section to motor, mains*
Cross section DC terminals for filter feedback on enclosure frame H1-H3
4mm
2
/11AWG
Cross section DC terminals for filter feedback on enclosure frame H4-H5
16mm
2
/6AWG
Maximum cross section to control terminals, rigid wire
2.5mm
2
/14AWG)
Maximum cross section to control terminals, flexible cable
2.5mm
2
/14AWG)
Minimum cross section to control terminals
0.05mm
2
/30AWG
*See tables for mains supply for more information!
Digital inputs:
Programmable digital inputs
4
Terminal number
18, 19, 27, 29
Logic
PNP or NPN
Voltage level
0-24V DC
Voltage level, logic '0' PNP
< 5V DC
Voltage level, logic '1' PNP
> 10V DC
Voltage level, logic '0' NPN
> 19V DC
Voltage level, logic '1' NPN
< 14V DC
Maximum voltage on input
28V DC
Input resistance, R
i
Approx. 4 k
Digital input 29 as thermistor input
Fault: > 2.9k
Ω
and no fault: < 800
Ω
Quick Guide
VLT HVAC Basic Drive FC 101 Quick Guide
28
MG.18.A1.02 - VLT
®
is a registered Danfoss trademark
1
1