1.3.8 Control Terminals
IP20 200-240V 0,25-11kW and IP20 380-480V 0,37-22kW:
130BB622.10
Illustration 1.3 Location of control terminals
1.
Place a screwdriver behind the terminal cover to
activate snap.
2.
Tilt the screwdriver outwards to open the cover.
IP20 380-480V 30-90kW.
130BB624.10
1.
Place a screwdriver behind the terminal cover to
activate snap.
2.
Tilt the screwdriver outwards to open the cover.
Digital input 18, 19 and 27 mode is set in par. 5-00 (PNP is
default value) and digital input 29 mode is set in par. 5-03
(PNP is default value).
Control terminals:
The illustration below shows all control terminals of the
frequency converter. Applying Start (term. 18), connection
between terminal 12-27 and an analog reference (term. 53 or
54 and 55) make the frequency converter run.
18 19
12 20 55
27 29 42 45 50 53 54
DIGI IN
DIGI IN
DIGI IN
DIGI IN
61 68 69
N
P
COMM. GND
+24V
0/4-20mA A OUT / DIG OUT
0/4-20mA A OUT / DIG OUT
GND
GND
10V/20mA IN
10V/20mA IN
10V OUT
130BB625.10
BUS TER.
OFF
ON