Frequency converter
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output (KW)
15
18.5
22
30
37
45
55
75
90
Typical shaft output (HP)
20
25
30
40
50
60
75
100
125
IP20 frame
H4
H5
H5
H6
H6
H6
H7
H7
H8
Max. cable size in terminals (mains, motor)
[mm
2
/AWG]
16/6
16/6
16/6
35/2
35/2
35/2
50/1
95/0
120/250
MCM
Output current
RELAY 2
130BB632.10
40
°
C ambient temperature
Continuous (3x380-440V)
[A]
31
37
42.5
61
73
90
106
147
177
Intermittent (3x380-440V)
[A]
34
40.7
46.8
67.1
80.3
99
116
161
194
Continuous (3x440-480V)
[A]
27
34
40
52
65
80
105
130
160
Intermittent (3x440-480V)
[A]
29.7
37.4
44
57.2
71.5
88
115
143
176
Max. input current
RELAY 2
130BB633.10
40
°
C ambient temperature
Continuous (3x380-440V)
[A]
29.9
35.2
41.5
57
70
84
103
140
166
Intermittent (3x380-440V)
[A]
32.9
38.7
45.7
62.7
77
92.4
113
154
182
Continuous (3x440-480V)
[A]
24.7
29.3
34.6
49-46
61-57
73-68
89-83
121-113 143-133
Intermittent (3x440-480V)
[A]
27.2
32.2
38.1
54-50
67-62
80-74
98-91
133-124 157-146
Max. mains fuses
See section
Fuses
Estimated power loss [W], Best case/typical
1)
Weight enclosure IP20 [kg]
7.9
9.5
9.5
24.5
24.5
24.5
36
36
51
Efficiency [%], Best case/Typical 1
1)
At rated load conditions
1.7.3 EMC Test Results
The following test results have been obtained using a system with a frequency converter, a screened control cable, a control box
with potentiometer, as well as a motor screened cable.
RFI filter type
Conducted emission.
Maximum shielded cable length
Radiated emission
Industrial enviroment
Housing, trades and light Industries Industrial environment
Standard
EN55011 Class A2 EN55011 Class A1 EN55011 Class B
EN55011 Class A1
0.25-1.5kW, 200-240V IP20
25m
25m
-
Yes
2.2kW, 200-240V
IP20
25m
25m
-
Yes
3.7kW, 200-240V
IP20
25m
25m
-
Yes
5.5-7.5kW, 200-240V
IP20
25m
-
Yes
11kW, 200-240V
IP20
25m
-
Yes
0.37-1.5kW, 380-480V IP20
25m
25m
-
Yes
2.2-4kW, 380-480V
IP20
25m
25m
-
Yes
5.5-7.5 kW, 380-480V IP20
25m
25m
-
Yes
11-15kW, 380-480V
IP20
25m
-
Yes
18-22kW, 380-480V
IP20
25m
-
Yes
30-45kW, 380-480V
IP20
25m
-
55-75kW, 380-480V
IP20
25m
-
90kW, 380-480V
IP20
25m
-
Quick Guide
VLT HVAC Basic Drive FC 101 Quick Guide
MG.18.A1.02 - VLT
®
is a registered Danfoss trademark
27
1
1
Содержание VLT HVAC Basic Drive FC 10
Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT HVAC Basic Drive FC 101...
Страница 32: ...www danfoss com drives MG18A102 130R0192 MG18A102 Rev 2010 06 02...
Страница 33: ......