Relay output
Programmable relay output
1
Relay 01 Terminal number
01-03 (break), 01-02 (make)
Max. terminal load (AC-1)
1)
on 01-02 (NO) (Resistive load)
250 V AC, 2 A
Max. terminal load (AC-15)
1)
on 01-02 (NO) (Inductive load @ cosφ 0.4)
250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-02 (NO) (Resistive load)
30 V DC, 2 A
Max. terminal load (DC-13)
1)
on 01-02 (NO) (Inductive load)
24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 01-03 (NC) (Resistive load)
250 V AC, 2 A
Max. terminal load (AC-15)
1)
on 01-03 (NC) (Inductive load @ cosφ 0.4)
250 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 01-03 (NC) (Resistive load)
30 V DC, 2 A
Min. terminal load on 01-03 (NC), 01-02 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
1)
IEC 60947 part 4 and 5
Control card, 10 V DC output
Terminal number
50
Output voltage
10.5 V ±0.5 V
Max. load
25 mA
NOTICE
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and other
high-voltage terminals.
Surroundings
Enclosure
IP20
Enclosure kit available
IP21, TYPE 1
Vibration test
1.0 g
Max. relative humidity
5%-95 % (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated
class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Max. 40 °C
Derating for high ambient temperature, see chapter 4.2.2 Derating for Ambient Temperature
Minimum ambient temperature during full-scale operation
0 °C
Minimum ambient temperature at reduced performance
- 10 °C
Temperature during storage/transport
-25 to +65/70 °C
Maximum altitude above sea level without derating
1000 m
Maximum altitude above sea level with derating
3000 m
Derating for high altitude, see chapter 4.2 Special Conditions
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See chapter 4.2 Special Conditions
Specifications
VLT
®
Micro Drive FC 51 Design Guide
88
MG02K302 - Rev. 2013-12-03
9
9
Содержание VLT FC51
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Micro Drive FC 51...