Normal overload 150% or 1 min
Frequency converter
Typical Shaft Output [kW]
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
P22K
22
Typical Shaft Output [HP]
7.5
10
15
20
25
30
IP 20
Frame
M3
Frame
M3
Frame
M4
Frame
M4
Frame
M5
Frame
M5
Output current
Continuous (3x380-440 V) [A]
12.0
15.5
23.0
31.0
37.0
42.0
Intermittent (3x380-440 V) [A]
18.0
23.5
34.5
46.5
55.5
63.0
Continuous (3x440-480 V) [A]
11.0
14.0
21.0
27.0
34.0
40.0
Intermittent (3x440-480 V) [A]
16.5
21.3
31.5
40.5
51.0
60.0
Max. cable size:
(mains, motor) [mm
2
/AWG]
4/10
16/6
Max. input current
Continuous (3x380-440 V) [A]
19.2
24.8
33.0
42.0
34.7
41.2
Intermittent (3x380-440 V) [A]
27.4
36.3
47.5
60.0
49.0
57.6
Continuous (3x440-480 V) [A]
16.6
21.4
29.0
36.0
31.5
37.5
Intermittent (3x440-480 V) [A]
23.6
30.1
41.0
52.0
44.0
53.0
Max. mains fuses [A]
See
Environment
Estimated power loss [W], Best case/
Typical
1)
131.0/
166.8
175.0/
217.5
290.0/
342.0
387.0/
454.0
395.0/
428.0
467.0/
520.0
Weight enclosure IP20 [kg]
3.0
3.0
Efficiency [%], Best case/Typical
1)
98.0/
97.5
98.0/
97.5
97.8/
97.4
97.7/
97.4
98.1/
98.0
98.1/
97.9
Table 9.4 Mains Supply 3x380-480 V AC
1)
At rated load conditions.
Specifications
VLT
®
Micro Drive FC 51 Design Guide
MG02K302 - Rev. 2013-12-03
85
9
9
Содержание VLT FC51
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Micro Drive FC 51...
Страница 2: ......